HomeMy WebLinkAboutPermit Correspondence 2004-1-1 ~7#~ -Z/JZ~X:16/-€-# ," Chip As per our discussion for the installation of the Gel filled cable to be installed under slab then up and under ITE room floor. , Reference Art.645, Where IT room raised floors are not treated the same as a plenum since ITE rooms may have their own dedicated HV AC system or may share a common system provided automatic ducts are installed to shut off circulation incase of smoke as per Art 645.4(2) and 645.5(0)(3). Therefore this installation would be approved. Note: Cable shall be fire rated and end of conduits and sleeves shall be fire caulked. Dave Gadomski Building Inspector III ( Electrical) , 541-726-3663 541-726-3676 Fax dgadomski@ci,springfield.or.us