HomeMy WebLinkAboutComments FLS 9/19/2006 Page 1 of l' ;, L1MBIRD Andrew From: GORDON Gilbert Sent: Tuesday, September 19, 2006 9:05 AM To: L1MBIRD Andrew Cc: GERARD Alan; FECHTEL Melissa Subject: Site Plan Tentative DRC2006-00062 Embassy Suites, Site Plan Tentative DRC2006-00062 Embassy Suites Address: 3530 Gateway Street Existing Use: Vacant Proposal: Construct an eight story, ~61 room Embassy Suites Hotel Planner: Andy Limbird " ;, ,J , ,Fire Department Comments: Access: A joint use access agreement shall be required with the neighboring property owner to the west for fire access to the west side of the proposed hotel (2004 Springfield Fire Code 503.1,1). Fire apparatus access roads shall support an 80,000 lb. imposed load per 2004 Springfield Fire Code 503.2,3 arid SFCAppendix D1 02, 1. , Water Supply: Another joint use agreement shall-be required for the use of the private hydrant located on the west side of the proposed hotel. If this is not workable, another hydrant shall be , required near the south side of the proposed hotel meeting spacing requirements of 2004 Springfield Fire Code Appendix C, Table 105,1, The location of the fire department connection is not acceptable. The fire department connection shall be located on the aboveground vault facing away from the building or located on the Springfield Utility Board Water Department approved aboveground vault Refer to comments by Bart McKee, SUB Water Department Senior Engineer. ' Gilbert R Gordon Deputy Fire Marshal Springfield Fire and Life Safety 225 Fifth Street Springfield, Oregon 97477 541 ~ 726-2293 ' g.Qordonlaici, soringfield ,or. us '" Date Received' r/~tJt Planner: Al 9/19/2006