RE: 019 Cabela's I Emergency Generator! 2800 Gateway! Permit#811-SPR2010-257
Dear Scott,
Andy, Gilbert and I had a brief meeting today concerning the emergency generator.
Items,addressed were as follows:
1) Outdoor storage, dispensing, spill control and containment for the diesel fuel (Class II Combustible Liquid):
please meet the requirements per S.U.B. for drinking water protection and per OSSC Sections [F]414.5.5,
[F]414.6 which re-direct compliance per the fire code.
2) Provide vehicle impact protection for the emergency generator per OFC Section 312.
3) Per Springfield public works division, provide an enclosure with rooffor the emergency generator. Since the
structure is less than 10 feet from the anchor building, the structure and materials must be non-combustible or
the structure must be protected by NFPA 13 fire sprinklers. Please provide wet-signature stamped engineering
for the structure including calculations, specifications and construction details. Also, clear space must be
maintained around the emergency generator to allow access for maintenance and repair. I recommend checking
with both planning and public works for any additional requirements they may have.
4) The anchor building exterior wall is equivalent to at least a i-hour fire-resistance-rated wall per Robert Castile,
building inspector, so fire separation from the emergency generator is provided.
5) The emergency generator is greater than 10 feet from the mall's required path of egress travel, so there are not
egress issues.
6) The additional items to achieve code compliance for the emergency generator are listed below in the previous
email.
Please submit (2) copies architect's wet-signature stamped, plan documents for review by the City of Springfield
planning, public works, fire and building safety.
Best regards,
Kip Kaufman
Plans Examiner, Building Safety
Development Services Department'
225 Fifth Street
Springfield, Oregon 97477
(S41) 726-3623
(541) 726-3676 fax
kkaufmanlaJ,sDringfield-or .gov
From: KAUFMAN Kip
Sent: Tuesday, January 18, 2011 11:40 AM
To: 'Scott Walker'
Cc: CASTILE Robert; GORDON Gilbert; RICHARDSON Bryan; UMBIRD Andrew
1
Date Received: I~;/,)oll
Planner: AL / /
. .
Subject: RE: 019 Cabela's I Emergency Generator/ 2800 Gateway/ Permit #811-SPR201O-2S7
Importance: High
"
.'
Dear Scott,
Deferred submittals require (2) copies architect's wet-signature, plan documents be submitted for review and approval
by the City of Springfield Development Services Department, Building Safety Division. This is true for both of your
deferred submittals: 1) the emergency generator and standby power, and 2) the shelving systems and storage racks.
In addition to planning, public works and possibly S.U.B. Drinking Water Protection review, the emergency generator
and standby power requires building, fire and electrical plan reviews for compliance with the following:
1) 2007 Oregon Structural Specialty Code Sections 1006, 1008, 1011, 1108.3, 2702 and 3003,
2) 2007 Oregon Fire Code/ Springfield Fire Code Sections 604, 1006, 1008, 1011,
3) 2008 Oregon Electrical Specialty Code,
4) NFPA 13, 70, 72, 110 and 111,
5) and listed in accordance with UL 2200.
There are many permits related to 2800 Gateway Street and to the Cabela's project. Please reference the permit
number for your project on your emails and on your submittal documents.
Thank you.
Best rega rds,
Kip Kaufman
Plans Examiner, Building Safety
Development Services Department
225 Fifth Street
Springfield, Oregon 97477
(541) 726-3623
(541) 726-3676 fax
kkaufman@springfield-or.gov
From: Scott Walker [mailto:swalker@bergmeyer.com]
Sent: Friday, January 14, 2011 7:08 PM
To: UMBIRD Andrew
Cc: KAUFMAN Kip; Stephanie Jones; Rachel Zsembery
Subject: 019 Cabela's I Emergency Generator
Hi Andy,
Thank you for returning my call earlier this evening. Thank you also, in advance, for coordinating the review of the
proposed location for our emergency generator. Please let me know if you need any additional information to aid your or
any other department's review.
Take care,
Scott
2
Date Received: /;;hM
Planner: AL I /
i
J. Scott Walker, LEED AP
Bergmeycr Associates, Inc.
51 Sleeper Street
Boston, MA 02210
Direct 617 695 7726
Phone 617 542 1025
Fax 6]7 5421026
.!Y...\Y..W..:..9GG!I!5;'yer .~QITI
.
.
<<019-11 0114_Emergency-Generator-Specs.pdf>> <<019-110114_Emergency-Gen-Location.pdf>>
3
Date !'{eceived:4+f,
Planner: AL