Subject: .occupancy Inspection at 6025 Main Sl., Springfield, OR
*
Proposed Use: Child Development Center
Dear Ms. Lillie,
At your request, the Community Services Division/Building Safety conducted an
, inspection of the building at the above address. The purpose of the inspection was to
determine the suitability of the building for the proposed use as indicated.
Based on the proposed occupancy, the existing conditions which are mentioned below
do not meet the minimum Building Safety Code requirements. Corrective measures
must be taken prior to occupancy to install, replace or modify the following items in
order for the building to conform to applicable safety codes:
I. Please submit a floor plan of the building showing the dimensions and the intended
use of each room. From this floor plan we will be able to determine occupant load and
exiting requirements.
2. All circuit breakers in the electrical panel shall be properly labeled.
3. The neutral wire and the grounding wire in the subpanel are bonded to the same bar.
The neutral wire is required to be isolated from the grounding wire.
4. The service equiptment has too many service disconnects. The service equiptment
shall be repaired or replaced to provide not more than six disconnects for all electrical
power to the building.
5. Toilets in public restrooms shall be provided with open front toilet seats.
6. Smoke detectors shall be installed in all sleeping and/or napping areas; one in
downstairs hallway and one upstairs.
7. One 2AIOBC, 5# multipurpose extinguisher shall be installed on the kitchen wall.
8. If radiant wall heaters are to be used they must be provided with ~afety guards to
protect young children from bums.
The above items are requirements for the existing structure only. Other items such as
parking, paving, site improvements, sidewalks, etc., have not been addressed as part of
this inspection, and may be required as part of Development Review. Please contact
the Planning Division at 726-3759.
,.
..
.
"
.
If you need any further information or have any questions regarding the above
requirements, please contact the appropriate inspector noted below between the hours
of 8:00-9:00 a.m. or 4:00-4:30 p.m. at 726-3759.
.'