Loading...
HomeMy WebLinkAboutMiscellaneous Field Test & Inspection Report 2011-3-3 Carlson Testing, Inc. Bend Office Geotechnical Office Eugene Office Salem Office Tigard Office (541) 330-9155 (503) 601-8250 (541) 345-0289 (503) 589_1252 (503) 684-3460 REPORT OF 4 X 8 CONCRETE CYLINDRICAL TEST SPECIMENS Test Methods: ASTM C 39/C 172/C 1064/C 138/C 31/C 143/C 231/C 1231 Date Molded: 02/03/2011 Date Received: 02/04/2011 Job Number: El101l3!. Permit #: SPR2010' 00269 Client: MCDONALDS USA LLC- CLINT CAMERON Project: MCDONALDS SPRINGFIELD - REMODEL Address: 3405 GATEWAY ST - SPRINGFIELD, OR Weather: SUNNY Test Time: 2: 30 PM JurisdictioJ: SPRINGFIELD I . I Cast By: S. DAUGHTRY I I Ticket#: I Air Temp. at Sampling Time: Contractor: RICH DUNCAN CONSTRUCTION INC - SCOTT JACKSON Subcontractor: Concrete Supplier: MINI MIX CONCRETE Truck #: 25 Load #: 1 51 Cylinders were cast for the following locations: WEST CORNER OF SOUTH BAY FOOTING /STEM WALL Total Concrete Placement Location: NORTH WEST,SOUTH WEST,SOUTH BAY SOUTH WEST AND SOUTH EAST CORNERS, FOOTING/STEM WALLS AND SLAB Strength Requirement: 3000 Mix Number: 3500 3/4 psi fc @ 28 Days Slump: Concrete Temp: ~ 3.0011 % Air: Max Agg: 3/411 Cubic Yards: 2 1.9% Admix! Amt: Register Number: 0001195 Lab Location: EUGENE I I Set Test @ Test Total Avg. Area . Unit I Type Of Cap Tested No. Davs Date Load Diameter PSI Fracture Tvne By 7 02/10/2011 34575 3.99 12.50 2770 I 2 PAD 60 3RT 28 03/03/2011 I 28 03/03/2011 I 28 03/03/2011 I I I I Distribute attachments. Average fc @ '28 days I D Please see reverse side for additional informatioJ. Job Number: E1101131. Register Number: 0001195 Date Molded: 02/03/2011 Project: MCDONALDS SPRINGFIELD - REMODEL \ " < I in. [25 mm] Type 1 Reasonable well.fanned cones on both ends, less than 1 in. [25 mmJ of cracking through caps Type 2 Well-Fonned cone on one end, yenical cracks running through caps. no well-defined cone on other end Type 3 Columnar vertical cracking through both ends, no well-formed cones r Type 4 Diagonal fracture with no cracking through ends; tap with hammer to distinguish from Type 1 Type 5 Side fractures at top or bottom (occur commonly with unbanded caps) Type 6 Similar to Type 5 but end of cylinder is pointed Asterisked (*) average unit PSI.test results did not meet listed acceptance criteria. Remarks: MCDONALDS USA LLC - CLINT CAMERON TO: CITY OF SPRINGFIELD BUILDING DEPARTMENT DIBBLE ENGINEERING - ROBE DIBBLE RICH DUNCAN CONSTRUCTION INC - SCOTT JACKSON RICH DUNCAN CONSTRUCTION INC - NATE COOKE Project Manager: B. LEACH Reviewed By: Reviewed On 02/11/2011 Our reports pertain to the material tested/inspected only. Information contained herein is not to be reproduced, except in full, without prior authorization from this office. Under all circumstances, the information contained in this repon is provided subject to all tenus and conditions of CTI's General Conditions in effect at the time this report is prepared. No party other than those to whom cn has distributed this report shall be entitled to nse or rely upon the infonuatlon contained in this document. ... ," Carlson Testing, Inc. Bend Office Geotechnical Office Eugene Office Salem Office Tigard Office (541) 330-9155 (503) 601-8250 (541) 345-0289 (503) 589-1252 (503) 684-3460 Daily Report of Structural Steel Client: MCDONALDS USA LLC - CLINT CAMERON Project: MCDONALDS SPRINGFIELD - REMODEL Address: 3405 GATEWAY ST - SPRINGFIELD, OR CTI representative S. DUGGER OBOA 623 was on site this date Feb. 16, 2011 Permit SPR2010-00269 Jurisdiction: cn Job #: SPRINGFIELD E1101131. to perform Special Inspection for: PO Numbe,!: , , Location of steel inspection [to include grid lines, elevations (floors) and drawing details]: I INSPECTED WELDMENTS FOR TUBE STEEL TRASH ENCLOSURE FRAME. (4) I TUBE STEEL COLUMNS AND (2) I TUBE STEEL HEADER BEAMS. THE PROCESS USED WAS I FCAW-G USING E71T-l WIRE WITH C02 GAS SHIELDING. I THE WELDS CONSISTED O? SINGLE PASS FILLET WELDS I AND FLF~E BEVEL GROOVE WELDS. THE FILLET WELDS I FOR TUBE TO BASE PLATE WERE 1/4". THE FLARE I BEVEL WELDS WERE FILLED. I DRAWINGS FOR THIS WORK ATTHE SHOP. THESE WELDS I WERE DONE USING A HAND SKETCH WITH NO. WELD SIZE I S?ECIFIED. THE WORK iREQUIRES ENGINEER'S REVIEW Yes NoN/A I AND WRITTEN .ACCEPTANCE FOR 'IAS-BUTLTlT CQND!'I'IQE. I NOTE THE COMPLETED WELDS MEET THE VISUAL I ACCEPTANCE CRITERIA SET FORTH BY AWS D1.1 FOR WELD PRO?ILES AND FIJLER MATERIALS USED. I I I I REPORT SUMMARY I I. Work inspected was: W Completed D In progress 2. Completed work inspectbd was not in compliance with D Approved plans and: specifications W Shop drawings D RFI 0 Design change D Submittal D N/A Document #(s) NEED I Dated 3. Noncomphance nem(s) lere noted this date. details on following pagers). [jj Yes D No D N/A 4. Noncompliance item(s) \vere reinspected this date, details on following page(s). I DYes D No W N/A D Conform D Remain in progress Report(s) fmdings were diLussed and left with DAN I I DFS #(s) SCOPE OF INSPECTION I. Checked in with superintendent, client or shop rep. Name: D.2\N Company: DANS STEEL 2. Inspection was "IBe' W Continuous 3. Wark performed: D In the field W D Periodic At fab shop D_ZU\1S STEEL 4. If shop inspection do they have fabrication and QC procedures? W Yes D No D N/A INSPECTION 1. Reviewed previous inspection reports? X 2. Verified steel materials are in compliance by reviewing random samples of the mill test reports, steel ID X markings or other documentation. 0 Verified weld filler materials confof!1l. o. X 4. Checked steel members to see thev were fabricated and erected in accordance with the workmanship and X tolerances required. 5. Checked welded studs and structural connections were installed as required. X 6. Verified high strength bolts and fasteners conform. X 7. Verified the quality of welds produced by welders, welding operators, and tackers confonn. X S. Verified steel frame joint details for bracing, stiffening, member locations. and application of joint details at each X connection are in compliance by random sampling. WELDER INFORMATION Welders Name: Certification #: MIKE SWEAR INGER & ROBERT DESANTIS 2831-C1329 & 7764 Yes No N/A 1. Verified the contractor's Welding Procedure Specifications are in conformance with X A WS requirements. 2. Verified the essential variables outlined in the Welding Procedure Specifications were X employed during execution of the work. 3. Verified the weldability of reinforcing steel other than ASTM A 706. X D See additional report pagers). D Distribute attachments. THERE WERE NO APPROVED of DANS STEEL Based on the Code. approval is r~qUired from the Building Official before the SPECIAL INSPECTED ltems noted above can be covered. Carlson Testing has no authority to direct work of contractors or subcontractors. - Page _of _ ... Daily Report of Structural Steel en Job #: El101l31. For: 02/16/2011 , Project: MCDONALDS SPRINGFIELD ~ REMODEL Notes: In some cases more than one box may be checked for a given item on the front page. Our reports pertain to the material tested/inspected only. Information contained herein is not to be reproduced, except in n without prior authorization from this office. Under all circumstances, the information contained in this report is provided subject to all terms and conditions of CTrs General Conditions in effect at the time this report is prepared. No party other than those to whom CTI has distributed this report shall be entitled to use or rely upon the information contained in this document. Ifthere are any further questions regarding this matter. please do not hesitate to contact this office. Respectfully submitted, CARLSON TESTING, INC. Reviewed By: Steven Dugger Review Date: 02/17/2011 SLD/LS MCDONF~S USA LLC - CLINT CAMERON TO: CITY OF SPRINGP!ELD BUILDING DEPARTMENT DIBBLE ENGINEERING - ROBE DIBBLE RICH DUNCAN CONSTRUCTION INC SCOTT JACKSON RICH DUNC~ CONSTRUCTION INC - NATE COOY~ .. c" ~ If. ~ "0 => ....: '" .." 0 N ,., Z < Z U U - e " " - .!:; p' '0' ~ ~ ~ - t "' u <: '" '"' "0 ~ ~tl - ~ :5t c u ,... ~ 0. in i= u ~ ~ ! <; u Ul '-< "' E-< " '" OJ Ul i2 0 "' z <: '" " H 0 E-< Cl '" '" Cl '" U '" '" '" '" ~ 0 00 H 0 '" H " '" - '" 0 " Z U '" Ul '" 0 Ul '" t9 U H '" Z U E-< " Ul H ! <: <: H '" U Ul @ Z H <: E-< .>: OJ '" '" Cl E-< ~ OJ 0 ~ E-< ~ " Cl ~ H '" OJ '" ::l '" '" :> '" '" '" 0 E 0 Z '" 0 '" 0 " :i! Z '" H " 8 " E-< <: Ul u '" E-< 0 OJ 0 OJ '-< '"' " Z H Cl U Ul :> z z z OJ '" 0 '" H ~ '" U OJ " Ul >2 '" . E-< <: 0 " '" '"' '" OJ ~ 0: '" H E-< '" '" " U, U '" Z 00 '"' - H 0 H , '" OJ '" '" '" Ul '" E-< 00 '" Z <: E-< ~ r; '" '" Ul " H H 0 ~ N .. "- '" ::l H "- I N 0 f 0 I I '"' Ul I 0 . Z ~. 'It 0 ~ ::.. 00 " " :oJ) ;;; a ::;;: u " .0' - ::.. " z '" '" E-< IX z<: 00.0) O::CIJ....:i "'ClOO '" 00 ~GH UZCl H :-<00:) Z,",OO ;.;HO '"'''''' UOO '0 '"''' vW:Z; ....:!H...., '"''"'" "'''' <:Z'" UlHZ :JO::H "'" UlUlZ o '" '"''" <:0'" Z '"' 0,"00 ClE-<OO l)H;-J :;:uo ~ ,.. v :oJ) '" ~ Ul '" u 8 E-< E-< o U Ul '" '" o o u '" E-< <: Z u Z H u Z ;.; Z o H E-< U " '" t:; Z o u Z o H E-< U " '" E-< Ul Z o u 6 Z ;:0 " ~ u Z " o u ;.; '" U H '" Carlson Testing, Inc. Bend Office Geotechnical Office Eugene Office Salem Office Tigard Office (541) 330-9155 (503) 601-8250 (541) 345-0289 (503) 589-1252 (503) 684-3460 REPORT OF 4 X 8 CONCRETE CYLINDRICAL TEST SPECIMENS Test Methods: ASTM C 39/C 172/C 1064/C 3l/c 143/C 231/C 1231 Datet.folded: 01/19/2011 Permit #: SPR2010-00269 Client: MCDONALDS USA LLC - CLINT CAMERON Date Received: 01/20/2011 Job Number: E1101131. Project: MCDONALDS SPRINGFIELD - REMODEL Address: 3405 GATEWAY ST - SPRINGFIELD, OR Contractor: RICH DUNCAN CONSTRUCTION INC - SCOTT JACKSON Subcontractor: Concrete Supplier: MINI MIX CONCRETE Truck #: 25 Load #: 1 Test Time: 8:05 AM JurisdictioJ: SPRINGFIELD I I Cast By: S. DAUGHTRY I I Ticket#: I Air Temp. at Sampling Time: Weather: OVERCAST 40 Cylinders wer~ cast for the following locations: DRIVE UP WINDOW CONTINUOUS FOOTING AND SPREAD FOOTING WITH STEM WALLS Total Concrete Placement Location: DRIVE UP WINDOW CONTINUOUS FOOTING WITH STEM W.~LS P~D SPREAD FOOTING Strength Requirement: 3000 Mix Number: 3500 3/4" Admix/Amt: NONE psi fc @ 28 Days Slump: 6.00" % Air: 1.8% Concrete Temp: ~ Max Agg: 3/4" Cubic Yards: 1. 5 Register Number: 0001170 Lab Location: EUGENE Set Test @ Test Total Avg. Area Unit I Type Of Cap Tested No. Days Date Load Diameter PSI Fracture Tvne Bv 7 01/26/2011 56255 4.00 12.56 4480 I 2 PAD 60 SD 28 02/16/2011 73465 3.99 12.50 5880 I 2 PAD 60 SD 28 02/16/2011 74445 3.99 12.50 5960 I 2 PAD 60 SD 28 02/16/2011 77615 3.99 12.50 6210 I 2 PAD 60 SD I I I Distribute attachments. Average fc @ 28 days 6020 I o Please see reverse side for additional informatioJ. , . Job Number: E1101131. Register Number: 0001170 Project: MCDONALDS SPRINGFIELD - REMODEL Date Molded: 01/19/2011 <: 1 in. [25 mm] Type] Reasonable well-fonned cones on both ends. less than 1 in. [25 mm] of cracking through caps Type 2 Well-Fomled cone on one end, vertical cracks running through caps, no well-defined cone on other end Type 3 Columnar vertical cracking through both ends. no well-fonned cones '" \ Type 4 Diagonal fracture v.ith no cracking through ends: tap with"harnrr1er to distinguish from Type] Type 5 Side fractures at top or bottom (occur commonly with unhanded caps) Type 6 Similar to Type 5 but end of cylinder is pointed Asterisked (*) average unit PSI test results did not meet listed acceptance criteria. Remarks: MCDONALDS USA LLC - CLINT CAMERON TO: CITY OF SPRINGFIELD BuILDING DEPARTMENT DIBBLE ENGINEERING - ROBB DIBBLE RICH DUNCAN CONSTRUCTION INC - SCOTT JACKSON RICH DUNCAN CONSTRUCTIOK INC - NATE COOKE Project Manager: B. LEACE Reviewed By: Reviewed On 02/17/2011 Our reports pertain to the material tested/inspected only. Infonnation contained herein is not to he reproduced. except in full, without prior authorization from this office. Under all circumstances, the information contained in this report is provided suhject to all tenns and conditions of CTI's General Conditions in effect at the time this report is prepared. No party other than those to whom CTI has distributed this report shall be entitled to use or rely upon the infonnation contained in this document.