Loading...
HomeMy WebLinkAboutNotes, Work PLANNER 6/15/2011 . . TENTATIVE SITE PLAN REVIEW APPLICATION PRE-SUBMITTAL CHECKLIST Deputy Fire Marshal: Gilbert Gordon Case #: PREll-00013 FIRE o Site Plan Complete Incomplete See Fire Note(s) rgJ [;j On-site vehicular circulation o Improvement and Public Utilities Plan Complete Incomplete See Fire Note(s) fgj fi;:il ~ Location of existing and required fire hydrants and similar public facilities Fire Notes: 1. Additional comments not related to the completeness of the application: a. The construction fence shall go around the fire hydrant so as not to impede fire fighter access to it. The fence shall maintain a minimum 3 foot clear width around the circumference of the fire hydrant meeting 2010 Springfield Fire Code 507.5.5. This also goes for vegetation encroaching on the hydrant space. b. Provide an additional gate on the north side near the northeast corner. The purpose is to keep water supply hose lay distances to within 600 feet on the west side of the Fred Meyer building to its northwest corner per 2010 Springfield Fire Code 507.5.1, Exception 2. c. Provide public works locks for the construction gates to maintain fire access to the west side of the Fred Meyer building. Public works locks can be obtained at Heyman's Safe, Lock and Security at 141 14th Street in Springfield (541-747-6713). Revised 9{24{07 Date Received: (,II~/~{f I Planner: AL