Daily Field Report
Client:
Project: Hayden Bridge Water Filtration
Plant Expansion
Springfield, Oregon
Date:
Project No.:
Report No.:
Inspector:
10 No.:
EWEB
500E. 4th Ave.
Eugene, Oregon
YlSi ~dtv\ f:>~
11-17-09
2087168
E-24582
D. Delatte
1080867-88
ICC
. Inspection of: Reinforced Concrete
Contractor: Wildish Building
Weather: Overcast..
BP No.: 2008-00225
Continuous Inspection: 0
Periodic Inspection: 0
Performed final inspection on the reinforcing steel for east wall of fiiter basin.
Preliminary reinforcing steel inspection was performed by our office on 11-10-09 (ref:
FEI report E-24515).
Observed the placement of 40.0 yards of Knife River 4000 psi concrete (mix
2440KIUOKS) into walls noted above. Concrete was placed by pump and was
mechanically consolidated. Cast one (1) set of four (4) 4" x 8" concrete test cylinders
from load 1. Jake Stucky (Wildish) and Mike Stickling (EWEB) were advised of the on-
site test resuils. Load 1: slump - 6"; air temperature - 49F; concrete temperature -
65F; air content at beginning of ioad - 3.6% and near middle of load - 2.9%. Air
content at beginning of load 2 - 3.2%. Load 2 was rejected by Mr. Stickling and Mr.
Stucky. Air content at beginning of load 3 - 6.0%
To the best of our knowledge, the work inspected was in accordance with plans dated
02/2008 and applicable workmanship provisions of the I.B.C., except i(noted above.
Reviewed By:
;h. '/11.y-
Michaei L. Meyer
Technical Manager
c:
EWEB- Mike Stickling (emaH)
EWEB- Wally McCullough (em ail)
OBEC- Pete Slocum (email)
Wildish Building Co.- Kevin Fitzjarrell (email)
Wildish Building Co.- Jake Stucky (email)
City of Springfield . . .
MLM:sc
This report an"d/or enclosed test data is the confidential property of the client to whom it is addressed and pertains to the specific
process and/or material evaluated. As such, information contained herein shall not be reproduced in part or full and/or any part
thereof be disclosed without FEI Testing & Inspection, Inc.'s written authorization.
700 rwJ ComeIIAvenue' CavalUs, Oregon 97330, phone (541) 757-4698, fax (541) 757-2991
29540 BAirport Road, Eugene, Qegoo 97402, phone (541) 684;J849 . fax (541 )684-3851
62979 NE Plateau Drive, Sutte 3, Bend, Oregon 97701. phone (541) 3824844 . fax (541) 382-4846
~
~ftt
11til.'I!IIltl:"h\..'n'IIIJ~.m"
GeolP.d1nical & OYlstrUCtiOf\ ServicEs
Compressive Strength of Concrete
(ASTM C 39\
CLIENT
EWEB
500E. 4th Ave.
Eugene, Oregon 97440
PROJECT
Hayden BridgeW;'ter
i-' ~_
"Filtration Plant Expansion
\ l~~ri~gfield, OrT\lof\
nVJ-{fuXl D\1~
\~008-00225 .
DATE
PROJECT NO.
REPORT NO.
11-11-09
2087168
6744
3q5l
BPNO.
DATE CAST 11-04-09 CAST BY D. Delatte DATE RECEIVED 11-05-09
STRENGTH REQUIRED 4000 psi SPECIMEN SIZE 4" x 8"
STRENGTH PLACED 4000 psi SACKS SUPPLIER Knife River
PRODUCT CODE 40-SE7 CEMENT MAX SIZE AGG. 3/4"
ADDITIVES AEA; Super; Eclipse AIR CONTENT 3.6%
LOAD NO. 1 TICKET NO. 3500818 SLUMP 41/2"
CONCRETE TEMP 64' F YARDAGE 4.0 OF. 4.0 TIME 1:40 PM
AIR TEMP 58" F WEATHER Overcast SPECIMEN STORAGE ASTM C 31
POUR LOCATION Two (2) inter tie tunnel walis.
TEST
DATE
11-11-09
12-02-09
12-02-09
Hold
AGE
(DAYS)
7
28
28
AREA
(IN.')
12.56
WEIGHT
(LBSt
8.52
TOTAL
LOAD (LBSt
53840
COMPRESSIVE
STRENGTH (PSI)
4290 )
AVERAGE
STRENGTH
(PSIl
TIME OF
TEST
11:55AM
TYPE OF
FRACTURE"
2
.. 1- End Cones 2 _ Cone/Split 3 - Columnar 4 - Diagonal 5 - Side (lop or bottom) 6 - Side (pointed lop or bottom)
REMARKS: Jake Stucky (Wildish) was advised of on-site test results.
Reviewed By:
A.1f~'
Michael L. Meyer
Technical Manager
c:-
EWEB- Mike Sticklin9 (email)
EWEB- Wally McCullough (email)
OBEC- Pete Slocum (email)
. Wildish Building Co.- Kevin Fitzjarrell (email)
Wildish Building Co.- Jake Stucky (em ail)
City of Springfield
Knife River
MLM:sc
This report andlor enclosed test data is the confidential property of the client to whom it is addressed and pertains to the specific
process and/or material evaluated. As such, information contained herein shall not be reproduced in part or full andlor any part
thereof be disclosed without FEI Testing & Inspection, Inc.'s written authorization.
750 NW Cornell Avenue. Corvallis, Oregon 97330, phone (541) 757-4698, fax (541) 757-2991'
29540 BAirport Road, Eugene, Oregon 97402. phone (541)684-3849' fax (541) 684-3851
62979 NE Plateau Drive, Suite 3, Bend, Oregon 97701. phone (541) 3824844 . fax (541)382-4846
EWEB
500E. 4'h Ave.
Eugene, Ore90n 97440
TEST AGE AREA WEIGHT TOTAL COMPRESSIVE
DATE (DAYS) (IN.'! (LBSI LOAD (LBS) STRENGTH (PSI!
10-21-09 7 12.56 8.43 52275 4160
11-11-09 28 12.56 8.44 64865 5160
11-11-09 28 12.56 8.49 67845 5400
Hold
(~ft)
'1~'llflrt;"lj..'~1.IIIJl.I~I.
CLIENT
DATE CAST
STRENGTH REQUIRED
STRENGTH PLACED
PRODUCT CODE
ADDITIVES
LOAD NO.
CONCRETE TEMP
AIR TEMP
POUR LOCATION
~
G....,;~ ,,1ical&~~
Compressive Strength of Concrete
lASTM C 39\
PROJECT Hayden Bridge Water
Filtration Plant Expansion
3Q'3l\-\cu1 ~g~~n
BP NO.2.Qo.8-00225
DATE
PROJECT NO.
REPORT NO.
11-11-09
2087168
6697
10-14-09 CAST BY D. Delatte DATE RECEIVED 10-15-09
4000 psi SPECIMEN SIZE 4" x 8"
4000 psi SACKS SUPPLIER Knife River
2440KIUOKS CEMENT MAX SIZE AGG. 3/4"
AEA; Super; Eclipse AIR CONTENT 4.2%
1 TICKET NO. 3444295 SLUMP 63/4"
71" F YARDAGE 10.5 OF 10.5 TIME 12:50 PM
66" F WEATHER Overcast SPECIMEN STORAGE ASTM C 31
Two (2) interior 6" channel walls in the northeast and southeast quadrant and two (2) interior 9" walls'
near 24" pipe in the northeast quadrant of filter basin all from slab to bottom side of upper slab.
AVERAGE
STRENGTH
(PSI!
TIME OF
TEST
8:10AM
11:10AM
11:15AM
TYPE OF
FRACTURE-
3
5
2
~ - 5280
REMARKS: Jake Stucky (Wildish) was advised of on-site test results.
.. ,. End Cones 2. Cone/Split 3 - Columnar 4 - Diagon~1 5 - Side (top or botlom) 6 - Side (pointed top orbotlom)
Reviewed By:
/Jl.'-t,~
Michael L.' Meier
Technical Manager
c:
EWEB- Mike Stickling (email)
EWEB- Wally McCullou9h (email)
OBEC- Pete Slocum (email)
Wild ish Building Co.- Kevin Fitzjarrell (email)
Wildish Building Co.- Jake Stucky (em ail)
City of Springfield
Knife River
MLM:sc
This report and/or enclosed test data is the confidential property. of the client to whom it is addressed and pertains to the specific
process and/or material evaluated. As such, infonnatlon contained herein shall not be reproduced in part or full and/or any part
thereof be disclosed without FEI Testing & In"spection, Inc.'s written authorization.
750 rwJ Cornell Avenue . Corvallis, Oregon 97330. phone (541) 757-4698, fax (541) 757-2991
29540 B Airport Road' Eugene, Oregon 97402. phone (541) 684-3849' fax (541) 684-3851
.62979 NE Plateau Drive, Suite 3, Bend, Oregon 97701' phone (541) 3824844 . fax (541) 382-4846
~K
~"''''I
~rt
Page 1 of 1
11!J.I.itl!Ii..1~,,'lj}'II'lmw.!II
Geotechnical & Construction Servire;
Daily Field Report
,
Client: EWEB Project: HaydenBridgeWater Filtration Oate: 11-10-09
500E. 4th Ave. Plant Expansion Project No.: 2087168
Eugene, Oregon Springfield, Oregon Report No.: E-24515
3151 Wu-tckY'\bn~ Inspector: D. Delatte
10 No.: 1080867-88
ICC
Inspection of: Reinforcing Steel! Weather: Overcast Continuous Inspection: 0
Epoxy Anchors
Contractor: Wildish Building BP No.: C2008~OO225 Periodic Inspection: 0
Performed preliminary inspection on the reinforcing steel for east wall of filter basin.
Reinforcing steel was checked for grade, size, laps, quantities, locations, ties,
clearance and supports. A final inspection will be performed prior to concrete
placement.
- -~ .-.- --, ~-
..'
Also, observed the inst?lIation;Of;four'(4) 5/8'x:.l;l';::~taif\less~steeLall-thread anchors
.into.concrete'wall for stopJog,reinforcing bars, tWo\2Eanchors at each end. Prior to
,installat!on,,'the predrillea--holes-were- ~leangd::'With- a:::im:ish: ~nd _ compressed air.
Verified minimum embedment-depth-of-6". Anchors'were secured with, Epcon A-7
epoxy adhesive (ISS -''ER55601 expiration date 12-29-10). .'
To the best of our knowledge, the work inspected was in accordance with plans dated
02/2008 and applicable workmanship provisions of the I.B.C:, except if noted,above.
Reviewed By:
~~~~D\if~.~
1. NOV 1 7 2009 [
-I !d'
/h.-i. ~
Michaei L.:~eF
Technical Manager
c:
EWEB- Mike Stickling (em ail)
EWEB- Wally McCullough (em ail)
OBEC- Pete Slocum (eniail)
Wildish Building Co.- Kevin Fitzjarrell (email)
Wildish Building Co.- Jake Stucky (email)
City of Springfield
MLM:sc
. '. ' ~ t .
." .
This repof1. andlor enclosed test data is the confidential property of the client to whom it is addressed and pertains to the specific
process and/or material evaluated. As such, information contained herein shall not be reproduced in part or full and/or any part
.... ." thereof be disclosed without FEl Testing & Inspection, lnc.'s written authorization.
750 NW CanelJAvenue' Cavallis, Qegoo 97330' pIlcr1e(541) 757-4698, fax (541) 757-2991
29540 BAirpcx1Road' Eugene, Oregon 97402, phone (541)684;)849. fax (541 )684-J851
62979 NE Plateau Drive, Suite 3, Bend, Oregon 97701 . phone (541) 3824844 . fax (541) 382-4846
(~ft)
11.'11""'."'''''1111'.'''. GeotP.d1nirnl & Construc:lion Servirns
CLIENT
DATE CAST
STRENGTH REQUIRED
STRENGTH PLACED
PRODUCT CODE
ADDITIVES
LOAD NO.
CONCRETE TEMP
AIR TEMP
POUR LOCATION
LOAD 1 SAMPLED
TEST
DATE
11-09-09
11 :30-09
11-30-09
Hold
AGE
(DAYS)
7
28
28
kt
Compressive Strength of Concrete
'ASTM C 39)
PROJECT Hayden Bridge Water
Filtration Plant Expansion
8i5l 4-\~~~J~~nc~
BP NO. I, ~008,00225. ;
DATE
PROJECT NO.
REPORT NO.
EWEB
500E. 4~ Ave.
Eugene, Oregon 97440
11-09-09
2087168
6736
11-02-09 CAST BY A. Fenstermacher DATE RECEIVED 11-03-09
4000 psi SPECIMEN SIZE 4" x 8"
4000 psi SACKS SUPPLIER Knife River
40-SE7 CEMENT MAX SIZE AGG. 3/4"
Super; Eclipse; AEA AIR CONTENT 4.6%
1 TICKET NO. 3500736 SLUMP 8"
630F YARDAGE 9.0 OF 18.0 TIME 10:10AM
4W F WEATHER Partiy Cioudy SPECIMEN STORAGE ASTM C 31
Filter building; east half of suspended slabs above 24" FW/BW pipes and center suspended
walkway, west side.
From suspended walkway.
AREA
(IN.')
.12.56
WEIGHT
(LBSI
8.45
COMPRESSIVE
STRENGTH JPSIl
4510~--
AVERAGE
STRENGTH
(PSIl
TIME OF
TEST
7:35 AM
TOTAL
LOAD (LBS)
56590
REMARKS: Jake Stucky (Wildish) was advised of on-site test results.
.. 1- End Cones 2 - Cone/Split 3 - Columnar 4 - Diagonal 5 - Side (top or bottom) 6 - Side (pointed lop or bottom)
Reviewed By:
;J1.'i.~~
Michael L. Meyl ~
Technical Manager
~.~~~u~~~.
1 NOV 1 8 2009
c:
EWEB- Mike Stickling (email)
EWEB- Wally McCullough (email)
OBEC-. Pete Slocum (email)
Wildish Building Co.- Kevin Fitzjarrell (email)
Wildish Building Co.- Jake Stucky (email)
City ot Springfield
Knife River
MLM:sc
.:!J
TYPE OF
FRACTURE*.
3
This report and/or enclosed test data is the confidential property of the client to whom it is addressed and pertains to the specffic
process and/or material evaluated. As such, information contained herein shall not be reproduced in part or full and/or any part
thereof be disclosed without FEI Testing & Inspection, Inc.'s written authorization.
750 NW Cornell Avenue' Corvallis, Oregon 97330 . phone (541) 757-4698 . fax (541) 757-2991
29540 B Airport Road . Eugene, Oregon 97402' phone (541) 684-3849 . fax (541) 684-3851
62979 NE Plateau Drive, Suite 3 . Bend, Oregon 97701 . phone (541) 3824844 . fax (541) 382-4846
~
~fEt
Page 1 of 1
11~'llflCl;.l~.'~a'IlIJ\'IIII/LII
Gcv""'; .nlcal & Construction Servire; .
Daily Field Report
Client: EWEB Project: Hayden Bridge Water Filtration Oate: 11-04-09
500E. 4th Ave. Plant Expansion Project No.: 2087168
Eugene, Oregon Springfield, Oregon Report No.: E-24480
2)15l ~O>.-\~ 6n:~ Inspector: D. Delatte
10 No.: 1 080867-88
ICC
Inspection of: Reinforced Concrete Weather: Partly Cloudy , Continuous Inspection: 0
Contractor: Wildish Building BPNo.: @08-00225 ' Periodic Inspection: 0
Performed final inspection on the reinforcing steel for two (2) inter tie tunnel walls. A
preliminary inspection was performed on 11-03-09 (:ef: FQr:.eport ~:24452).
.-- -~~.-
Observed the placement of-4,0-yards'of Knife River 4000 psi. concrete (mix 40-SE7)
into areas noted above: Concrete was-placedbywheei.barrow and .was mechanically
consolidated.' Cast one (1) s'.;j 'of fo0r (4) 4'''x.8" compressive. strength cylinders.
Notified Jake Stucky (Wild ish).. of tneon'site resulls:--c. Slump _ - 4 1/2"; concrete
temperature - 64F; air teIl1P~i8ture ~'58F; air-content-':'3.60/o'. -
To the best of our knowledge, the work inspected was in accordance with plans dated
02/2008 and applicable workmanship provisions of the I.B.C., except if noted above.
Reviewed By:
!h,~.~
Michael L. Meyer
Technical Manager
c;
EWEB- Mike Stickling (em ail)
EWEB- Waily McCullough (em ail)
OBEC- Pete Slocum (emaii)
Wildish Building Co.- Kevin Fitzjarrell (em ail)
Wildish Building Co.- Jake Stucky (email)
City of Springfield .
[)~cg~D~~
J NOV - 9 2009
"::\1
};
MLM;sc
This report and/or enclosed test data is the confidential property of the client to whom it is addressed and pertains to the specific
process and/or material evaluated. As such, information contained herein shall nol be reproduced in part or full and/or any part
thereof be disclosed \'Vithout FE1 Testing & Inspection, Inc.'s written authorization.
7m NW ComeIIAvenue' Cavalfrs, Qegoo 97330, phme(541) 757-4698, fax (541) 757-2991
29540 BAirport Road, Eugene, Oregon 97402 . phme (541) 684;)849 . fax (541) 684-3851
62979 NE Plateau Drive, Suite 3, Bend, Oregon 97701 . phone (541) 3824844 . fax (541) 382-4846
EWEB
500E. 4th Ave.
Eugene, Oregon 97440
~ftt
11:L'llml;"I~~'1:1;.IlIJl.IN.
CLIENT
DATE CAST
STRENGTH REQUIRED
STRENGTH PLACED
PRODUCT CODE
ADDITIVES
LOAD NO.
CONCRETE TEMP
AIR TEMP
POUR LOCATION
fJ(
~1;c-~ II ,;cal & C'AYlStnJdion ServicEs
Compressive Strength of Concrete
fASTM C 39\
PROJECT
Hayden Bridge'Water
i ,-
Filtration Plant Expansion
~~:~~
[3.008-00225
11-04-09
2087168
6683
DATE
PROJECT NO.
REPORT NO.
25101
BPNO.
10-07-09 CAST BY A. Fenstermacher DATE RECEIVED 10-08-09.
4000 psi SPECIMEN SIZE 4" x 8"
4000 psi SACKS SUPPLIER Knife River
40-SE7 .CEMENT MAX SIZE AGG. 3/4"
Super; Eclipse; AEA AIR CONTENT 5.5%
1 TICKET NO. 3444076 SLUMP 8"
71" F YARDAGE 10.0 OF 10.0 TIME 12:45 PM
62. F WEATHER Clear SPECIMEN STORAGE ASTM C 31
Filter building 6" walls; southeast quadrant, west half of north and south walls; northwest quadrant, west
half of walls.
AVERAGE
TEST AGE AREA WEIGHT TOTAL COMPRESSIVE STRENGTH TIME OF TYPE OF
DATE (DAYSl (IN.'l (LBSI LOAD (LBSl STRENGTH (PSIl (PSI) TEST FRACTUREH
10-14-09 7 12.56 8.49 56195 4470 8:50 AM 2
11-04-09 28 12.56 8.48 69850 5560 10:55 AM 2
11-04-09 28 12.56 8.43 71070 5660 1- 5610 I' 11:00AM 2
Hold I I
REMARKS: Jake Stucky (Wildish) was advised of on-site test results.
"1- End Cones 2 - Cone/Split 3 -Columnar 4- Diagonal 5- Side (lOp or bottom) 6-Side (pointed top or bottom)
Reviewed By:
t1~e:r-
Technical Manager
c:
EWEB- Mike Stickling (email)
EWEB- Wally McCullough (email)
OBEC- Pete Slocum (em ail)
Wildish Building Co.- Kevin Fitzjarrell (email)
Wildish Building Co.- Jake Stucky (email)
City of Springfield
Knife River
MLM:sc
This report and/or enclosed lest data is the confidential property of the client to whom it is addressed and pertains to the speCific
process and/or material evaluated. As such, information contained herein shall not be reproduced in part or full and/or any part
thereof be disclosed without FEI Testing,& Inspection, lnc,'s written authorization.
750 rwJ Cornell Avenue. Corvallis, Oregon 97330, phone (541) 757-4698, fax (541) 757-2991
29540 B Airport Road, Eugene, Oregon 97402 . phone (541) 684-3849 . fax (541) 684-3851
62979 NE Plateau Drive, Suite 3 . Bend, Oregon 97701 . phone (541) 3824844 . fax (541) 382-4846
~
6J..."....."'p...'.'..'p.'......'......J.
,.. ."
.....t.. ..
.....;~..
':.;"::..
Page 1 of 1
1I:"'lmfl';.I\'~':';"IIIU..w.l
Geoted1nical & Construc:OOn SeMoes
Daily Field Report
Client:
EWEB
500E. 4th Ave.
Eugene, Oregon
Project: Hayden Bridge Water Filtration
Plant Expansion
Springfield, Oregon
2Y\61 \-\G.L\cUn 6n ~
Oate:
Project No.:
Report No.:
Inspector:
10.No.:
11-03-09
2087168
E-24452
D. Delatte
1080867-88
ICC
Inspection of: Reinforcing Steel
Contractor: Wildish Building
Weather: Clnside- _....,
BP No.: 2008-00225'
Continuous Inspection: 0
Periodic Inspection: 0
Performed preliminary inspection oDJhe. reinforciQg steei for two (2) inter tie tunnel
walls._Reinforcingsteel was checked Jar grade, size;:-Iaps;-quantities,-Iocations, ties,
ciear'ance and .supports~'-"A"JinaUnspection 'will D!l-:performed prior to concrete
--~ ' - . .
To the best of our knowledge, the work inspected was in accordance with plans dated
02/2008 and applicable workmanship provisions of the I.B.C., except if noted above.
Reviewed By:
Ih .. '" fiL -----
Michael ~.;J;r
Technical Manager
c:
EWEB- Mike Stickling (email)
EWEB- Wally McCullough (email)
OBEC- Pete Slocum (email)
Wildish Building Co.- Kevin Fitzjarrell (em ail)
Wildish Building Co.- Jake Stucky (em ail)
City of Springfield
-.
MLM:sc
This report and/or enclosed test data is the confidential property of the client to whom it is addressed and pertains to the speCific
process and/or material evaluated. As such, information contained herein shall not be reproduced in part or full and/or any part
thereof be disclosed without FEI Testing & Inspection. lnc.'s written authorization.
700 rwJ ComeII Avenue' CavaJrIS, Qegoo 97330. phone (541) 757-4698, fax (541) 757-2991
29540 BAirportRoad. Eugene, Qeg0097402. phone (541)684;)849 . fax (541)684-3851 .
62979 NE Plateau Drive, Sutte3' Bend, Oregon 97701. phone (541) 3824844. fax (541) 382-4846
~
~"''''t
~.rt
Page 1 of 1
1'~'IItICl;.I~..'~;'IlII~.IH.
Geotechnical & Construdion Services
Daily Field Report
Client:
EWEB
500E. 4th Ave.
Eugene, Oregon
Project: Hayden Bridge Water Filtration
8Iant'Expansion-, .
, ..0_. ...,
3'151 ~~rB~~
Oate:
Project No.:
Report No.:
Inspector:
10 No.:
11-02-09
2087168
E-24455
A. Fenstermacher
5258882-49
ICC
Inspection of: Reinforced Concrete
Contractor: Wildish Building
Weather: Partly Cloudy .
BP No.: \2008:00225 /
~--
Continuous Inspection: 0
Periodic Inspection: 0
Pe.rformed final inspection on the reinforcing steel for filter building, east half of
suspended slabs above 24" FW IBW pipes and center section of suspended walkway
on west side. A preliminary inspection was performed on 10-30-09 (ref: FEI report E-
24445).
Observed the placement of 18.0 yards of Knife River 4000 psi concrete (mix 40-SE7)
into areas noted above. Concrete was placed by pump and was mechanically
consolidated. Cast one (1) set of four (4) 4" x 8" compressive strength cylinders.
Notified Jake Stucky (Wildish) of the on-site resuits. Slump - 8"; concrete temperature
- 63F; air temperature - 48F; air content - 4.6%.
To the best of our knowledge, the work inspected was in accordance with plans dated
02/2008 and applicable workmanship provisions of the I.B.C., except if noted above.
Reviewed By:
th. ~'Ar---
Michael L. Meyer
Technical Manager
c:
EWEB- Mike Stickling (email)
EWEB- Wally McCullough (email)
OBEC- Pete Slocum (email)
Wildish Building Co.- Kevin Fitzjarrell (email)
Wildish Building Co.- Jake Stucky (email)
City of Springfield
MLM:sc
This report and/or enclosed test data is the confidential property of the client to whom it is addressed and pertains to the specific
process and/or material evaluated. As such, information contained herein shall not be reproduced in part or full and/or any part
thereof be disclosed without FEI Testing & Inspection, Inc.'s written authorization.
700 rwJ CaneIIAvenue' CavalfIS, Oregon 97330, phore(541) 757-4698' fax (541) 757-2991
29540 B Airport Road . Eugene, Qegoo 97402 . phone (541) 684;)849 . fax (541) 684-3851
62979 NE Plateau Drive, Suite 3, Bend, Oregon 97701. phone (541) 3824844 . fax (541)382-4846
----
~
~P..t
.~tt
Page 1 of 1
11:ll'IIIIC'l;<llf"~a.tIIIJ~1IW!I
G:...,U:..,; " .;caJ & Construc:OOn Servire;
Daily Field. Report
Client:
EWEB
500E. 4th Ave.
Eugene, Oregon
Project: Hayden Bridge Water Filtration
Plant Expansion
Springfield, Oregon
oC\5l t-\rotc\en b'f1clgL
Oate:
Project No.:
Report No.:
Inspector:
10 No.:
1 0-30-09
2087168
E-24445
A. Fenstermacher
5258882-49
ICC
Inspection of: Reinforcing Steel
Contractor: Wildish Buiiding
Weather: Overcast
BP No.: r26~8,00225
Continuous Inspection:. 0
Periodic Inspection: 0
~~
Performed. prelimina.ry in_~peclionori the reinforgjD9 -sieeCfor~ building east half
suspended.slaos over 24" FW IBWpipes-anc{ center suspended walkway on the west
side. ',Reinforcingsteel w..asc:.heck,:d'for~grade,..~ize; 'l<3ps;:,qiJ.?[ltiJiesi.~locations, ties,
clearance-and supports. A final Inspection Will be performed pnor to concrete
placement.
To the best of our knowledge, the work inspected was in accordance with plans dated
02/2008 and applicable workmanship provisions of the I.B.C., except if noted above.
Reviewed By:
A.--/.~
Michael L. Me..;lr
Technical Manager
c:
EWEB- Mike Stickling (email)
EWEB- Wally McCullough (em ail)
OBEC- Pete Siocum (em ail)
Wildish Building Co.- Kevin Fitzjarrell (email)
Wildish Building Co.- Jake Stucky (email)
City of Springfield
f{tj) ~~ a 'W ~r)
lrLINOV - 9 2009
. J
L - I
MLM:sc
This report andlor enclosed test data is the confidential property of the client to whom it is addressed and pertains to the specific
process and/or material evaluated. As such, information contained herein shall not be reproduced in part or full andlor any part
thereof be disclosed without FEI Testing & Inspection, Inc.'s written authorization.
700 rwJ Cornell Avenue. CavaJIis, Qegoo 97330, phone'(541) 757-4698, fax (541) 757-2991
29540 BftJrportRoad' Eugene, Qegoo 97402, phone (541) 684;)849 . fax (541) 684-3851
62979 NE Plateau Drive, Suite 3, Bend, Oregon 97701 . phone (541) 3824844 . fax (541)382-4846