PS#2 Elevator Enclosure - 1" Plan Review - Conditions of Approval
PeaceHealth at RiverBend - Sacred Heart Medical Center Project - Parking Garage #2
1141-021-3
COM2007c00509\
'.c- -.. ""-'
Clair Company, Inc. (CLAIR) has completed the plan review for the above referenced Submittal for the
Peace Health at Riverbend, Sacred Heart Medical Center Project, PS #2 Building. This plan review has been
conducted on behalf of the City of Springfield and CLAIR recommends approval with conditions of the
associated documents. .
Attention:
Subject:
Project:
CLAIR Project No.:
Building Permit No.:
CLAIR requests that the permit applicant/designer respond in writing to each comment in the Conditions of
Approval plan review document by adding an applicant response row directly below the CLAIR review
comment field and fill in the indicated fields on the attached EXCEL2000 document along with submitting all
necessary requested submittals.
If you have any questions or need clarifications regarding the ihfonnation we have provided or requested, please
do not hesitate to contact our office at (541) 758-1302 or by email ataclairr7i)claircomoanv.com.
Sincerely,
duff!--
Allan Clair, C.B.O.
Project Manager
Cc:
Al Gerard, City of Springfield Fire Department
Kirk Haskell, PeaceHealth
Bill Shaw, Berry Construction
CLAIR Project File #1141-021.3
Attached:
# I - Codes and Standards
#2 - Submittal Log
#3 - Plan Review Document
if
525 NW Second Street. Corvallis, Oregon 97330
d BOO.383.88S5 ph 541.758.1302 Ix 541.753.2264
www.claircompany.com
July 31,2009
fAf.
-
City of Springfield
Development Services Department
225 Fifth Street
Springfield, OR 97477
i .J /'001 '5" '2. ~to".-n,.r ~ . NdW ~ ~,.
Attention: Dave Puent, Building Official
Subject: PS#2 Elevator Enclosure -1" Back Check - Notes to Inspector
Project: PeaceHealth at RiverBend - Sacred Heart Medical Center Project - Parking Garage #2
CLAIR prOjcct{o' i i~i--v~0>--'- -...
Building Perm; 0.: COM2007-00509'
Clair Company, In. CLAIR) completed the plan review for the above referenced Submittal for the
PeaceHealth at Riverbend, Sacred Heart Medical Center Project, PS #2 Building. This plan review has been
conducted on behalf of the City .of Springfield and CLAIR recommends approval with notes to inspector of the
associated documents.
If you have any questions or need clarifications regarding the information we have provided or requested,please
do not hesitate to contact our office at (541) 758-1302 or by email atacIairrQ)c1aircomoanv.com.
Sincerely,
duff!--
Allan Clair, c.B.O.
Project Manager
Cc:
Al Gerard, City of Springfield Fire Department
Kirk Haskell, PeaceHealth
Bill Shaw, Berry Construction
CLAIR Project File #1141-021-3
Attached:
# I - Codes and Standards
#2. Submittal Log
#3 - Plan Review Document
City of Springfield
Berry Architects
Peace Health at RiverBend
Sacred Heart Medical Center Project
. Parking Garage #2
Elevator Enclosure
Height (feet):
S-2
I-B
8 Tiers
87'~5" max
, -7-0"1
(7~ *"1.. ~H~~. f1~ (1.."" Wolf ~ '
. Occuoanc'f Group'(sl:
Tvoe of Construction:
Stories:
248.774.18 sf
Building Area (Sq. Ft.):
Occupant Load:
1.244 total
167 oer tier
S~rinklers: None - standoioes on Iv
Alarms: none
Fire Wall: 2-hr an. RMP
Please respond in writing to each comment by creating a response row to each item. This plan review document is created in Microsoft EXCELOO. Each city comment is a whole number.
Your response to each item will be a x.1 number. For example, City comment is Item 1.0, your response is Item 1.1. Each of your responses will be shown in bold face type, Indicate
which detail, specification, or calculation shows the requested information. Responses such as "see plans" or "plans comply" or citing a code section does not resolve a review comment
or expedite plan approval. An explanation of how compliance with the code requirement is achieved and a reflection of that explanation in the construction document with the revisions
clouded is our expectation. Your complete and clear response will expedite the re-review and approval of this project or deferred submittal. Thank you for your assistance.
Item #
City Comment From
City
Comment
Date
Construction
Document or
Plan Sheet and
In<:>fA\
City Comment I Applicant Response
Response From
Response
Date
Status of
Item
Elevator Enclosure - Plan Review
CLAIR
7/7/2009
General
Please clarify how ventilation for the new enclosure will be
orovided. 2007 OSSC. Section 1203.1
Please cfarify how egress and exit lighting requirements for the
new enclosure will be provided. 20070SSC, Section 1205.1
Condition ofl
Aooroval
2
CLAIR
7/7/2009
General
Condition of
Aporoval
3
CLAIR
7/7/2009
A1.1
June 23, 09
Enclosing the elevator lobby MAY void the current exception in
NFPA 72 that allows the omission of elevator lobby smoke
detection for elevator recall; this lobby is no longer in an outdoor
area or location that is open to the weather. Please clarify
whether 1. this lobby will be heated and 2. if there are existing
hoistway or elevator room smoke or heat detectors intertied to a
building fire alarm system; if both 1. and 2. are implemented,
please provide an elevator lobby smoke detector for firefighter
recall and connect to the existing fire alarm system. 2007 NFPA
726.16.3.5.
Condition of
Aporoval
10f2
SHMC - Parking Garage #2
Elevator Enclosure
1st Plan Review - Conditions of Approval
July 7,2009
CLAIR: 1141-021-3
~-
~w<
For questions call CLAiR at (800) 383-8855
City of Springfield
Berry Architects
Peace Health at RiverBend
Sacred Heart Medical Center Project
Parking Garage #2
Elevator Enclosure
.'J~
'"""'eco"w"'~~0 .
Occuoancy Grouol!;.}:
TYDe of Construction:
-=C\~l:'lrie5:
Height (feet):
S-2
i-B
8 Tiers
87'-5" 'max
7-J.1-d0l,
1'5*'1- tA-tHr.,~~. /S<f"bewlL-cw",.
248.774.18 sf
Building Area (Sq. Ft.):
Occupant Load:
1.244 total
167 Der tier
Sl?rinklers: None - standoioes only
Alarm!';: none
Fir. Wall: 2-hr @ RMP
Please respond in writing to each comment by creating a response row to each item. This plan review document is created in Microsoft EXCELOO. Each city comment is a whole number.
Your response to each item will be a x.1 number. For example, City comment is Item 1.0, your response is Item 1.1. Each of your responses will be shown in bold face type. Indicate
which detail, specification, or calculation shows the requested information. Responses such as "see plans" or "plans comply" or citing a code section does not resolve a review comment
or expedite plan approval. An explanation of how compliance with the code requirement is achieved and a reflection of that explanation in the construction document with the revisions
clouded is our expectation. Your complete and clear response will expedite the re-review and approval of this project or deferred submittal. Thank you for your assistance.
Item #
City Comment From
City
Comment
Date
Construction
Document or
Plan Sheet and
Irmt.,~\
City Comment I Applicant Response
Response From
Response
Date
Status of
Item
Elevator Enclosure. Plan Review
CLAIR
7/7/2009
General
Please clarify how ventilation for the new enclosure will be
~ovided. 2007 OS_SC. Section 1203.1 _
Enclosure area shall be naturally ventilated by the addition Bill Shaw/Berry 7/16/2009
of two operable sashes into the storefront system per Architects
attached drawing A1.2R (hard copy to be submitted as
Supplemental Information). Sashes shall be approx 7 s.f.
each giving a total ventilation area of approx. 14 s.f., or 4%
of the enclosure area of 348 s.f. The nature of the space is
such that general use thereof is closely connected to
operation of the exterior door, providing de facto
ventilation to the space. The operable sashes will be used
to augment this as deemed necessary. Given the occupant
load and the intended use of the space we believe this to
be adequate.
1.1
lof4
SHMC - Parking Garage #2
Elevator Enclosure
1st Back Check - Notes to Inspector
July 31, 2009
CLAIR: 1141-021-3
For questions call CLAIR at (800) 383-8855