As per our discussion for the installation of the Gel filled cable to be installed under slab then up
and under ITE room floor.
, Reference Art.645, Where IT room raised floors are not treated the same as a plenum since ITE
rooms may have their own dedicated HV AC system or may share a common system provided
automatic ducts are installed to shut off circulation incase of smoke as per Art 645.4(2) and
645.5(0)(3). Therefore this installation would be approved.
Note: Cable shall be fire rated and end of conduits and sleeves shall be fire caulked.