Loading...
HomeMy WebLinkAboutComments FLS 9/2/2008 . . Page 1 of 1 L1MBIRD Andrew From: GORDON Gilbert Sent: Tuesday, September 02, 2008 9:02 AM To: L1MBIRD Andrew Cc: GERARD Alan; FECHTEL Melissa Subject: Non-Conforming User DRC2008-00052 Kelley Greg LLC-Parklane Mobile Home Park Non-Conforming Use DRC2008-00052 Kelley Greg LLC Address: 225 41st Street Existing Use: Park Lane Mobile Home Park Proposal: Replace existing RV spaces and residence with 20 new mobile home spaces Planner: Andy Limbird, Planner \I Fire Department Comments: Water Supply: OK. The applicant is proposing three additional public and one private fire hydrant to serve this site. Access: OK. 1. "No Parking-Fire Lane" signs shall be posted on both sides of "Private Street A" and ;'E" and one side of "Private Street D" per 2007 Springfield Fire Code 503.3 ?Ind SFC Appendix D103.6. 2. New private streets shall have an all-weather surface capable of supporting an 80,000 lb. load per SFC 503.2.3 andSFC Appendix D 1 02.1. 3. Plan Sheet C2 of 6 identifies a proposed gate on the SE side along Commercial Avenue. Since one of the proposed fire hydrants is shown near that location, the gate would have to be a vehicle gate with a minimum 20 foot clear width. If the gate is electric activated, a Knox keyed gate switch shall be installed. If the gate is manual, then a public works lock from Heyman's Safe, Lock and Security at 131 14th Street in Springfield shall be installed for fire access. Gilbert R. Gordon Deputy Fire Marshal Springfield Fire and Life Safety 225 Fifth Street Springfield, OR 97477 Phone: 541-726-2293 E-Mail: ggordon@cLsQringfield.or.us Date Received: 9/.;.p<t1t71" Planner: AL I I 9/2/2008