HomeMy WebLinkAboutOccupancy Correspondence 1983-1-31
~
..
s" '" JGFlELD
'vnr OF SPRINGFIELD
Fire Prevention Bureau
Building Division
Janua ry 31, 1933'
" ,
/
.,'''' .
1:/
RE: Occupancy Inspection at 3000 Main Street, Springfield, Oregon
Dear Gary,
.~
,~
Mr. Gary DuBray
136 North 42nd Street
Springfield, Oregon 97477
To satisfy this requirement, the existing ,wood door.and frame shall be re-
placed with a rated door and frame assembly. The pass-through window shall
also be replaced with an approved assembly or closed in with one-hour fire-
resistive construction. The sliding door at the second floor shall also
either be replaced by an approved door and frame assembly or shall be closed
in with one-hour fire-resistive construction.
2) Every portion of a Group H Occupancy having a floor area of 200 square feet
or more shall ,be served by at least two separate exists. S.S.C., Section
3318.
To satisfy this requirement a second exit shall be added in the main shop
space and in the paint spray room. The second exit shall be separated from
the existing exit by a distance equal to not less than one-half of the length
of the maximum overall diagonal dimensiDn of the area to be served measured
in a straight line between exits.
3) The paint spray room shall be provided with an automatic sprinkler system
designed and installed as required by the Uniform Fire CDde. Coordinate
this requirement with Mike Hudman, City Fire Prevention Officer, phone
726-3737.
225 North 5th Street · Springfield, Oregon 97477 · 503/726-3753,503/726-3737
,
e"'..
-~
--
Mr. Gary DuBray
Occupancy Inspection
3000 Main Street
January 31, 1983
Page 2.
4) The paint spray room shall also be provided with an approved mechanical ven-
tilation system as required by Section 45 of the Uniform Fire Code. Coordin- ((
ate this requirement with Mike Hudman. The paint spray room shall not be '.'
used until items 3 & 4 have been complied with. .
5) If any electrical service or equipment changes are required to facilitate
your business, please coordinate these items with the City Electrical In-
spector.
6) The proposed Auto Body Shop use of the existing building is not in confor-
mance with the City Zoning Code. The zone change and special use permits
requests have been made to the City Planning Department,-and are scheduled
for public hearin~ at the Planning Commission meeting of March 2, 1983.
CODrdinate all items relative to allowable land and building use with Greg
Mott of the City Planning Department.
Questions regarding the above items may be directed to me at 726-3669.
, Sincerely,
/j~",.24j- ?
Lorne W. Pl eger
Senior Plans Examiner
~(~
~1i ke Hudman
Fire and Life Safety Plan Review-
cc: Greg Mott
LWP/lh