CLIENT
PROJECT
EWEB
500E. 4th Ave.
Eugene, Oregon 97440
BPNO.
DATE CAST
STRENGTH REQUIRED
STRENGTH PLACED
PRODUCT CODE
ADDITIVES
LOAD NO.
CONCRETE TEMP
AIR TEMP
POUR LOCATION
11-17-09
4000 psi
4000 psi
40K1UOKS
CAST BY
SACKS
CEMENT
Eclipse: Super
1 TICKET NO.
65"F YARDAGE
49" F WEATHER
East wall of filter basin.
LOAD 1 SAMPLED
1" lift in wall.
~
Compressive Strength of Concrete
(ASTM C 39)
Hayden Bridge Water
Filtration Plant Expansion
Springfield, Oregon
DATE
PROJECT NO.
REPORT NO.
12-15-09
2087168
6763
11-18-09
4" x8"
Knife River
3/4"
2.9%
6"
12:20 PM
ASTM C 31
AVERAGE
TEST AGE AREA WEIGHT TOTAL COMPRESSIVE STRENGTH TIM E OF TYPE OF
DATE (DAYS) (IN.') (LBS) LOAD (LBS) STRENGTH (PSIl (PSI) TEST FRACTUREH
I 11-24-09 7 12.56 8.51 I 58890 4690 2:20 PM 3
f 12-15-09 28 12.56 8.55 I 69520 5540 8:10AM 2
12-15-09 28 12.56 8.53 I 72155 5740 ,5640 8:15AM 2
I Hold I
"1-End Cones 2 . Cone/Split 3-Columner 4-Oiagonal 5 - Side (top Of bottom) 6 - Side (pointed top or bottom)
2008-00225
D. Delatte
DATE RECEIVED
SPECIMEN SIZE
SUPPLIER
MAX SIZE AGG.
AIR CONTENT
SLUMP
TIME
SPECIMEN STORAGE
3501031
10.0 OF
Overcast
40.0
REMARKS: Jake Stucky (Wildish) and Mike Stickling (EWEB) were advised of on-site test results.
Reviewed By:
A.~/J~
Michael L. Mey'; .
Technical Manager
c:
EWEB- Mike Stickling (email)
EWEB- Wally McCullough (email)
OBEC- Pete Slocum (email)
Wildish Building Co.- Kevin Fitzjarrell (email)
Wildish Building Co.- Jake Stucky (email)
City of Springfield
Knife River
MLM:sc
This report andlor enclosed test data is the confidential property of the client to whom it is addressed and pertains to the specific
process and/or material evaluated. As such, information contained herein shall not be reproduced in part or full and/or any part
thereof be disclosed without FEI Testing & Inspection, Inc.'s written authorization.
7f:IJ NW ComellAvenue' Corvallis, Oregon 9733O. phone (541) 757-4698 . fax (541) 757-2991
29540 B Airport Road . Eugene, Oregon 97402. phone (541)684-3849' fax (541)684-3851
62979 NE Plateau DIive, Suile3' Bend, Oregon 97701. phone (541)382-4844 . fax (541) 382-4846
~
~ftl
Page 1 of 1
1I1~'IIlLhI'..n.":'lllhtn.m"
(JoJ.,(,;..;.,.."J & Construdioo SaV.ces
Daily Field Report
Client: EWEB Project: Hayden Bridge Water Filtration Date: 12-14-o9
500E. 4th Ave. Plant Expansion Project No.: 2087168
Eugene, Oregon Springfield, Oregon Report No.: E-24770
Inspector: D. Delatte
10 No.: 1080867-88
ICC
Inspection of: Reinforced Concrete Weather: Overcast Continuous Inspection: 0
Contractor: Wildish Building, Co BPNo.: 2008-00225 Periodic Inspection: 0
Performed final inspection on the reinforcing steel at the following locations: walkway
along the top of center wall; east wall of settle water channel: two (2) gullet slabs at
elevation :1:593.0 all within filter basin and weir box walls and columns. Preliminary
reinforcing steel inspection was performed by our office on 12-07-09 thru 12-11-09 (ref:
FEI reports E24734 and E24766).
Observed the placement of 37.0 yards of Knife River 4000 psi concrete (mix
2440KIUOKS) into areas noted above. Concrete was placed by pump and was
mechanically consolidated. Cast one (1) set of four (4) 4" x 8" concrete test cylinders
from load 1. Slump - 6": air temperature - 35F; concrete temperature - 55F; air
content - 5.9%.
Jake Stucky (Wildish) was advised of the on-site test results.
To the best of our knowledge, the work inspected was in accordance with plans dated
0212008 and applicable workmanship provisions of the I.B.C., except if noted above.
Reviewed By:
;h . 't;'.~ ---
Michael L. ~eyr
Technical Manager
ru [g@[g O~[g
~ DEe 1 7 2009
-=\\
c:
EWEB- Mike Stickling (email)
EWEB- Wally McCullough (em ail)
OBEC- Pete Slocum (em ail)
Wildish Building Co.- Kevin Fitzjarrell (email)
Wildish Building Co.- Jake Stucky (email)
City of Springfield
..:::J
MLM:sc
This report andlor enclosed test data is the confidential property of the client to whom it is addressed and pertains to the specific
process andlor material evaluated. As such, information contained herein shall not be reproduced in part or full and/or any part
thereof be disclosed without FEI Testing & Inspection, Inc.'s written authorization.
750 NW ComeIAverue' CavaIis, Oeg:n 97330' p-a-e(541) 757-4698' fax (541) 757-2991
29540 B AijxJrt Road . Eugene, Oeg:n 97402 . p-a-e (541) 684-3849 . fax (541 )684-3851
62979 NE Plateau Drive, Suite 3 . Bend, Oregon 97701 . phone (541) 382-4644 . fax (541) 3824846