To Design Team,
1. Please provide required roof structure design for dumpster enclosure with sanitary floor '
drain (plan sheet A 110). 1101.2 OPSC
2. Tee pipe fittings are not'approved as horizontal branch fittings, wyes are required (plan
sheet C4 note 220). 715.20PSC
3. 3034 PVC piping is not approved under and within 2 feet of buildings, including covered
dumpster enclosures (plan sheet C4 note 279). 313.4 OPSC
4. The dumpster enclosure sanitary floor drain requires a trap, vent, c1eanout, and
automatic means of maintaining trap seai (plan sheet C4 note 230). 719,1002,.1007
OPSC
5. 3034 PVC piping is not approved under and within 2 feet of buildings (plan sheet C5 note
478). 313.4 OPSC
6. Missing note detail for 8 inch storm piping labeled note 479 (plan sheet C5).