Loading...
HomeMy WebLinkAboutCorrespondence PWE 2/4/2011 . . L1MBIRD Andrew From: Sent: To: Cc: Subject: MCEACHERN Clayton Friday, February 04,201110:19 AM 'glarsen@bhengineers.com' L1MBIRD Andrew FW: Generator containment info >Staff does not support piping the generator enclosure drainage to the outside wall and allowing it to drain across the sidewalk and parking lot. I would encourage you to discuss the stormwater drainage details with the City's Public Works Engineer for this >project, Clayton McEachern I have discussed the matter with Andy limbird (the assigned planner) and the proposed drainage pathway across the parking lot is acceptable, with the following conditions: 1. The drain pipe from the enclosure to the curb face must be equipped with a shutoff valve that is closed during refueling/servicing or testing of the generator, with an attached sign that states this (we can provide an example if necessary) 2. The drain pipe cannot discharge across the sidewalk adjacent to the generator structure, but must go under the sidewalk and discharge onto the parking lot via a weep hole in the curb face 1 Date Received:_J./'f/ don Planner: AL I