Loading...
HomeMy WebLinkAboutSpecial Inspection Correspondence 1988-5-31 '. . .~ ~ COMMERCIAL AIR FILTER & AIR CONDITIONING SERVICE. 3155 WEST 5TH - EUGENE. OREGON 97402 - (503) 345-2374 J r/!.a- ..----- May 31, 1988 Mr. Yu Lee 682 Rowan Ave. Springfield, OR 97477 * . , RE: MAKE-UP AIR AND KITCHEN EXHAUST ATt3995 MAIN SrREET. Dear Mr. Lee; Our company has performed an inspection and verification regard- ing the balance between the make-up air and the kitchen exhaust system. The kitchen hood has 57.7 square feet of surface area. It is regarded as a type 1 installation. The CFM requirements are 5800. The primary make- up air unit is a McGraw-Edison with 4420 CFM at .85 S.P. The dishwasher exhaust is 1080 CFM at .5 S.P. The other make-up air, in the electrical service room, is 2160 CFM at .5 S.P. Total exhaust is 6880 (kitchen hood 5800 plus dishwasher 1080). Total make-up air is 6580 CFN. (Kitchen hood 4420 plus electrical room make-up air 2160.) This creates a 4% neg- ative pressure in the kitchen. We conclude that the kitchen exhaust and make-up air systems are properly balanced. Thank you. JR/mmm Enclosures