HomeMy WebLinkAboutBuilding Correspondence 2008-4-11
;
/. '.
.
.
.~~
.~CLalr
'1
525 NW Second Street, Corvallis. Oregon 97330
rt 800,383,8855 ph 541 758 1302 f. 541.753.2264 J
WWW~~~C3~y.com ~ ~ ~
April 11,2008
City of Springfield
225 Fifth Street
Springfield OR, 97477
SCANNED
Attention:
David Puent, Building Official
Subject:
International Accreditation Services, Inc. (IAS) Accreditation Documents and Special
Inspector Roster
Project:
PeaceHealth at RiverBend - Sacred Heart Medical Center Project (SHMC)
As previously discussed and approved by the City, CLAIR has been providing all required special inspection and
materials testing services for the SHMC Project in strict compliance with our !AS accreditation. I have enclosed
current copies of our IAS accreditation certificates along with a roster of the special inspectors, including their
individual certifications, utilized during the course of the SHMC Project.
There have been questions raised regarding CLAIR's registration with the OBOA voluntary special inspection
program. CLAIR has maintained registration with OBOA during the course of the project. However, CLAIR has
not maintained strict adherence to the utilization of OBOA registered special inspectors due to project dynamics.
CLAIR has confirmed with the project Owner, PeaceHealth and the Engineer of Record, KPFF, that CLAIR's
IAS accreditation is all that is required to meet the project requirements as the Owner's Special Inspection and
Materials Testing Agency.
With the approval of the Building Official, Owner, and Engineer of Record, regarding project requirements,
which accept (AS accreditation, the project requirement for adherence to the provisions of the OBOA voluntary
special inspection program has been removed.
If you have any questions or concerns, please do not hesitate to contact me at (541) 758-1302 or by email at
ac lair@claircomoanv.com.
Respectfully Submitted,
titL!t:-
Allan Clair, C.B.O.
Project Manager
Cc:
David Arndt, KPFF
Bob Collier, PeaceHealth
Carole Knapel, City of Springfield
Special Inspection Staff for SHMC
Emolovee
Antley, Mike
IOBOA
Structural Steel (Bolting & Welding)
Baker, Gil (Northwest Structural Steel (Bolting & Welding)
Geotech, Inc.)
Bauer, Andy
(Northwest Geotech,
Inc.)
Cleary, John C. (Sr.)
Cleary, John D. (Jr.)
Day, Dennis
De Fever, Tom
Reinforced Concrete
Structural Masonry
Reinforced Concrete
Reinforced Concrete
Structural Steel (Bolting & Welding)
Structural Wood
Reinforced Concrete
Structural Masonry
I ICC
Structural Steel & Welding
Structural Steel & Welding
Reinforced Concrete .
Structural Masonry
Structural SteelfWelding
Wood
Reinforced Concrete
Prestressed Concrete
Structural Masonry
Spray Applied Fireproofing
Reinforced Concrete
Spray Applied Fireproofing
Structural Masonry
Structural Steel & Welding
Reinforced Concrete
Structural Masonry
. ,
,
. . .
, -
I Other
ACl: Concrete Field Testing Tech I
A WS: Welding Inspector
Carlson Testing: UT Testing Insp, Levell!
COP: Structural Steel
Hellier: Magnetic Particle Testing
NDE: ANST Level Ill, UT Technician
A WS: Welding Inspector
.
COP: Wood Diaphragms & Sheer Walls, Proprietary
Anchor, St. Steel & Welding, Structural Masonry
ACI Concrete Field Testing Tech I
ACI Concrete Lab Tech I
ASNT ACCP Levell! Visual Testing
A WS: Welding Inspector
Nuclear Density Gauge Inspector
ACl: Concrete Field Testing Tech I
CPN: Radiation Safety/Nuclear Gauges
.
American Society: ACCP Levell!
A WS: Welding Inspector
CPN: Radiation Safety/Nuclear Gauges
Troxler: HazMat Certification
W ABO: Structural Steel
ACI: Concrete Field Testing Tech I
COP: Proprietary Anchors, Rein. Concrete, Structural
Masonry
Special Inspection Staff for SHMe
I Emplovee
Fra zer, John
Holman, Dan J.
Johannesen, Jason
Lee, Robert M.
Mackessy, Mike
MacMillan, James T.
McCarty, Bill
Sanetra, Paul
(Northwest Geotech,
Inc.)
IOBOA
N/A
Reinforced Concrete
Structural Masonry
Structural Steel (Bolting & Welding)
N/A
Reinforced Concrete
Reinforced Concrete
Structural Masonry
Structural Steel (Bolting)
Reinforced Concrete
Structural Masonry
N/A
Reinforced Concrete
Structural Masonry
I ICC
Structural Steel
Structural Masonry
Reinforced Concrete
Prestressed Concrete
Spray Applied Fireproofing
Reinforced Concrete
Structural Masonry
Structural Steel & Welding
Prestressed Concrete
Spray Apo.Iied Fireproofing
Prestressed Concrete
Reinforced Concrete
Spray Applied Fireproofing
Structural Masonry
Reinforced Concrete
Prestressed Concrete
Structural Masonry
Structural Steel & Welding
Reinforced Concrete
Structural Masonry
Structural Steel & Welding
Reinforced Concrete
Structural Masonry
Prestressed Concrete
Structural Steel & Welding
Prestressed Concrete
Reinforced Concrete
Spray Applied Fireproofing
Structural Masonry
Reinforced Concrete
Structural Masonry
I Other
ACI: Concrete Field Testing Tech I
UT Levelll
Magnetic Particle Levelll
A WS: CWl
CPN: Nuclear Gauge Safety
A WS: Welding Inspector
City of Corvallis: II different certs
.
CPN: Radiation Safety/Nuclear Gauges
Troxler: HazMat Cert & Radiation Safety/Nuclear
Gauges
ACI: Concrete Field Testing Tech I
ACI: Concrete Field Testing Tech I
City of Corvilllis: High Bolt, Rein Concrete,
Structural Masonry & Structural Steel & Welding
COP: Reinforced Concrete & Structural Masonry
Troxler: HazMat Cert & Radiation Safety/Nuclear
Gauges
.
ACl: Concrete Field Testing Tech I
Special Inspection Staff for SHMC
I Emplovee
Sarver, Craig J.
Thomason, Chris
Tilton, David
Zastawnik, Carl
(Northwest Geotech,
Inc.)
IOBOA
N/A
Fireproofing
Structural Steel (Bolting & Welding)
Fireproofing
Prestressed Concrete
Reinforced Concrete
Structural Masonry
Structural Steel (Bolting & Welding)
Structural Steel (Bolting & Welding)
I lCC
Reinforced Concrete
Spray Applied Fireproofing
Structural Masonry
Structural Steel & Welding
Spray Applied Fireproofing
Structural Steel & Welding
Structural Masonry
Spray Applied Fireproofing
Prestressed Concrete
Reinforced Concrete
Structural Masonry
Structural Steel & Welding
lCBO: Structural Steel & Welding
- ..,.
c
lather
ACl: Concrete Field Testing Tech I
Troxler: HazMat Cert & Radiation Safety/Nuclear
Gauges
ACI: Concrete Field TestingTech I
A WS: Welding Inspector
NDE: Magnetic Particle ilL
NDT: Magnetic Particle Testing LevelllIl
Quality Control Technician
.
ACI: Concrete Field Testing Tech I
A WS: Welding Inspector
COP: Prestressed Concrete, Reinforced Concrete,
Structural Masonry, Structural Steel, & Structural
Wood
Troxler: HazMat Cert & Radiation Safety/Nuclear
Gauges
ACl: Concrete Field Testing Tech I
COP: Structural Steel
A WS: Welding Inspector
.
Special Inspection Staff for SHMC
I Employee
IOBOA
I Other
I ICC
SUBCONTRACTED FIRMS:
LEVELTON ENGINEERING (APS Fabrication Shop, Langley B.C.)
I Employee
I Masoud Farjadi
I Suresh Khurana
I Ernesto Decena
I Rhonnel Tipay
I Stanley Dehann
I John Davidson
I Glenn Stark
OBOA
ICC
Other
Canadian Standards Association: Concrete &
Samplin~
Canadian Standards Association: Concrete &
Sampling
Canadian Standards Association: Concrete &
Samplin~
Canadian Standards Association: Concrete &
Sampling
Canadian Standards Association: Concrete &
Sampling
Canadian Welding Bureau: Level 3 Weldinlllnspector
Canadian Welding Bureau: Level I Welding Insoector
FLOOD TESTING (American Stair, Romeoville, IL)
I Employee
I Michael Chiappetta
I Ron St. Germain
Robert Hay III
OBOA
ICC
Other
A WS: Certified Welding Inspector
A WS: Certified Welding Inspector
Illinois Department of Transportation: concrete tech I
ASNT NDT Level III (MT, PT, UT)
A WS: Certified Welding Inspector
Prestressed Concrete
Reinforced Concrete
Spray Applied Fireproofing
Structural Masonry
St. Steel & Welding
PROFESSIONAL INDUSTRIES, INC. (Heleport Structural Steel Fabrication: Lansing, MI)
I Emp!ovee
I Greg Crooks
IOBOA
I ICC
I Other
A WS: Certified Welding Inspector
,
.
.
International Accreditation Service, Inc.
CERTIFICATE OF ACCREDITATION
. This is to signify that":,
, .
.
CLAIR COMPANY, INC. .
525 NORTHWEST 2"" STREET, #3
CORVALLIS, OREGON 97330 ,
'''.
.:<'
. . '
Tef>.ting LaboratoiyTL-229
(Revised February 12, 2008)
.'
.'.
has demonstrated compliance with ANS/ISO/IEC Standard 17025:2005, General criteria for the competence of testing and
calibration laboratories, and has been accredited, commencing Qctober 5,2007, for the test methods listed in the approved
scope of accreditation. . '
:.
:P~~
Patrick V. McCullen '
Vice President
13~&~A -~
._ f II ~:/I/'"C/"__
'c. P. Ramani~ P.E. . ........
President
-- .".,
(see attached scope of accreditation for fields of testing and accredited test methods)
This accreditation certificate supersedes any lAS accreditation certificate bearing an earlier date. The certificate becomes invalid upon suspension,
cancellation, or revocation of accreditation. See the !AS Accreditation Listings on the web at www.iason1ine.org for current a"""_J;_tion information,
or contact lAS directly at (562) 699-054\. Print Date: 0212112008 Page 1 of2
.'
,
International Accreditation Service, Inc.
ScoPE OF ACCREDITATION
Clair Company, Inc. TL-229
(Revised February 12, 2008!
"'.
.
Clair Company, Inc.
525 NW 2'><1 Street #3
Corvallis, OR 97330
Marty Warner
Technical Director.
(541) 758-1302
.., 'I Spray applied fire proofing
ACCREDITED TEST METHODS
ASTM Standards C 31, C 39, C 42, C 136, C 138, C 143, C
172,C173, C231,C511andC1064
ASTM Standards C 140, C 270, C 1019 and C 1314; 1997
UBe Standard 21-16
ASTM Standards C 117, D 421, 0 422, 0 698, D 2217, 0 2419, I
D 2922,04318 and 0 1557
ASTM Standards D 2041, D 2726 and D 2950 I
ASTM Standards A 388, A 435, A 577, E 165, E 709 and E
797; ASME Standard B 31.3; AWS Standards D1.1 and SNT-
TC-1A
ASTM Standards E 605 and E 736; 1997 UBC Standard 7-6
20061BC Section 1713.3.2
Testing and inspection
under ASTM E 329
FIELDS OF TESTING
" I Concrete,
I Masonry
I Soils and rock
I Bituminous
Steel
:.
Fasteners
.'
October 5. 2007
C_~_..cement Date
/,"o/Wr~
'. ~
"
C. P. Ramani, P .E.
President
This accreditation certificate supersedes any !AS accreditation certificate bearing an earlie" date. The certificate becomes invalid upon suspension,
cancellation, or "evocation of accreditation. See the !AS Accreditation Listings on the web at www.iasonline.org for current accreditation infonnation,
0" contact lAS directly at (562) 699-0541. Print Date: 0212112008 Page 2 of2
,
.
.
'.
International Accreditation Service, Inc.
CERTIFICATE OF ACCREDITATION
..'This is'to'signifY that'.>
CLAIR COMPANY, INC.
3333 GAME FARM ROAD
SPRINGFIELD, OREGON 97477
Testing Labo~tory. TL-283
(Revised February 12, 2008) .'
,
,',
has demonstrated compliance with ANS/ISOIIEC Standard 17025:2005, General criteria for the competence of testing and
calibration laboratories, and has been accredited, commencing October 5,2007, for the test methods listed in the approved
scope of accreditation.
I.
Ild/;Jt~
I Patrick V. McCullen '
Vice President
C. P. Ramani; P.E. <';'-,
President
"c;y~~./J
......
(see attached scope of accreditation for fields of testing and accredited test methods)
This accreditation certificate supersedes any !AS accreditation certificate bearing an earlier date. The certificate becomes invalid upon suspension,
cancellation, or revocation of accreditation. See the !AS Accreditation Listings on the web at www.iasonline.org for current accreditation information,
or contact !AS directly at (562) 699-0541. Print Date: 02121/2008 Page I of2
-
International Accreditation Service, Inc.
SCOPE OF ACCREDITATION
Clair Company, Inc. TL-283
(R~ed February 12, 2008)
.
Clair Company, Inc.
3333 Game Farm Road
Springfield, OR 97477
'-'--'..
Marty Warner
Technical Director
(541) 758-1302
Masonry
ACCREDITED TEST METHODS
ASTM Standards C 31, C 39, C 42, C 138, C 143, C 172, C
173, C.231, C 511 and C1064
ASTM Standards C 140, C 270 and C 1019; 1997 UBC
Standard 21-16
ASTM Standard D 2922
ASTM Standards D 2041 and D 2950
ASTM Standards A 388. A 435, A 577, E 165, E709 and E
797; ASME Standard B 31.3; AWS Standards D1.1 and
SNT-TC-1A
ASTM Standards E 605 and E 736; 1997 UBC Standard 7-6
2006 IBC Section 1713.3.2 .
FIELDS OF TESTING
Concrete
Testing and inspection
under ASTM E 329
Soils and rock
Bituminous
Steel
Spray applied fire proofing
.
Fasteners
...- .
... 0;1' ".."'~r>
. ,
, . --
October 5. 2007
Commencement Date .
-
C. P. Romani, P.E.
President
This accreditation certificate supersedes any !AS accreditation certificate bearing an earlier date. The certificate becomes invalid upon suspension,
cancellation, or revocation of accreditation. See the lAS Accreditation Listings on the web at www.iasonline.org for current accreditation information,
or contact lAS directly at (562) 699-0541. Print Date: 02121/2008 Page 2 of2
"
---.- '.~""-'.'~
.
u__.____.
Consulting Engineers
April 8, 2008
Mr. Allan Clair
Clair Company
525 Northwest Second Street
Corvallis, OR 97330
Subject: Sacred Heart Medical Center- Accreditation for Speciallnspection(Materials Testing
'Dear Allan:
It is our understanding that the City of Springfield deems Ciair Company's International
Accreditation Service, Inc. (IAS) accreditation to be acceptabie for the project accreditation
requirements. KPFF takes no exception to this position.
Sincerely,
,()~ ~
David Arndt, SE
Associate
RWP:mlq:jef
102344.30
~..., I.' . .-" \ .
1801 Fifth Avenue Suits IBOO Sesttle, WA 98101 (208) 822~5B22 Fax (20B) 822~8130
Suttle ElllflU Tacoma LacBY PorI/and Eugflne Sacramento San FrancIsco Walnut Creek Los.Angelell Long Beach Pasadena Irvine
Sin Diego PhoenIx Denver SI. LouIs Nflw York & Ammln. Jordan
.~.~
..
.
.
IH1'
_Lair
525 NW Second Street. Corvallis, Oregon 97330
d 800.383.8855 ph 541.758.1302 "541.753.2264
www.claiTcompany.com
April II, 2008
American Institute of Steel Construction, Inc. (AISC)
One West Wacker Drive, Suite 700
Chicago, IL 6060 I
Attention:
Roger Ferch, President
Subject:
,AISC Letter to the City of Springfield, Oregon, dated March 17,2008
Project:
PeaceHealth at RiverBend - Sacred Heart Medical Center Project (Project)
Hospital/OHVI Building
We have received a copy of your letter "Clair Company - Plagiarism Concerns", dated March 17, 2008, which
was sent to Mr. Dave Puent, City of Springfield, Building Official. Clair Company, Inc. (CLAIR) understands
and appreciates your position and concerns. There has not been and there will not be any further use of the
referenced checklist in any form. Also, I have discussed this issue in detail with Mr. Puent.
For clarification, CLAIR was not performing fabricator qualification or approval services. In order to waive full
time shop inspections, project specifications require periodic shop inspections and review of testing performed by
the fabricator by the owners testing agency (see attached relevant specification section). At the time of the
inspection it seemed appropriate to use a format for tire review that would be familiar to the fabricator since the'
waiver was also based on the fabricator maintaining AISC certification. The intent of the checklist was to provide
a general guideline for the review only.
I attempted to contact by phone Brian Raff, the AISC representative who discussed this issue with Mr. Puent. I
left a voice message for Mr. Raff stating that we understood AISC's concern and that we would not use the
subject form in the future. I requested a call back from Mr. Raff, but to this date have not received a return call.
If you have any questions or continued concerns, please do not hesitate to contact me at (541) 758-1302 or by
email ataclair@claircomoanv.com.
Respectfully Submitted,
/Ptt!-
Allan J. Clair
President
Cc:
Dave Puent, City of Springfield
Patrick V. McCullen, IAS
, .
'""'""l ..1'.'.
.
., ___:::.__.n.::'.:.:..
-.
...-- ..-.....--.-.---- ".
Peacehea1th'Sacred Heart Medical-Center
At Riverbend
Springfield, Oregon
June 8, 2005
Site, Hospital and OHVI Building Bid Packages 1, 3, 3a .
Issued for Bid
B. Shop Inspection: When approved by the Building Official, the Owner, and Engineer/Architect,
full-time special inspection in the fabrication shop by the Owner's Testing Agency'may be
waived, subject to the following:
1. The Fabricator participates in the AISC Quality Certification Program and is designated
an AISC-Certified Plant. .
2. All shop inspection is provided by the Contractor, per the requiremCl)ts herein, and is
documented. .Reports and test results are to be available for the Owner's Inspector to
review. .
3.' A specific quality: control plan for this project shall be developed and submitted to the
Structural Engineer for approval prior to the prefabrication/preerection meeting.
4. Periodic inspection by the Owner's Inspection Agencyis allowed by the Fabricator..
5. Certified Plants: Continuous plant inspection is not required at plants producing
prefabricated steel products which are certified by the Building Official. .
C. Contractor Responsibilities Related to Shop and Field Inspections
Maintain complete records of all quality control and testing performed by the Contractor.
Furnish all electrical power, turning or moving of members, hoisting, staging, and other
facilities required for inspection.
Provide testing agency with access to 'Places where structural steel work is being
fabricated or erected so required inspection and testing can be accomplished.
Correct deficiencies in, or remove. and replace structural steel that inspections and test
reports indicate do not comply with specified requirements.
Additional testing, at Contractor's expense, will be performed to determine compliance.of
corrected work with specified requirements.
Grant Inspectors full authority to inspect all material and work that fails to conform in
, every respect to these specifications.
When required by_ Engineer/Architect or Owner's Independent Testing Agency or
Contractor's engaged inspection organization, make adequate platforms available to the
Inspector for the purpose of checking high-strength bolts and welds. Scaffolding shall be
provided to ensure safe perforrnaiJ.ce of this operation.
1.
2.
3.
4.
5.
, .
, , 6.
~.. "\ 7.
D. Shop and Field Tests and Inspections _ .
1. Bolted connections will, be tested and inspected accOrding to RCSC's "Load and
Resistance Factor Design Specification for Structural Joints Using ASTM A 325 or
A 490 Bolts."
2. Welded Cormections: In addition to visual inspection, welded .connections will be
inspected and tested according to A WS D1.1 and the inspection procedures listed below,
at testing agency's option,.or as required by contract documents.
a. Procedures
1) Liquid Penetrant Inspection: ASTM E 165.
2) Magnetic Particle Inspection: ASTM E 709; pwfu.~ed on root pass and oi:1
finished weld. Cracks or zones of incomplete fusion or penetration will not
be accepted. .
3) Radiographic Inspection: ASTM E 94 and ASTM E 142; minimum quality
level "2-2T."
4) Ultrasonic Inspection: ASTM E 164.
Anshen + Allen
STRUCTURAL STEEL
05120-Page 19
.
,..
, '.
.
.
J=Eil81r
525 NW Second Street, Corvallis. Oregon 97330
d 800.3838855 ph 541.758.1302 Ix 541.7532264
www.c1aircompany.com
April I 1,2008
International Accreditation Service, Inc.
5360 Workman Mill Road
Whittier, CA 90601
Attention:
Patrick V. McCullen, Vice President
Subject: .
Project: .
IAS Certified Letter dated March 25, 2008
PeaceHealth at RiverBend - Sacred Heart Medical Center Project (Project)
HospitaVOHVI Building
This letter is in response to your letter dated March 25, 2008. Please find attached the requested copy of our response
to the letter from S&M Steel Fabricators (S&M), (undated), which was addressed to the City of Springfield Building
Official, Dave Puent. We believe our letter and supporting documentation will provide the requested point by point
response to the statements made by S&M.
In reference to lAS' concerns that Clair Company, Inc. (CLAIR) is representing itself as being accredited to conduct
inspections to fulfill "approved fabricator" status, we offer the following clarifications.
The fabricator, S&M, already participates in a program with AISC to establish Certified Plant status. In addition to
participation in the AISC program, in order to waive full time shop inspection, Project specifications also require the
following (see attached copy of Specification Section):
I.' Contraclorlfabricator to provide shop inspection and testing. Report and test results are to be available for the
Owner's Inspector to review.
2. Periodic inspection by the Owner's Inspection Agency is allowed by the fabricator.
CLAIR scheduled a visit at the fabricator to provide a general review of shop procedures and to review in.house
inspection and testing procedures and reporting pertaining to the Project.
CLAIR was not representing itself as any kind of an accrediting or auditing agency, IAS accredited or otherwise.
If you have any questions, or need clarification regarding the information we have provided, please do not hesitate to
contact me at (541) 758-1302 or by email ataclair@claircomo.lOv.com.
Respectfully Submitted,
/JtjL
Allan J. Clair
President
Cc:
Dave Puent, City of Springfield
! , .'
. ,..,.."
, .' .-
r
...,'--. '
. -.-
..,. ....P.,
._..~,_._--_. ".
Peacehealth'SaCred HearrMedical'Center
At Riverbend
Springfield, Oregon
June 8,2005
Site, Hospital and OHVI Building Bid Packages 1, 3, 3a .
Issued for Bid
,
B. Shop Inspection:. When approved by the Building Official, the Owner, and Engineer/Architect,
full-time special inspection in the fabrication shop by the Owner's Testing Agency'may be
waived, subject to the following:
1. The Fabricator- participates in the AlSC Quality Certification Program and is designated
an AISC-Certified Plant. .
2. All shop inspection is provided by the Contractor, per the requirements herein, and is
documented. .Reports and test results are to be available for the Owrer's Inspector to
review. . I .
3. A specific quality: control plan for this project shall be developed and submitted to the
Structural Engineer for approval prior to the prefabrication/preerection meeting.
4. Periodic inspection by the Owner's Inspection Agencyis allowed by the Fabricator..
5. Certified Plants: Continuous plant inspection is not required at plants producing
prefabricated steel products which are certified by the Building Official. .
C. Contractor ResponsibilitieS Related to Shop and Field Inspections
Maintain complete records of all quality control and testing performed by the Contractor.
Fmnish all electrical power, tmning or moving of members, hoisting, staging, and other
facilities required for inspection. .
Provide testing agency with access to places where structural steel work is being
fabricated or erected so required inspection and testing can be accomplished.
Correct deficiencies in, or remove. and replace structural steel that inspections and test
reports indicate do not comply with specified requirements.
Additional testing, at Contractor's expense, will be performed to determine compliance .of
corrected work with specified requirements.
Grant Inspectors full authority to inspect all material and work that fails to conform in
. every respect to these specifications.
When required by..Engineer/Architect or Owner's Independent Testing Agency or
Contractor's engaged inspection organization, make adequate platforms available to the
Inspector for the purpose of checking high-strength bolts and welds. Scaffolding shall be
provided.to ensure safe performailce of this operation.
1.
2.
3.
4.
5.
~ .. \
, 6.
,.
:--" 7.
D. Shop and Field Tests and Inspections .
1. Bolted connections will, be testCd and inspected according to RCSC's "Load and,
Resistance Factor Design Specification for Structural Joints Using ASTM A 325 or .
A 490 Bolts."
2. Welded Connections: In addition to visual inspection, welded connections will be
inspected and tested according to A WS D 1.1 and the inspection procedures listed below,
at testing agency's option,.or as required by contract documents.
a. Procedures
1) Liquid Penetrant Inspection: ASTM E 165.
2) Magnetic Particle Inspection: ASTM E 709; performed on root pass and 00
finished weld. Cracks or zones of incomplete fusion or penetration .will not
be accepted.
3) Radiographic Inspection: ASTM E 94 and ASTM E 142; minimum quality
level "2-2T."
4) Ultrasonic Inspection: ASTM E 164.
Anshen + Allen
STRUCTURAL STEEL
05120-Page 19