Loading...
HomeMy WebLinkAboutPermit Correction Notice 1981-1-27 rITY Cf SPRLNGFIEI,lJ E LEe T R Ie'" INS PEe T' ION R E PlJR T 8qso .~_j , ~OfWlo- OWNER/RENTER: Oregon Industrial Lbr Prod. IncADDRESS: ADDRESS OF INSPECTION: Same 'Marcola & Hayden Bridge Rd. Spfld Semi TYPE OF REQUEST: Annual Electrical TYPE OF STRUCTURE: Remanufacturing Mill USE::' same HEIGHT nATE~ 1-27-81 ,/ 1. Remove picture over lighting panel. 2. Install ground type receptacle in area of heater in south wall. 3. Remove extension cord wiring in shipping office. ~ ~ 4. Reverse Polarity in shipping office receptacle"(recommend installing receptacle near center of bench). 5. Repair defective flex into newman planer motor. 6. Flex to be secured to double end trim motor," 7 . Reverse' pol arityin receptacle above. starter' fornEiWmanpl aner. 8. Pin-up (clamp-type) lights, to have3condii(;torcords (ground required). 9.' Remove cordwir'ing to newman planer. 10. It is required that the area in front of control centers, disconnects, panels and relay centers be dept clear at all times, and a passage way to this area must be provided. 11. Repair cord into side'head grinder'motor. 12. Remove cord hung light over newman planer. Install metallic raceway. 13.' Repair defective conduit into control station to hula saw. 14. Replace cover on motor below hula saw station. '15. Seal open K.O.'s, secure cover and secure receptacle in junction box below #1 molder. 16. Seal open K.O.'s in control center by #1 molder. 17. Repair defective flex into motor on #3 molder. 18. Strap conduit to floor by #3 molder. (1){) MrW Co l Cf- , INSPECTOR: ACCCl'1PAN I ED BY: APPROVED BY: l\ \""~",,"_,,,..~.'.. .~_.:_.~_ '''b--''_'~';'''.J''::.,''''~_';'.~~ ',."....4. CITY OF SPRINGFIELD ELECTRIC. INSP'ECT'ION REI4tRT CWNERlRENTER: ADDRESS OF INSPECTION: lYPE OF SlRUCTURE: .ADDRESS : USE: lYPE OF REQUEST: HEIGHT PATE: WIRING METHOD: NON-METALLIC SHEATHED CABLE - ARMORED CABLE CONDUIT POtIER co: G!.~NGES ORDERETI: 19. Secure flex' connector into motor on #3 moldertr'irri saw. 20. Secure conduit and relay to #3 molder 'trim saw.' ,. , 21. Seal open K.O.'s in relays to #2 molder trim saw. 22. Repair defective flex into jointer. 23. Repair defective cord connector into radial saw. 24. Reverse polarity in receptacle in compressor room. 25. Bond control center by woods planer and seal open K.O.'s. 26. Remove cord through open K.O. in lighting panel to molder area and seal all open K.O. 'so 27. Repair defective flex to hula saw by woods planer. 28. Install 3 conductor cord to portable heater innboiier room. 29. Remove cordwldng to sump pump in b6ilerroom. Install conduit to a receptacle adjacent to pump. 30. Properly bond light fixtures over bench.' 31. Install servi ce ground 'conductor from pane 1 inSuperi ntendents ciffi ce to fuel bi n frame worJ 32. Install receptacle adjacent to candy dispensers in lunch room. 33. Install 3 conductor cords to all dispensers and refrigerator in lunch room. 34. Install light outlet in Helen's office. 35. Seal open box above cabinet in dry kiln control #1. 36. Install receptacle adjacent to l100re pressure controller (by dooe). 37. Repair defective flex into #3 and #4 dry kiln motor (fan motor). 38. Repair defective flex to motor for #5 and #6 dry kiln fans. INSPECTOR: ACCQ"1PAN I ED BY: APPROVED BY: ~I1Y OF SPRINGFIB,.D E LEe T R I C AlP INS PEe T ION R E .R T OfINERlRENTER: ADDRESS OF INSPECTION: lYPE OF STRUCTURE: ADDRESS: I lYPE OF REQUEST: I USE: HEIGHT PATE~ WIRING METHOD: NON-METALLIC SHEATIiED CABLE -- ARMORED CABLE CONDUIT POWER CO: OWjGES ORDERED: 39. Reverse polarity in receptacle in receptacle in control room to #5 and #6 kilns. 40. Reverse polarity in receptacle in bog resaw control center. 41. Repair defective flex into M.G. set by big resaw. 42. Relocate or protect damage conduits by chipper motor. 43. Repalce missing cover on LB condulet by wood 'belt motor. INSPECTOR: 'Chas. C. Watson ACCCMPANIED BY: La rry McCa 11 um APPROVED BY: " '.