HomeMy WebLinkAboutPermit Building 2010-10-18
ii~ 10/18/2010
City of Springfield 10:35:14AM
Building Permit & Inspection Summary Job #:
COM2010-00754
225 Fifth Street
541-726-3753 Phone Job Address: 600 HAYDEN BRIDGE WAY Springfield
541-726-3676 Fax Scope of Work: Kitchen
Project Status: OK to Issue Description of Work: Kitchen remodel
Owner & Contractor(s)
Name Address City. State, Zip Phone
CON ESCHENBACHER HOMES INC 1574 COBURG RD EUGENE OR 97401 541-937-2636
ELC HOME COMFORT HEATING & AIR INC PO BOX 24205 EUGENE OR 97402 (541) 345-283
FIR OMLID & SWINNEY FIRE PROTECTIO 157 S 47TH STREET SPRINGFIELD OR 97478 541-741-1775
OWN INTERNATIONAL CHURCH OF THE FO 600 HAYDEN BRIDGE WA SPRINGFIELD OR 97477 541-726-8449
Valuation of Proiect
Date
Occupancy Construction Type Cost Per Su Ft Su Ftl! Valuation Calculated Staff
EstiIrulte EstiIrulte $ 1.00 60,000.00 $60,000.00 2010/06/10 DJB
$60,000.00
Fees Paid
Description Amount Paid Date Paid Receipt #
Plan Review Comm/IndlPublic $334.07 06/10/2010 3201000000000000293
Penn Serv/Fdr 200 amps or less $81.00 07/07/2010 3201000000000000397
Add, Alter, Extend Circ $55.00 07/07/20 I 0 3201000000000000397
Add, Alter, Extend Circ Ea Add $54.00 07/07/2010 3201000000000000397
+ 12% State Surcharge $22.80 07/07/2010 3201000000000000397
+ 5% Technology Fee $9.50 07/07/2010 3201000000000000397
FLS Safety Systems Review $120.00 08/05/2010 2201000000000000928
***+ 10% Administrative Fee*** $12.00 . 08/05/2010 2201000000000000928
Total Amount Paid $688.37
Plans Reviewed
Department Received Due Date Completed Result Reviewer Comments
Planning Review 06/15/20 I 0 06/15/2010 APP EMM Interior remodel only. Needs
Final Site Inspection for
DRC2009-00038 for addition
of this room. Please call
Andy Limbird at (541)
726-3784. PLEASE GIVE
48 HOURS NOTICE.
lof5
iiE~
City of Springfield
Building Permit & Inspection Summary
10/18/2010
10:35:14AM
Job #:
COM2010-00754
225 Fifth Street
541-726-3753 Phone
541-726-3676 Fax
Project Status: OK to Issue
Fire Department Review
06/15/20 I 0
Structural Review
Structural Review
06/15/20 I 0
07/13/2010
Job Address:
600 HAYDEN BRIDGE WAY
Springfield
Scope of Work: Kitchen
Description of Work: Kitchen remodel
06/18/2010 APP
GRG
Plans Review: church kitchen
remodel. Job
#COM2010-00754.
Occupancy Classifcation:
A-2. Construction Type: V-B.
Plans reviewed under the
2007 Springfield Fire Code
and 2007 Oregon Structural
Specialty Code.
Provide fire extinguishers
with a minimum rating of
40-B within 30 feet of travel
distance of the accessory
kitchen area. The top of the
extinguisher( s) shall be
between 3 and 5 feet above
finished floor (2007
Springfield Fire Code
906/NFPA 10, A.5.4.1.3).
Provide a letter to Springfield
Fire Marshal Al Gerard
verifying that the
non-commercial kitchen
appliances will be used for
heating or occasional
preparation of foods and not
be used for prepping offoods
producing grease laden
vapors meeting Oregon
Mechanical Specialty Code
Interpretation 507.2.3. The
letter shall be received and
approved prior to final
occupancy. .
Completed I st Plan Review
Received mechanical
specifications for Type I
commercial kitchen hood, but
missing submittal of fire
suppression system plans for
Type I hood. Also, received
incomplete site plan with
incomplete specifications for
accessible parking.
06/22/2010 WE
07/13/2010 WE
KLK
KLK
.
20f5
'1~.""'!.""''''.''~'''...''
Wit. '
, ... .
11 .
. ,
.....""'..."... . .1
City of Springfield
Building Permit & Inspection Summary
10/18/2010
1O:35:14AM
Job #:
COM2010-00754
225 Fifth Street
541-726-3753 Phone
541-726-3676 Fax
Job Address: 600 HAYDEN BRIDGE WAY
Scope of Work: Kitchen
Description of Work: Kitchen remodel
Project Status: OK to Issue
Structural Review
07/14/2010
07/14/2010 WE
KLK
Structural Review
07/20/20 I 0
07/20/2010 WE
KLK
Fire Department Review
07/20/20 I 0
07/20/2010 APP
GRG
Springfield
Left phone message for
architect, Rodd Hansen, to
provide engineering
calculations and
specifications corresponding
to the structural changes to
the;kitchen area- new
footings, columns and beams
(is well as new footing,
column, beam and truss
connections for all lateral and
verticalioads.
Reviewed beam calc. and
footing calc. from architect.
Per phone call with architect,
Architect to provide 1)
structural design criteria and
2) a wet-signature stamped
letter stating that there are not
any lateralioads imposed on
the new columns, beams and
footings.
Plans Review: Installation of
Type I hood, rated shaft and
restaurant type exhaust fan for
kitchen remodel. Job
#COM2010-00754.
Contractor: HCH Mechanical.
Plans Reviewed under the
2007 Springfield Fire Code,
2007 Oregon Mechanical
Specialty Code.
This deferred submittal shows
the proposed installation of a
Captive Aire roof mounted
restaurant exhaust fan listed
as meeting UL705 and UL762
standards; a Captive Aire
model BD-2 hood and plenum
system and a steel duct shaft
surrounded by 3M 1 hour
rated fire wrap except for the
16 inch space below the
ceiling which is sheet rocked.
Plans appear to meet fire code
requirements.
30f5
8~r.~I..-_...~...
Wit.. ,
. ,
.___". .___.. _ 1
City of Springfield
Building Permit & Inspection Summary
10/18/2010
10:35:14AM
Job #:
COM2010-00754
225 Fifth Street
541-726-3753 Phone
541-726-3676 Fax
Project Status: OK to Issue
Job Address: 600 HAYDEN BRIDGE WAY
Scope of Work: Kitchen
Description of Work: Kitchen remodel
Fire Department Review
07/29/20 I 0 APP
GRG
07/29/20 I 0
Structural Review
08/03/20 I 0
08/03/2010 WI
KLK
Structural Review
08/06/20 I 0
08/06/2010 APP
KLK
Springfield
Plans Review: Commercial
Kitchen Hood and Duct Fire
Suppression System. Job
#COM201O-00754. Designer:
Steve Francalancia/Chuck
Harper. Contractor: Omlid
and Swinney Fire Protection.
Plans reviewed under the
2007 Springfield Fire Code,
2002 edition ofNFP A 17 A
Standard for Wet Chemical
Extinguishing Systems and
2004 edition ofNFPA 96,
Standard for Ventilation
Control and Fire Protection of
Conunercial Cooking
Operations.
This submittal is for the
protection of a newly installed
Type I hood and a
commercial applicance
featuring a combined 6 burner
range and small griddle. The
kitchen suppression system is
an Amerex KP275 system. It
feeds a 16416 duct nozzle (I
flow point) protecting the
duct (less than 50 perimeter
inches); an 11982 nozzle for
the five foot long plenum (I
flow point), a 14178 nozzle
protecting 4 burners (2 flow
points); an 11982 nozzle
protecting the other two
burners; and an 11982 nozzle
protecting the griddle.
Plans appear to meet code
requirements.
Received letter from the
architect confirming structural
changes to the kitchen effect
gravity loads only. There are
not any lateral loads imposed
on the effected. columns,
beams and footings. WI:
Public Works
Provide signed electrical
permit application.
40f5
225 Fifth Street
541-726-3753 Phone
541-726-3676 Fax
Project Status: OK to Issue
Public Works Review
07/30/2010
Inspections
Final Site Plan
Framing Inspection
Drywall
Ceiling Grid
Fire Dept Kitchen Supp System
Fire Department Final
Final Building
Underfloor Plumbing
Rough Plumbing
. Final Plumbing
Rough Mechanical
Final Mechanical
Rough Electric
Final Electric
Electric Service
City of Springfield
Building Permit & Inspection Summary
Job Address: 600 HAYDEN BRIDGE WAY
Scope of Work: Kitchen
Description of Work: Kitchen remodel
08/06/20 I 0 APP
EW
10/18/2010
1O:35:14AM
Job #:
COM2010-00754
Springfield
PW received this application
on.7/30/2010.
SDC Worksheet is attached
Inspections Conducted
Comments
Call Andy Limbird at (541)
726-3784 for Final Site Inspection
of Fireside Room before Final
Building Inspection at (541)
726-3784. Please give 48 hours
notice.
Date
Result
Called Sub
07/26/20 I 0
50f5
Inspector
EMM
OK
GAD