CITY OF SPRINGFIELD
Fire Prevention Bureau
Building Division
January 18, 1983
Mr. Dan Jenkinson
245 North 23rd Street
Springfield, Oregon 97477
RE: Occupancy Inspection at 3477 Main Street, Springfield, Oregon
*
/
Dear Mr. Jenkinson:
At your request, a joint inspection was performed January 11, 1983 by the City Building
Division and Fire Prevention Bureau to determine the suitability of the existing garage
structure at 3477 Main Street for use as an automotive service and detailing facility.
. .
Since the existing structure was originally a.two:car:residential garage (clas'sified
M-l) and the proposed use is a commercial automotive service and detailing facility
(classified B-1), the structure shall be modified. to meet minimum State Structural
'Specia1ty Code and Fire and Life Safety Code (S.S.C.) standards for the intended use
as fo 11 ows : . .
1) A noncombustible, nonabsorbent floor of concrete or asphalt shall be installed to
replace the existing dirt floor. Section 702 (b), S.S.C.
2) Untreated wood shall not be closer than 6 inches to earth. Section 2517 (c-7) S.S.C.
To meet this requirement it is recommended that the existing structure be jacked-up
and a concrete .curb or stem-wall be installed for the structure to rest on. A pres-
sure treated sill plate shall be secured to the stem-wall with minimum 1:1" ~ x 10"
anchor bolts at maximum spacing of 6 feet, with a minimum of 2 bolts per piece not
greater than 12" from each end. Section 2907 (e) S.S.C. -'
3) A minimum 3 foot wide by 6'8" high man door shall be installed. Section 3302 (a),
S.S.C. The existing overhead doors are not recognized as exit doors by the S.S.C.
4) The east wall of the structure is only about 4 feet from the easterly property line.
Table 5-A, S.S.C. requires that this wall be of one-hour rated .fire-resistive con-
struction. The wall shall be modified to meet this requirement according to the
assemblies recognized in Table 43-B, S.S.C., or the Gypsum Association Fire-Resis-
tive Design Manual.
The City Electrical lnspector, Jim Matteson, has approved the. electrical service con-
nection, and the service request was sent to the Springfield Utility Board. You are
hereby given 60 days from this date to modify the structure as outlined above, or the
City Building Division will order the electrical service disconnected.
During the interium period until items 1-4 above are completed, the structure shall be
used for storage only and no automotive serivce or detailing shall be performed within
the structure.
225 North 5th Street · Springfield. Oregon 97477 · 5031726.3753. 5031726-3737
~
.
.
"-.
Mr. Dan Jenkinson
Occupancy Inspection
3477 Main Street
January 18, 1983
Page 2.
Questions regarding this letter should'be directed to me at 726-3669.