HomeMy WebLinkAboutBuilding Correspondence 1989-9-5 . . General Growth of California, Inc. 15821 VENTURA 80ULEVARD. SUITE 525 ENCINO, CALIFORNIA 91436 FAX: (818) 907-8841 (818) 907-3400 September 5, 1989 Mr. Don r-tlore Building Division CITY OF SPRINGFIELD Development Services 225 North 5th Street Springfield, Oregon 97477 Subject: Radiant Heating Systems Sears Auto Center Gateway Mall/Springfield, Oregon Reference: Inspectors note of 8/25/89. Dear Mr. r-tlore: The following information is furnished in response to the referenced note: Attachment Number 1,2, and 3 provide general information concerning the installation. Attachments Number 4 amd 5 covers ventilation requirements. Since the volume of the service center, 196,700 cubic feet, is not less than 1/20 of the combined input rate in BTU/HR, (6 units @ 60,000 = 360,000 BTU/HR) provisions to supply deficiency in combustion air is not required per Uniform Mechanical Code Sec. 601 (b). The heater manufuacture's combustion air requirement is 1.83 CFM per 10,000 BTU/HR plus 12xl.83 CFM at the CFM at the initial inlet at each radiant heating branch line. In our installation we have 6 burners at 60,000 BTU/HR plus 2 end inlets which requires a total of 109.8 CFM. The vacuum pump has adequate capacity to provide this. Si ncerely, ///-,/~.d/~ Robert Balfou-r/-- Mechanical Engineer, M 011462 RB/ftlllc WP47