Loading...
HomeMy WebLinkAboutCorrespondence FLS 8/30/2010 ... ...'..... . , MILLER Liz From: Sent: To: Subject: GORDON Gilbert Monday. August 30.20105:02 PM MILLER Liz RE: Minimum Development Standards DRC2010-00020 and DRC2010-00021 1415 Mississippi Avenue-Glenwood Liz, Here are what I think is the appropriate sections from the 2010 Springfield Fire Code: 304.3.3 Capacity exceeding 1.5 cubic yards. Dumpsters and containers with an individual capacity of 1.5 cubic yards [40.5 cubic feet (1.15 m3)] or more shall not be stored in buildings or placed within 5 feet (1524 mrri) of combustible walls, openings or combustible roof eave lines. Exceptions: I. Dumpsters or containers in areas protected by an approved automatic sprinkler system installed throughout in accordance with Section 903.3 .1.1, 903.3 .1.2 or 903.3 .1.3. 2. Storage in a structure shall not be prohibited where the structure is of Type I or IIA construction, located not less than 10 feet (3048 mm) from other buildings and used exclusively for dumpster or container storage. 304.3.4 Capacity of 1 cubic yard or more. Dumpsters with an individual capacity of 1.0 cubic yard [200 gallons (0.76 m3)] or more shall not be stored in buildings or placed within 5 feet (1524 mm) of combustible walls, openings or combustible roof eave lines unless the dumpsters are constructed of noncombustible materials or of combustible materials with a peak rate of heat release not exceeding 300 kW/m2 when t::sted in accordance with ASTME 1354 at an incident heat flux of 50 kW/m2 in the horizontal orientation. Exceptions: I. Dumpsters in areas protected by an approved automatic sprinkler system installed throughout in accordance with Section 903.3 .1.1, 903.3 .1.2 or 903.3 .1.3. 2. Storage in a structure shall not be prohibited where the structure is of Type I or IIA construction, located not less than 10 feet (3048 mm) from other buildings and used exclusively for dumpster or container storage. Hope this helps. Gilbert R. Gordon Deputy Fire Marshal Springfield Fire and Life Safety 225 Fifth Street Springfield. OR 97477. Phone: 541-726-2293 E-Mail: qqordon@ci.sprinqfield.oLus Date Received: Planner: LM <g /30 IJJ2 1 r . .t-'''\... From: MILLER Liz Sent: Monday, August 30, 2010 10:23 To: GORDON Gilbert . Subject: PN: Minimum Development Standards DRC201O-00020 and DRC201O-00021 1415 Mississippi Avenue- Glenwood . , From: MILLER Liz Sent: Monday, August 30, 2010 10:23 !10M To: MILLER Liz Subject: RE: Minimum Development Standards- DRC201O-00020 and DRC201O-000211415 Mississippi Avenue-Glenwood Gilbert, After speaking with the applicant and seeing the revised plan, it seems like the applicant is proposing keeping their trash receptacle inside the building. Could you send me something on the maximum size dumpster or receptacle permitted inside? Thanks so much. Liz From: MILLER Liz Sent: Monday, August 30, 2010 9: 11 AM To: GORDON Gilbert Subject: RE: Minimum Development Standards DRC201O-00020 and DRC2010-00021 1415 Mississippi Avenue-Glenwood Thanks Gilbert. From: GORDON Gilbert Sent: Friday, August 27, 2010 12:05 PM To: MILLER Liz Cc: GERARD Alan; FECHTEL Melissa Subject: PN: Minimum Development Standards DRC201O-00020 and DRC2010-00021 1415 Mississippi Avenue- Glenwood Liz, With the modification of the site plan, one comment that would need to be added would be to have a public works lock obtained at Heyman's Safe, Lock and Security, Inc. at 131 14th Street in Springfield (phone: 541-726-1545) for the manual swinging vehicle gate fronting Mississippi Avenue. All other Springfield Fire Marshal comments for this proposal remain with no changes. Gilbert R. Gordon Deputy Fire Marshal Springfield Fire and Life Safety _ 225 Fifth Street Springfield, OR 97477 Phone: 541-726-2293 E-Mail: qqordon@ci.sprinqfield.or.us From: GORDON Gilbert Sent: Friday, July 30, 2010 08:50 To: MILLER Liz Date Received: Planner: LM <( bo~ I 2 -- - ,..,,-- - ee: GERARD Alan; FECKTEL Melissa- Subject: Minimum Development Standards DRC201O-00020 and DRC201O-000211415 Mississippi Avenue-Glenwood Liz, Springfield Fire Marshal's Office does not have any comments for the proposed minimum development standards for the prospective automotive dealership for this site. Access from Mississippi Avenue is pre-existing. A relatively new fire hydrant (H-1426) fed 9ft a 16 inch water line is located at the southwestern corner of 14th Avenue and Mississippi. It is well within the maximum 400 foot hose lay distance for the proposed 504 sq. ft. structure. Gilbert R. Gordon Deputy Fire Marshal Springfield Fire and Life Safety 225 Fifth Street Springfield, OR 97477 Phone: 541-726-2293 E-Mail: qqordon@.ci.sprinqfield.or.us Date Received: ~(~O I TO Planner: LM 3