HomeMy WebLinkAboutComments FLS 9/19/2006
Page 1 of l'
;,
L1MBIRD Andrew
From: GORDON Gilbert
Sent: Tuesday, September 19, 2006 9:05 AM
To: L1MBIRD Andrew
Cc: GERARD Alan; FECHTEL Melissa
Subject: Site Plan Tentative DRC2006-00062 Embassy Suites,
Site Plan Tentative DRC2006-00062 Embassy Suites
Address: 3530 Gateway Street
Existing Use: Vacant
Proposal: Construct an eight story, ~61 room Embassy Suites Hotel
Planner: Andy Limbird
"
;,
,J
,
,Fire Department Comments:
Access: A joint use access agreement shall be required with the neighboring property owner to
the west for fire access to the west side of the proposed hotel (2004 Springfield Fire Code
503.1,1).
Fire apparatus access roads shall support an 80,000 lb. imposed load per 2004 Springfield
Fire Code 503.2,3 arid SFCAppendix D1 02, 1.
, Water Supply: Another joint use agreement shall-be required for the use of the private hydrant
located on the west side of the proposed hotel. If this is not workable, another hydrant shall be
, required near the south side of the proposed hotel meeting spacing requirements of 2004
Springfield Fire Code Appendix C, Table 105,1,
The location of the fire department connection is not acceptable. The fire department
connection shall be located on the aboveground vault facing away from the building or located
on the Springfield Utility Board Water Department approved aboveground vault Refer to
comments by Bart McKee, SUB Water Department Senior Engineer. '
Gilbert R Gordon
Deputy Fire Marshal
Springfield Fire and Life Safety
225 Fifth Street
Springfield, Oregon 97477
541 ~ 726-2293 '
g.Qordonlaici, soringfield ,or. us
'"
Date Received' r/~tJt
Planner: Al