DEVELOPMENT SERVICES DEPARTMENT
225 FIFTH STF1EET
SPRINGFIELD, OR 97477
(541) 726-3753
FAX (54;) 726-3689
January 29, 1996
Rick Martinka
4675 Main Street
Springfield, OR 97478
Subject: Occupancy Inspection at 4675 Main Street, Springfield, Oregon,
*
Proposed Use: Auto Body Repair
Dear Mr, Martinka,
At your request, the Community Services DivisionlBuilding Safety conducted an
inspection of the building at the above address. The purpose of the inspection was to
determine the suitability of the building for the proposed use as indicated,
Based on proposed occupancy, the existing conditions that are mentioned below do not
meet the minimum Building Safety Code requirements. Corrective measures must be
taken prior to occupancy to install, repair, replace or modify the following items in order
for the building to conform to applicable safety codes:
Buildin2
A handrail is required for the interior stairs located by the paint mixing area. Handrails
shall be placed not less than 30" nor more than 38" above the nosings of the stair treads,
The ends of the handrail shall return to a post or walL
The upper storage area,requires installation of a guardrail not less than 42 inches in
height. The open space between the intermediate rails or ornamental pattern of guardrails
shall be constructed so that a sphere 12 inches in diameter cannot pass through.
Electrical
Ground fault circuit interrupter protection (GFCI) is required for receptacle outlets
located in the bathroom and garage area.
Broken or missing cover plates were noted on electrical outlets, switches and/or junction
boxes and shall be replaced.
.
.
.
.
"I."
All electrical wiring shall be maintained in a safe condition. Several loose wiring
connections to the light fixtures on top of the spray booth were noted and shall be
repaired,
,
Paint mixing rooms are Class I hazardous locations and are required to be wired
according to ART.516&500 of the National Electrical Code. All wiring in areas of this
type shall be explosion-proof,
Mechanical
Ducts conveying explosive or flammable vapors or fumes shall terminate not less than
thirty feet from property line, two feet above roof and ten feet above surrounding grade.
Ventilation duct at South side of the building shall terminate above carport roof a
minimum of two feet.
Fir" n""artment
Mechanical ventilation shall be kept in operation at all times while spraying operations
are being conducted and for a sufficient time thereafter to allow vapors from drying
coated articles and finishing material residue to be exhausted. Spraying equipment shall
be interlocked with the ventilation of the spraying and such that the spraying operations
cannot be conducted unless the ventilation system is in operation, UFC 45.206
The intended use of the building falls under an H-4 occupancy which requires an
automatic fue-extinguishing system when the floor area exceeds 3,000 sq, ft, The
building is over 3,000 sq. ft. and a complete sprinkler system is required to be provided
with a one-hour fire resistive separation wall at the building center line between the paint
and welding areas. UFC 1O.507(F)2
Sprinkler valve shall be secured in an open position,
Installation of a pressure gauge on the existing sprinkler riser is required.
Flammable or combustible liquid storage and mixing rooms shall be classified as an H-3
occupancy. All H-3 occupancies shall include an automatic fire extinguishing system,
ventilation, approved electrical fixtures, explosion control and spill and drainage control.
UFC 79.203 UFC 79.805
The above items are requirements for the existing structure only. Other items such as
parking, paving, site improvements, sidewalks, etc" have not been addressed as part of
this inspection and may be required. Please contact the Planning Division of this office
regarding any necessary improvements to the site.
,"'
,
.
.
.
"
All electrical wiring shall be maintained in a safe condition. Several loose wiring
connections to the light fixtures on top of the spray booth were noted and shall be
repaired.
Paint mixing rooms are Class I hazardous locations and are required to be wired
according to ART.516&500 of the National Electrical Code. All wiring in areas of this
type shall be explosion-proof.
Mechanical
Ducts conveying explosive or flammable vapors or fumes shall terminate not less than
thirty feet from property line, two feet above roof and ten feet above surrounding grade.
Ventilation duct at South side of the building shall terminate above carport roof a
minimum of two feet.
fir" n"n~rtment
Mechanical ventilation shall be kept in operation at all times while spraying operations
are being conducted and for a sufficient time thereafter to allow vapors from drying
coated articles and finishing material residue to be exhausted. Spraying equipment shall
be interlocked with the ventilation of the spraying and such that the spraying operations
cannot be conducted unless the ventilation system is in operation. UFC 45,206
The intended use of the building falls under an H-4 occupancy which requires an
automatic fire-extinguishing system when the floor area exceeds 3,000 sq. ft. The
building is over 3,000 sq. ft. and a complete sprinkler system is required to be provided
with a one-hour fue resistive separation wall at the building center line between the paint
and welding areas, UFC 1O.507(F)2
Sprinkler valve shall be secured in an open position.
Installation of a pressure gauge on the existing sprinkler riser is required.
Flammable or combustible liquid storage and mixing rooms shall be classified as an H-3
occupancy. All H-3 occupancies shall include an automatic fue extinguishing system,
ventilation, approved electrical fixtures, explosion control and spill and drainage control.
UFC 79,203 UFC 79.805
The above items are requirements for the existing structure only, Other items such as
parking, paving, site improvements, sidewalks, etc" have not been addressed as part of
this inspection and may be required. Please contact the Planning Division of this office
regarding any necessary improvements to the site.
....
\,
.
.
./
If you need any further information or have any questions regarding the above
requirements, please contact the appropriate inspector noted below between the hours of
8:00-9:00 a.m" 1:00-2:00 p.m., or 4:00-4:30 p.m. at 726-3759.
Sincerely,
o LA/'
..~l;A'1' fl ~ 7-
. Tom Marx
Building Inspector
r;~ 4,"" J)---jjL-k
Ralph Shaw Dave Gadomski
Mechanical Inspector Electrical Inspector
cc: Staff Jennings, owner
Jim Henley, Fire Department
Dave Puent, Community Services Manager/Building Official
SENDER: '-12'[; ~/~75 Afs.:'n 51-:
_Comple1eltems 1 and/or 2 for adclltlonalservlc8s. I also wish to receive the "
"Complete items 3, 4e, end 4b, BUILDING following services (for an
-Print your nama and address on the reverse of this form 80 that we can return this extra fee):
~~~u., ~
-Attach this form 10 the front of the mall~eC8. or on the back if space does not . 1. 0 Addressee's Address ~
pennlt. L.
-Write "Retum R9C8ipt Requestoo" on the mailpiece below the article number. 2. 0 Restricted Delivery ~
-The Return Receipt will show to whom the artide was delivered and the date 'S.
delivered. Consult posbnaster for fee. Cii
u
Izrti:t Imb()5q~7, ~
4b, servi~~e ~
o Registereq,- k(..certified ~
o Express MaUl 0 Insured ~
o Return R~plfor Men:handise 0 coo :
7, oatei h7//iL 1
8, Addr~ss.e;tl Addrass (Only if ,aquastad i!
and IB8 is paid) . ca
(:
...
..
'D
";
..
..
~
l1
e
..
:5
c
o
'0 3, Articla Addressad to:
tl
a.
E
o
u
Ul
Ul
W
0:
C
C
<l
Z
~ 5, Received By: (Print Nama)
Iii
0: /
! 6,s~~d:a~~
PS Form 3811, December 1994
BelL (V\a r-H Vl ~q
'HotS Muin -st,
Spn~dd, OK q1L/-:;<g
Domestic Return Receipt
UNITED STATES POSTAL SERVICE
First-Class Mail
Postage & Fees PaId
USPS
Permit No, G., 0
. Print your name, address, and ZIP Code in this box.
.
fj
--~
P?,%'[if'AW"';;;'~iilJ'!J1Jt'"'!'i1r:tQj1lll.1i}:ijfolL'q/~.?7
. ~~,
DEVELOPMENT SERVICES
225 FIFTH STREET
SPRINGFIELD, OR 974'77
"".
,.
Il
i"
.'
,I
.
"
j~
'.
;i