HomeMy WebLinkAboutMiscellaneous Field Test & Inspection Report 2011-4-8
SfEI
TEIlIIlG & INIPEOIOII INC
('...,m.mnical & C'..ombudion Services
Compressive Strength of Concrete
(ASTM C 39\
CLIENT Mr. Carl Kern
Sheltercare
. PO Box 23338
Eugene. Oregon 97402
PROJECT
AFIYA Apartment Complex
1082 Main SI.
Springfield, Oregon
DATE
PROJECT NO.
REPORT NO.
04-08-11
2107080
7474
BPNO.
COM 20Q9.01546
DATE CAST 03-11-11 CAST BY D. Delatte DATE RECEIVED 03-14-11
STRENGTH REQUIRED 3000 psi SPECIMEN SIZE 4"xS"
STRENGTH PLACED 4000 psi SACKS SUPPLIER ESG
PRODUCT CODE 314065 CEMENT MAX SIZE AGG. 3/4"
ADDITIVES AEA; Fiber; Hot water AIR CONTENT 4.1%
LOAD NO. 1 TICKET NO. 58021915 SLUMP 4"
CONCRETE TEMP 72' F YARDAGE 8.0 OF TIME 10:15AM
AIR TEMP 50' F WEATHER Overcast SPECIMEN STORAGE 2 day field cure
POUR LOCATION Sidewalk on the west side of project. Rem. ASTM C 31
LOAD 1 SAMPLED South end.
AVERAGE
TEST AGE AREA WEIG~T TOTAL COMPRES~~V~, STRENGTH TIME OF TYPE OF
DATE (DAYS) fiN.') (LBS LOAD/LBS' STRENGTH PSI (PSIl TEST FRACTURE"
03-18-11 7 12.56 8.60 42655 3400 8:30 AM 5
04-08-11 28 12.56 6.53 58120 4630 9:20 AM 4
04-08-11 28 12.56 8.56 60000 4780 4705 9:25 AM 3
Hold
-1. End Cones 2 - Cone/Split 3 - Columnar 4 - Diagonal 5 - Side (lop Of bottom) 6- Side (pointed lOp or bottom)
REMARKS: Chris (Meili Construction) was advised of on-site test results.
Reviewed By:
fJ1. 'i.17t-
Michael L. Meyer .
Technical Manager
c:
Sheltercare - Susan Ban (email)
Meili Construction - Curt Meili (email)
Meili Construction - Kris Russnogle (email)
Meili Construction - Andy Renfro (emaiQ
Meili Construction - Chris Hyde (email)
Lunabridge - Destin Ferdun (email)
Bergsund DeLaney Architecture - Anne DeLaney (email)
Bergsund DeLaney Architecture - Julie Romig (email)
Hohbach-Lewin - Vikki Bourcier (email)
Springfield Church of the Brethren - Dale Seese (email)
Michael Roberts - (email)
City of Springfield - Denny Wright (email)
MLM:sc
This report and/or enclosed test data Is the confidential property of the dient to whom it is addressed and pertains to the specific
process and/or material evaluated. As such, Information contained herein shall not be reproduced in part or full and/or any part
thereof be disclosed without FEI Testing & Inspection. Inc.'s written authorization.