HomeMy WebLinkAboutCorrespondence FLS 5/7/2008 . . . Page 1 of 1 L1MBIRD Andrew From: GORDON Gilbert Sent: Wednesday, May 07, 2008 3:33 PM To: L1MBIRD Andrew Cc: GERARD Alan; FECHTEl Melissa Subject: Site Plan Modification Major DRC2008-00024 City of Springfield/Police-Justice Center Andy, Here are the Fire Department comments for the ancillary building modifications: Site Plan Modification-Major DRC2008-00024 City of Springfield/Police DepartmenUJustice Center Address: 230 4th Street Existing Use: Parking lot and vacated public street Proposal: Add secure parking lot and ancillary building Planner: Andy Limbird, Planner II Fire Department Plans Review Comments: Access: OK. Provide Knox keyed gate switches at both east and west electric gate entrances (Springfield Fire Code 506.1.1). Water Supply: OK. Landscaping: A 3 foot clear space shall be maintained around the circumference of fire hydrants (2007 SFC 508.5.5). Landscaping: Immediate access to fire department connections shall be maintained at all times and without obstruction by fences, bushes, trees, walls or any other object for a minimum of 3 feet (2007 SFC 912.3). Gilbert R. Gordon Deputy Fire Marshal Springfield Fire and Life Safety 225 Fifth Street Springfield, OR 97477 Phone: 541-726-2293 E-Mail: ggordon@cLsRrinqfield.or.us 5/7/2008 . Data Received: ,h/,2IJIl{. ~ / Planner: AL