Compressive Strength of Concrete
(ASTM C 39)
.1~111~ICl;"'h'''' ~~'llli\'.m.
(k,~ , .;caJ & Conslrt.Kfun Services
CLIENT
EWEB
500E. 4th Ave.
Eugene. Oregon 97440
PROJECT
Hayden Bridge Water
Filtration Plant Expansion
Springfield, Oregon
~
DATE L~~~~
PROJECT NO. 2087168
REPORT NO. 6430
B.P. NO.
2008-00225
DATE CAST 05-11-09 CAST BY D, Delatte DATE RECEIVED 05-12-09
STRENGTH REQUIRED 4000 psi SPECIMEN SIZE 4" x8"
STRENGTH PLACED 4000 psi SACKS SUPPLIER Knife Hiver
PRODUCT CODE 2440KIUOKS CEMENT MAX SIZE AGG. 3/4"
ADDITIVES Super; Eclipse; AEA AIR CONTENT 3.6%
LOAD NO. 1 TICKET NO. 3379959 SLUMP 5"
CONCRETE TEMP 6go F YARDAGE 3.0 OF 3.0 TIME 1:35 PM
AIR TEMP 650 F WEATHER Overcast SPECIMEN STORAGE ASTM C31
POUR LOCATION New wall at blue hood patch.
AVERAGE
TEST AGE AREA WEIGHT TOTAL COMPRESSIVE STRENGTH TIME OF TYPE OF
DATE (DAYS) (IN.') (LBS) LOAD (LBS) STRENGTH (PSI! (PSI) TEST FRACTURE-
05-15-09 4 12,56 8.60 49915 3970 9:45 AM 6
05-18-09 7 12.56 8.64 60260 4800 11:05AM 5
06-08-09 28 12.50 8.59 76795 6140 8:20 AM 5
06-08-09 28 12.50 8.59 78250 6260 6200 8:25 AM 6
Hold
U1 _ End Cones 2 - Cone/Split 3 - Columnar 4 - Diagonal 5 - Side (top and bottom) 6 - Side (top or bottom)
REMARKS: Jake Stucky (Wildish) was advised of on-site test results.
Reviewed By:
/JJ,;:.~
Michael L. Meyer
Technical Manager
c:
EWEB- Mike Stickling (email)
EWEB- Wally McCullough (email)
OBEC- Pete Slocum (ema;I)
Wildish Building Co.- Kevin Fitzjarrell (email)
Wildish Building Co.- Jake Stucky (ema;I)
City of Springfield
Knife River
MLM:sc
This report and/or enclosed test data is the confidential property of the client to whom it is addressed and pertains to the specific
process and/or material evaluated. As such, information contained herein shall not be reproduced in part or full and/or any part
thereof be disclosed without FEI Testing & Inspection, lnc,'s written authorization,
700 rfN CcmeI1Avenue' Cavallis, Oegon 97330' phme(541) 757-4698, fax (541) 757-2991
29540 BAirpatRood' Eugene, Oegon 97402' phme(541)684-J849' fax (541) 684-3851
63000 Corporate Place. Suite 2. Bend. Oregon 97701 . phone (541) 382,4844. fax (541) 382-4846
~
'}.'1
~/J-
(J
~.......
~yrtl
RECEIVED
JUN 1 2 ln09
Page 1 of 1
~'mlrt;"U"'~l.llll~.IUt!l
<k..:cJ ,,1iCaI & Construction Services
Daily Field Report
:lient: EWEB Project: Hayden Bridge Water Filtration Date: 06-05-09
500E. 4'h Ave. Plant Expansion Project No.: 2087168
Eugene, Oregon Springfield, Oregon Report No.: E-23107
Inspector: D. Delatte
ID No.: 1080867-88
ICC
lspection of: Reinforced Concrete Weather: Overcast Continuous Inspection: 0
:ontractor: Wildish Building Co, BPNo.: 2008-00225 Periodic Inspection: 0
Performed final inspection on the reinforcing steel for 54" diameter raw water
penetration wall at contact basin north riser box. Preliminary reinforcing steel
inspection was performed on 06-04-09 (reference FEI report E-23092). Advised by
Mike Stickling (EWEB) that he spoke with EOR about the #7 bars noted on preliminary
report. He stated contractor added one (1) #4 bar to each existing #4 bar on each face
from footing to 8' high. Mr. Stickling stated no RFI was generated.
Observed the placement of 5.0 yards of Knife River 4000 psi concrete (mix
2440KIUOKS) in wall noted above. Concrete was placed by pump and was
mechanically consolidated. Cast one (1) set of four (4) 4" x 8" concrete test cylinders.
Slump - 51/2"; air temperature - 67F; concrete temperature - 70F; air content - 3.5%.
Jake Stucky (Wildish) was advised of the on-site test results and was asked to notify
our office when additional services are needed.
To the best of our knowledge, the work inspected was in accordance with plans dated
02/2008 and applicable workmanship provisions of the I.B.C., except if noted above.
viewed By:
~.,/.~
:hael 'L. ~er
:hnical Manager
NEB- Mike Stickling (email)
NEB- Wally McCullough (email)
3EC- Pete Slocum (em ail)
i1dish Building Co.- Kevin Fitzjarrell (em ail)
ildish Building CO.-'Jake Stucky (em ail)
ly of Springfield
\i1:sc
This report and/or enclosed test data is the confidential property of the client to whom it is addressed and' pertains to the specific
process and/or material evaluated. As such, information contained herein shall not be reproduced in part or full and/or any part
thereof be disclosed without FEI Testing & Inspection, Inc.'s written authorization.
700 N>N CaneIIAvenue' Corvallis, 0egl197330' phcoe(541) 757-4600, fax (541) 757-2991
29540 B Airpat Road . Eugene. 0egl197402 . phme (541) 684-3849 . fax (541) 684-3851
62979 NE Plateau Drive. Suite 3 ' Bend, Oregon 97701 . phone (541)382-4844' fax (541) 382-4846
~
~ftJ
Page 1 of 1
1I~'.IILrt;"II~~'~~'ILlli.ltl.
Geotechnical & Construcfun Servires
Daily Field Report
Client: EWEB Project: Hayden Bridge Water Filtration Date: 06-03-09
500E. 4th Ave. Plant Expansion Project No.: 2087168
Eugene. Oregon . Springfield. Oregon Report No.: E-23092
Inspector: D, Delatte
10 No.: 1080867-88
ICC
Inspection of: Reinforcing Steel Weather: Overcast Continuous Inspection: 0
Contractor: Wildish Building Co, BP No.: 2008-00225 Periodic Inspection: 0
Performed prelim inary reinforcing steel inspection for 54" diagonal raw water
penetration wall at contact basin north riser box. Reinforcing steel was checked for
grade, size, lap. placement and clearances, where applicable, #7 vertical rebar spaced
,at 6" on center were not installed as shown in detail D/309. #4 rebar 5" on center was
installed on both sides of pipe penetration in same manner as is noted in detail for wall
above penetration. The additional #7 bars shown were installed on each side of
penetration as shown in detail. EOR to be contacted regarding "as-built" conditions.
Jake Stucky (Wildish) and Mike Stickling (EWEB) were advised of the on-site'
observations and were asked to notify our office when additional services are needed.
To the best of our knowiedge, the work inspected was in accordance with plans dated
02/2008 and applicable workmanship provisions of the I.B.C., except if noted above. .
Reviewed By:
(h .~ IAr----
Michael L. Meyer
Technical Manager
c:
EWEB- Mike Stickiing (email)
EWEB- Wally McCullough (email)
OBEC- Pete Siocum (email)
Wildish Building Co.- Kevin Fitzjarrell (em ail)
Wildish Building Co.- Jake Stucky (email)
City of Springfield
MLM:sc
This report and/or enclosed lest data is the confidential property of the client to whom it is addressed and pertains to the specific
process and/or material evaluated. As such, information contained herein shall not be reproduced in part or full and/or any part
thereof be disclosed without FEI Testing & Inspection, Inc.'s written authorization,
7f:JJ NN CaneII Avenue' CavaJIis, Qegn 97330, ptme(541) 7574698'fax (541)757-2991
29540 BAirpatRoad . Eugene. Qegn 97402, phme(541)(384.;3849. fax (541) 6843851
62979 NE Piateau Drive, Suite 3 'Bend, Oregon 97701' phone (541) 3824844 . fax (541) 382-4846
EWEB
500E. 4th Ave.
Eugene, Oregon 97440
~ftl
.1:"II~lrv;.lr..':':'.IIIJll.IU"
CLIENT
DATE CAST
STRENGTH REQUIRED
STRENGTH PLACED
PRODUCT CODE
ADDITIVES
LOAD NO.
CONCRETE TEMP
AIR TEMP
POUR LOCATION
~
GcvkG: Jlical & Construction Servires
Compressive Strength of Concrete
(ASTM C 39)
PROJECT
DATE
PROJECT NO.
REPORT NO.
05-29-09
2087168
6399 .
Hayden Bridge Water
Filtration Plant Expansion
Springfield. Oregon
B.P. NO.
2008-00225
05-01-09 CAST BY D. Delatte DATE RECEIVED 05-02-09
4000 psi SPECIMEN SIZE 4" x 8"
4000 psi SACKS SUPPLIER Knife River
2440KIUOKS CEMENT MAX SIZE AGG. 3/4"
Super: Eclipse: AEA AIR CONTENT 3.7%
1 TICKET NO. 3354348 SLUMP 7 1/2"
630 F YARDAGE 10.0 OF 10.0 TIME 10:20 AM
590 F WEATHER Clear 'SPECIMEN STORAGE ASTM C31
Back 30" pipe peditration wall, catch basin pit walls, and south ramp west end retaining wall footing.
AVERAGE
TEST AGE AREA WEIGHT TOTAL COMPRESSIVE STRENGTH TIME OF TYPE OF
, 'DATE (DAYS) (IN.') (LBS) LOAD (LBS) STRENGTH (PSIl (PSI) TEST FRACTURE"
05-08-09 7 12.56 8.49 59520 4740 2:15 PM 3
05-29-09 28 12.56 8.59 76070 6060 9:10AM 2
05-29-09 28 12.56 8.57 76250 6070 6065 '9:15AM 4
Hold
"1 - End Cones 2 - Cone/Split 3 - Columnar 4 - Diagonal 5 - Side (top and bottom) 6 - Side (top or bottom)
Reviewed By:
/11,~,~
Michael L. Meyer
Technical Manager
c:
EWEB- Mike Stickling (email)
EWEB- Wally McCullough (email)
OBEC- Pete Slocum (email)
Wildish Building Co.- Kevin Fitzjarrell (email)
Wild ish Building Co.- Jake Stucky (email)
City of Springfield
Knife River
MLM:sc
RECEIVED
JUN 02 lnfl.9
This report andlor enclosed test data is the confidential property of the client to whom it is addressed and pertains to the specific
process and/or material evaluated. As such, information contained herein shall not be reproduced in part or full andfor any part
thereof be disclosed without FEI Testing & Inspection, Inc.'s written authorization,
700 NW CaneD Avenue. Cav.3IIis. Qegon 97330. ~ (541) 757-4698, fax (541) 757-2991
29540 BAirpatRoad . Euglfle, Qegon 97402 . ~(541)684-3849' fax(541)~1
63050 Corporate Place. Suite 2 . Bend, Oregon 97701 . phone (541) 382-4844 . fax (541) 382-4846
EWEB
500E. 4th Ave.
Eugene. Oregon 97440
~......~
~yrtt
111'lUltt;"h,..'~~.nm.I~1.
CLIENT
DATE CAST
STRENGTH REQUIRED
STRENGTH PLACED
PRODUCT CODE
ADDITIVES
LOAD NO.
CONCRETE TEMP
AIR TEMP
POUR LOCATION
~
G<AJ,,"; ,,1ical & Construdion Services
Compressive Strength of Concrete
(ASTM C 39)
PROJECT
DATE
PROJECT NO.
REPORT NO.
Hayden Bridge Water
Filtration Plant Expansion
Springfield, Oregon
05-26-09
2087168
6388
B.P. NO.
2008-00225
04-28-09 CAST BY D. Delatte DATE RECEIVED 04-29-09
4000 psi SPECIMEN SIZE 4" x 8"
4000 psi SACKS SUPPLIER Knife River
40-SE7 CEMENT MAX SIZE AGG. 3/4"
Super; Eclipse, AEA AIR CONTENT 5.6%
1 TICKET NO. 3379738 SLUMP 61/2"
680 F YARDAGE 3.0 OF 3,0 TIME 1:20 PM
650 F WEATHER Overcast SPECIMEN STORAGE ASTM C31
Two (2) walls at 30" pipe penetration across from filter N2, catch basin sump slab at south ramp.
AVERAGE
TEST AGE AREA WEIGHT TOTAL COMPRESSIVE STRENGTH TIME OF TYPE OF
DATE (DAYS) (IN.') (LBS) LOAD (LBS) STRENGTH (PSI) (PSI) TEST FRACTURE~
05-05-09 7 12:56 8,38 46190 3680 8:10AM 3
05-26-09 28 12,56 8.41 65130 5190 9:00 AM 4
05-26-09 28 12.56 8.40 66890 5330 5260 9:05 AM 4
Hold
**1 - End Cones 2 - Cone/Split 3 - Columnar 4 - Diagonal 5 - Side (top and bottom) 6 - Side (top or bottom)
REMARKS: Jake Stuck (Wildish) was advised of on-site test results.
Reviewed By:
/JPI.~
Michael L. Meyer
Technical Manager
c:
EWEB- Mike Stickling (email)
EWEB- Wally McCullough (email)
OBEC- Pete Slocum (email)
Wildish Building Co.- Kevin Fitzjarrell (email)
Wildish Building Co.- Jake Stucky (email)
City of Springfield
Knife River
MLM:sc .
RECEIVED
MAY 2 9 1009
This report and/or enclosed test data is the confidential property of the client to whom it is addressed and pertains to the specific
process andlor material evaluated. As such, information contained'herein shall nol be reproduced in part Of full andler any part
thereof be disclosed without FEr Testing & Inspection, Inc.'s written authorization.
7fIJ WI CaneII Avenue' CavaJIis, Qegoo 97330. phme (541) 757-4698, fax (541) 757-2991
29540 BAiJpatRoad . Eugene. Qegoo 97402, phme(541}684-3849' fax(541}684-3851
63050 Corporate Place. Suite 2 . Bend, Oregon 97701 . phone (541) 382-4844 . fax (541) 382-4846
EWEB
500E. 4th Ave,
Eugene, Oregon 97440
{~FEI
11a.'II~lrt;.li\~'~a'IIIJ~.Ul~
CLIENT
DATE CAST
STRENGTH REQUIRED
STRENGTH PLACED
PRODUCT CODE
ADDITIVES
LOAD NO.
CONCRETE TEMP
AIR TEMP
POUR LOCATION
'<i-
Geotecl1nical & Construction Services
Compressive Strength of Concrete
(ASTM C 39)
PROJECT
Hayden Bridge Water
Filtration Plant Expansion
Springfield, Oregon
DATE
PROJECT NO.
REPORT NO.
05-22-09
2087168
6383
B.P.NO.
2008-00225
04-24-09 CAST BY D. Delatte
4000 psi
4000 psi SACKS
2440K1UOKS CEMENT
AEA, Super. Eclipse
1 TICKET NO. 3379658
65' F YARDAGE 2.0 OF 2.0
62" F WEATHER Inside
Slab on grade at 30" pipe penetration across from filter NZ.
DATE RECEIVED
SPECIMEN SIZE
SUPPLIER
MAX SIZE AGG.
AIR CONTENT
SLUMP
TIME
SPECIMEN STORAGE
04-25-09
4" x8"
Knife River
3/4"
4.2%
41/4"
1:05 PM
ASTM C31
AVERAGE
TEST AGE AREA WEIGHT TOT At COM PRESSIVE STRENGTH TIM E OF TYPE OF
DATE (DAYS) (IN.') (LBS) LOAD (LBS) STRENGTH (PSI) (PSI) TEST FRACTURE-
05-01-09 7 12.56 8.49 50990 I 4060 7:35 AM 4
05-22-09 28 12.56 8.48 65360 I 5200 4:30 PM 3
05-22-09 28 12,56 8.50 67995 I 5410 5305 4:35 PM 4
Hold
"1 - End Cones 2 - Cone/Split ~ - Columnar 4 - Diagonal 5 - Side (top and bottom) 6 - Side (top or bottom)
REMARKS: Jake Stucky (Wildish) was advised of on-site test results.
Reviewed By:
J1J, ';I. /L. ----
Michael L. ~~r
Technical Manager
c:
EWEB- Mike Stickling (emaii)
EWEB- Wally McCullough (email)
OBEC- Pete Slocum (email)
Wildish Building Co.- Kevin Fitzjarrell (email)
Wildish Building Co.- Jake Stucky (email)
City of Springfield
Knife River
MLM:sc
This report andlor enclosed test data is the confidential property of the client to whom it is addressed and pertains to the specific
process and/or material evaluated. As such, information contained herein shall not be reproduced in part or full andlor any part
thereof be disclosed without FEI Testing & Inspection, Inc.'s written authorization,
7fiJ NN CaneII Avenue. CavalTIS, CAa;p1 97330. p/u1e(541) 7574698, fax (541) 757-2991
2954() BAirpcrtRood . Eugene. CX8goo 97402, pha1e (541)684-3849' fax (541) 684-3851
630fiJ Corporate Place. Suite 2 . Bend, Oregon 97701 . phone (541) 382-4844 . fax (541) 3824846
~FE'
JI~"11Irw;"Wr.'n.llIu.~
CLIENT
~
Gc.vW " .:caJ & Calstrucfun Servires
Compressive Strength of Concrete
(ASTM C 39)
PROJECT
DATE
PROJECT NO.
REPORT NO.
05-22-09
2087168
6442
EWEB
500E. 4~ Ave.
Eugene. Oregon 97440
Hayden Bridge Water
Filtration Plant Expansion
Springfield. Oregon
DATE CAST
STRENGTH REQUIRED
STRENGTH PLACED
PRODUCT CODE
ADDITIVES
LOAD NO.
CONCRETE TEMP
AIR TEMP
POUR LOCATION
TEST
DATE
05-22-09
06-12-09
06-12-09
Hold
AGE
(DAYS)
7
28
28
B.P. NO. , 2008-00225
05-15-09 CAST BY D. Delatte
4000 psi
4000 psi SACKS
2440KIUOKS CEMENT
Super; Eclipse;AEA
1 TICKET NO. 3354448
680 F YARDAGE 10.0 OF
590 F WEATHER Clear
Slab on grade. west end of south ramp.
DATE RECEIVED
SPECIMEN SIZE
SUPPLIER
MAX SIZE AGG.
AIR CONTENT
SLUMP
TIME
SPECIMEN STORAGE
10.0
AREA
(IN.'l
12.56
WEIGHT
(LBS)
8.53
COMPRESSIVE
STRENGTH (PSIl
4880
AVERAGE
STRENGTH
(PSI)
TIME OF
TEST
3:30 PM
TOTAL
LOAD (LBSl
61280
".1 - End Cones 2 - Cone/Split
3 - Columnar
4 - Diagonal
5 - Side (top and bottom)
6 - Side (top or bottom)
REMARKS: Jake Stucky (Wildish) and Mike Stickling (EWEB) were advised of on-site test results,
Reviewed By:
A .'1. /l,~, ---
Michael L. ~:y-:;r--
Technical Manager
c:
EWEB- Mike Stickling (email)
EWEB- Wally McCullough (email)
OBEC- Pete Slocum (email)
Wildish Building Co.- Kevin Fitzjarrell (email)
Wildish Building Co.- Jake Stucky (email)
City of Springfield
Knife River
MLM:sc
05-16-09
4" x8"
Knife River
3/4"
4.0%
8"
1 0:25 AM
ASTM C31
TYPE OF
FRACTURE~
4
RECEIVED
MAY 2 8 2009
This report and/or enclosed test data is the confidential property of the client to whom it is addressed and pertains to the specific
process and/or material evaluated. As such, information contained herein shall not be reproduced in part or full and/or any part
thereof be disclosed without FEI Testing & Inspection, Inc.'s written authorization.
7fIJ WI CareIIAvenue' CavaIJis, Oe(pl 97330. phme(541) 757-4698' fax (541) 757-2991
29540 B Airport Road . Eugene, 0e(pl97402 . phme (541) 684-3849 . fax (541) 684-3851
63050 Corporate Place. Surte 2 . Bend, Oregon 97701 'phone (541) 382-4844 ' fax (541) 382-4846
(!If!)
11~'II~ltw:"I~~':l;'IIIJ~twI
CLIENT
DATE CAST
STRENGTH REQUIRED
STRENGTH PLACED
PRODUCT CODE
ADDITIVES
LOAD NO.
CONCRETE TEMP
AIR TEMP
POUR LOCATION
LOAD 1 SAMPLED
\<
TEST. ,c." AGE
';:DATE- .: ,'(DAYS)
I:.:, 04:29-09' I 7
I ' 05~20-69 I 28
I 05-20-09 I 28
I Hold I
RECEIVED
MAY 2 6 2009
~
Gc..,~ , ,;caJ & Cffstrucfun Servires
Compressive Strength of Concrete
(ASTM C 39)
PROJECT
Hayden Bridge Water
Filtration Plant Expansion
Springfield, Oregon
DATE
PROJECT NO.
REPORT NO,
05-20-09
2087168
6372
EWEB
500E. 4th Ave.
Eugene. Oregon 97440
B.I'. NO.
2008-00225
, CAST BY
D. Delatte
DATE RECEIVED
SPECIMEN SIZE
SUPPLIER
MAX SIZE AGG.
AIR CONTENT
SLUMP
TIME
SPECIMEN STORAGE
04-22-09
3000 psi
3000 psi
30-1K
Fiber mesh; AEA
1 TICKET NO. 3353967
70' F YARDAGE 8.0 OF
65' F WEATHER Clear
Elevated slab. north end of coagulant building.
SACKS
CEMENT
15.0
West end of slab.
AREA WEIGHT TOTAL COM PRESSIVE
(IN.') (LBS) LOAD (LBS) STRENGTH (PSI)
12.56 7.88 27405 2180 I
, 12.50 7.86 41640 3330 I
12.50 7.87 42180 3370 I
I
AVERAGE
STRENGTH
(PSI)
TIME OF
TEST
7:55 AM
10:30 AM
10:35 AM
3350
04-23-09
4" x8"
Knife River
3/4"
6.6%
51/2"
8:,15 AM
ASTM C31
TYPE OF
FRACTURE~
5
5
5
**1 - End Cones 2 - Cone/Split
5 - Side (top and bottom)
6 - Side (top or bottom)
3 - Columnar
4 - Diagonal
REMARKS: Jake Stucky (Wildish) was advised of on-site test results,
Reviewed By: '
A, '-i,a,--
Michael L. Meyer
Technical Manager
c:
EWEB- Mike Stickling (email)
EWEB-_Wally McCullough (email)
OB'EC- Pete Slocum (email)~
iWildisti'Building Co.- Kevin Fitzjarrell (email)
Wildish.Building Co,,~~ak~ Stucky (email)
City of,Springfield" '. ,:.',
Knife River
MLM:sc
This report and/or enclosed test data is the confidential property of the client to whom it is addressed and pertains to the specific
process and/or material evaluated. As such, information contained herein shall not be reproduced in part or full and/or any part
thereof be disclosed without FEI Testing & Inspection, Inc.'g written authorization.
7f'IJ NN CaneIIAvenue' CavaIIis, 01J!:p197330' phcre(541) 757-4698, fax (541) 757-2991
29540 BAirpat Road, Eugene, 01J!:p197402' pho1e(541)6!l4.;J849. fax (541 )684-3851
630f'IJ Corporate Place. Suite 2 . Bend. Oregon 97701 . phone (541) 382-4844 . fax (541) 3824846
~......t
...7ft "
RECEIVED
~
11~'II~'lrv;<Vfll~'W~'lllhl.IN.
MAY 2 1 ZUUg Compressive Strength of Concrete
Geotechnical & Construction ServicEs (ASTM C 39)
CLIENT
EWEB
500E.' 4~h Ave.
Eugene. Oregon 97440
PROJECT
Hayden Bridge Water
Filtration Plant Expansion
Springfield, Oregon
DATE
PROJECT NO.
REPORT NO.
05-18-09
2087168
6430
B.P. NO.
2008-00225
DATE CAST 05-11-09 CAST BY D. Delatte DATE RECEIVED 05-12-09
STRENGTH REQUIRED 4000 psi SPECIMEN SIZE 4" x8"
STRENGTH PLACED 4000 psi SACKS SUPPLIER Knife River
PRODUCT CODE 2440KIUOKS CEMENT MAX SIZE AGG. 3/4"
ADDITIVES Super; Eclipse: AEA AIR CONTENT 3.6%
LOAD NO. 1 TICKET NO. 3379959 SLUMP 5"
CONCRETE TEMP 69" F YARDAGE 3.0 OF 3.0 TIME 1:35 PM
AIR TEMP 65" F WEATHER Overcast ' SPECIMEN STORAGE ASTM C31
POUR LOCATION New wall at blue hood patch.
TEST
DATE
05-15-09
05-18-09
06-08-09
06-08-09
Hold
AGE
(DAYS)
4
7
28
28
AREA
(IN.')
12.56
12.56
WEIGHT
(LBS) ,
8.60
8.64
TOTAL'
LOAD (LBS)
49915
60260
COMPRESSIVE
STRENGTH (PSI!
3970
4800
AVERAGE
STRENGTH
(PSI)
, TIME OF
TEST
9:45 AM
11:05AM
TYPE OF
FRACTURE-
6
5
**1 - End Cones
2 - Cone/Split
3 - Columnar
4 - Diagonal
5 - Side (top and bottom)
6 - Side (top or bottom)
REMARKS: Jake Stucky (Wildish) was advised of on-site test results.
Reviewed By:
;11. '7.~
Michael L. Meyer
Technical Manager
c:
EWEB- Mike Stickling (email)
EWEB- Wally McCullough (email)
OBEC- Pete Slocum (email)
Wild ish Building Co.- Kevin Fiizjarrell (email)
WildishBuilding Co., Jake Stucky (email)
City of Springfield
Knife River
MLM:sc
This report and/or enclosed test data is the confidential property of the client to whom it is addressed and pertains to the specific
process and/or material evaluated. As such, information contained herein shall not be reproduced in part or full and/or any part
thereof be disclosed without FEI Testing & Inspection, Inc.'s written authorization.
7'3J MN ComeIIAvenue' Cavallis. CXegon 97330, phone (541 ) 757-4698, fax (541) 757-2991
29540 B I\jrport Road . Eugene. CXegon 97402 . pima (541) 684-J849 . fax (541) 684-3851
63050 Corporate Place, Suite 2 . Bend, Oregon 97701 . phone (541) 382-4844 . fax (541) 382-4846
SFE)
11"'IINCI;.u..'~a.nIJI.mti
CLIENT
'~
Geotechnical & Construction ServiceS
Compressive Strength of Concrete
(ASTM C 39)
PROJECT
DATE
PROJECT NO.
REPORT NO.
05-08-09
2087168
6399
EWEB
500E. 4th Ave.
Eugene, Oregon 97440
Hayden Bridge Water
Filtration Plant Expansion
Springfield, Oregon
DATE CAST
STRENGTH REQUIRED
STRENGTH PLACED.
PRODUCT CODE
ADDITIVES
LOAD NO.
CONCRETE TEMP
AIR TEMP
POUR LOCATION
TEST
DATE
05-08-09
05-29-09
05-29-09
Hold
AGE
(DAYSl
7
28
28
**1 - End Cones
Reviewed By:
11. 'i.!fu..t
Michaell. ~eye(
Technical 'Manager
B.P.NO.
2008-00225
05-01-09 CAST BY D. Delatte DATE RECEIVED 05-02-09
4000 psi SPECIMEN SIZE 4" x 8"
4000 psi SACKS SUPPLIER Knife River
2440KIUOKS CEMENT MAX SIZE AGG. 3/4"
Super: Eclipse; AEA AIR CONTENT 3.7%
1 TICKET NO. 3354348 SLUMP 7 1/2"
630 F YARDAGE 10.0 OF 10.0 TIME 10:20 AM
590 F . WEATHER Clear SPECIMEN STORAGE ASTM C31
Back 30" pipe peditration wall, catch basin' pit walls, and south ramp west end retaining wall footing.
AREA
(IN.')
12.56
TOTAL
LOAD (LBSI
59520
COMPRESSIVE'
STRENGTH (PSI)
4740
AVERAGE
STRENGTH
(PSn
TIME OF
TEST
2:15 PM
TYPE OF
FRACTURE..
3
WEIGHT
(LBSl
8.49
I
2 - Cone/Split
4 - Diagonal
5 - Side (top and bottom)
6 - Side (top or bottom)
3 - Columnar
c:
EWEB- Mike Stickling (email)
EWEB- Wally McCullough (email)
OBEC- Pete Slocum (email),
Wildish Building Co.- Ke\lin:Fitzjarrell (email)
Wildish Building Co.- Jake Stucky (email)
Cily of Springfield
Knife River
..
MLM:sc
RE.CS\\lE\.
t<W 1 3 2009
This report and/or enclosed test data isJhe,confidential property of the client to whom it is addressed and pertains to the specific
process and/or material evaluated. Assoch, information contained herein shall not be reproduced in part or full and/or any part
thereof be disclosed'without FE! Testing & Inspection, Inc.'s written authorization,
7fIJ t#V ComeII Avenue' CavaIIis, Oreg:n 97330, phone (541) 757-4698. fax (541) 757-2991
29540 BAirport Road, Eugene, Oreg:n 97402' phone (541)684J849 . fax (541)684-3851
630fIJ Corporate Place, Suile 2 . Bend. Oregon 97701 . phone (541) 382-4844 . fax (541) 382-4846