HomeMy WebLinkAboutCorrespondence Miscellaneous 1/21/2011 . . ,'/ L1MBIRD Andrew From: Sent: To: Cc: Subject: KAUFMAN Kip Friday, January 21,2011 2:28 PM 'swalker@bergmeyer.com'; L1MBIRD Andrew; GORDON Gilbert; CASTILE Robert PUENT David; GERARD Alan RE: 019 Cabela's I Emergency Generator! 2800 Gateway! Permit#811-SPR2010-257 Dear Scott, Andy, Gilbert and I had a brief meeting today concerning the emergency generator. Items,addressed were as follows: 1) Outdoor storage, dispensing, spill control and containment for the diesel fuel (Class II Combustible Liquid): please meet the requirements per S.U.B. for drinking water protection and per OSSC Sections [F]414.5.5, [F]414.6 which re-direct compliance per the fire code. 2) Provide vehicle impact protection for the emergency generator per OFC Section 312. 3) Per Springfield public works division, provide an enclosure with rooffor the emergency generator. Since the structure is less than 10 feet from the anchor building, the structure and materials must be non-combustible or the structure must be protected by NFPA 13 fire sprinklers. Please provide wet-signature stamped engineering for the structure including calculations, specifications and construction details. Also, clear space must be maintained around the emergency generator to allow access for maintenance and repair. I recommend checking with both planning and public works for any additional requirements they may have. 4) The anchor building exterior wall is equivalent to at least a i-hour fire-resistance-rated wall per Robert Castile, building inspector, so fire separation from the emergency generator is provided. 5) The emergency generator is greater than 10 feet from the mall's required path of egress travel, so there are not egress issues. 6) The additional items to achieve code compliance for the emergency generator are listed below in the previous email. Please submit (2) copies architect's wet-signature stamped, plan documents for review by the City of Springfield planning, public works, fire and building safety. Best regards, Kip Kaufman Plans Examiner, Building Safety Development Services Department' 225 Fifth Street Springfield, Oregon 97477 (S41) 726-3623 (541) 726-3676 fax kkaufmanlaJ,sDringfield-or .gov From: KAUFMAN Kip Sent: Tuesday, January 18, 2011 11:40 AM To: 'Scott Walker' Cc: CASTILE Robert; GORDON Gilbert; RICHARDSON Bryan; UMBIRD Andrew 1 Date Received: I~;/,)oll Planner: AL / / . . Subject: RE: 019 Cabela's I Emergency Generator/ 2800 Gateway/ Permit #811-SPR201O-2S7 Importance: High " .' Dear Scott, Deferred submittals require (2) copies architect's wet-signature, plan documents be submitted for review and approval by the City of Springfield Development Services Department, Building Safety Division. This is true for both of your deferred submittals: 1) the emergency generator and standby power, and 2) the shelving systems and storage racks. In addition to planning, public works and possibly S.U.B. Drinking Water Protection review, the emergency generator and standby power requires building, fire and electrical plan reviews for compliance with the following: 1) 2007 Oregon Structural Specialty Code Sections 1006, 1008, 1011, 1108.3, 2702 and 3003, 2) 2007 Oregon Fire Code/ Springfield Fire Code Sections 604, 1006, 1008, 1011, 3) 2008 Oregon Electrical Specialty Code, 4) NFPA 13, 70, 72, 110 and 111, 5) and listed in accordance with UL 2200. There are many permits related to 2800 Gateway Street and to the Cabela's project. Please reference the permit number for your project on your emails and on your submittal documents. Thank you. Best rega rds, Kip Kaufman Plans Examiner, Building Safety Development Services Department 225 Fifth Street Springfield, Oregon 97477 (541) 726-3623 (541) 726-3676 fax kkaufman@springfield-or.gov From: Scott Walker [mailto:swalker@bergmeyer.com] Sent: Friday, January 14, 2011 7:08 PM To: UMBIRD Andrew Cc: KAUFMAN Kip; Stephanie Jones; Rachel Zsembery Subject: 019 Cabela's I Emergency Generator Hi Andy, Thank you for returning my call earlier this evening. Thank you also, in advance, for coordinating the review of the proposed location for our emergency generator. Please let me know if you need any additional information to aid your or any other department's review. Take care, Scott 2 Date Received: /;;hM Planner: AL I / i J. Scott Walker, LEED AP Bergmeycr Associates, Inc. 51 Sleeper Street Boston, MA 02210 Direct 617 695 7726 Phone 617 542 1025 Fax 6]7 5421026 .!Y...\Y..W..:..9GG!I!5;'yer .~QITI . . <<019-11 0114_Emergency-Generator-Specs.pdf>> <<019-110114_Emergency-Gen-Location.pdf>> 3 Date !'{eceived:4+f, Planner: AL