January 18, 1990
Bob Nelson
361 Shelley Street
Springfield, OR 97477
Dear Mr. Nelson:
I am sending this letter as requested in our telephone
conversation on January 12, 1990,
The east half of the south wall, at 361 Shelley, 'meets the two
hour fire-resistive requirement. The west half of the south wall
does not. A second layer of 5/8 inch Type X gypsum board shall be
applied to this wall section before the two hour fire-resistive
requirement is satisfied.
If I can be of any further assistance, please contact me at
726-3759.
Sincerely,
~ "'" VV\.e<.A-j-
Tom Marx
Building Inspector
cc: Dave Puent, Building Official