HomeMy WebLinkAboutPermit Correspondence 1990-1-26 ;- '. ~ . ~.- -. -iliiL....:.'~ J~_ ~..A. II Luaa...:y~~ ' ~--::4' Schaudt, Stemm & Wild, Inc. CONSULTING ENGINEERS, SURVEYORS AND PLANNERS 388 High Street 503/485.8383 Eugene, Oregon 97401 January 26, 1990 Job No. 90-3546 Larry Jackson Mid-Wi11amette Acoustics 1646 Bradly Drive Eugene, Oregon 97401 * Re: Inspection and Certification of Lateral Force Bracing for Suspended Ceiling System, Albertson's in Springfield, Oregon. Per your instructions, I have inspected the ceiling construction at the Albertson's Store in Springfield. Elva Duvall, the project superintendent, and I removed ceiling tiles to inspect the details of the ceiling suspension system and bracing. The ceiling suspension system is the USG/Donn DXL system which you provided me the printed technical specifications for my calculations. The lateral force bracing system of wires and struts are spaced 12 feet on center each way per specifications. The typical vertical support wire system is spaced 4 feet on center along the main support tees per specifications. Tom Marks, the Springfield building inspector, indicated that the four wires at each strut location were not sloped at an angle of 450 from the plane of the ceiling as required by the specifications, therefore the system is unacceptable. The specifications permit substantiating design calculations to support alternatives. I have investigated the UBC Design requirements under seismic forces and lateral force design. Actual ceiling and fixture weight approximates 2 psf, the seismic code requires a minimum 4 psf for design. Actual horizontal force per strut section was computed at 86.4 pounds using the 4 psf minimum. UBC design requirements also require a minimum design of 200 pounds for each bracing wire. Calculated values using code minimums are 122# at 450, 170# at 600 and 203# at 650 the approximate worst case in the ceiling layout. ~ooD V'V\J\,Y" CO I Ci'- . . Page 2 Larry Jackson/Mid-Willamette Acoustics Re: Inspection and Certification of Lateral Force Bracing for Suspended Ceiling System, Albertson's in Springfield, Oregon. January 26, 1990 Based upon the design of the roof framing system by others of trusjoist members spaced 4 feet on center between glulam girders, the variable height between roof surface and ceiling line, the attachments are extended to the joist lines as constructed. There is no Code system that is permitted to install an additional support framing system at the roof line permitting the 450 alignment of the suspension wires. Based upon the details as constructed, calculations to check actual and Code minimum loads and forces, values permitted by the manufacturer's suspension system, I certify that the lateral force bracing system in place will support and resist all lateral force requirements of the 1990 edition of the State of Oregon Specialty Code. Respectfully submitted, SCHAUDT, STEMM & WILD, INC. EHS/sar C: R.A. Chambers & Assoc. ~ ALB~~IlJC;; .HEET NO, / ,.,~ / UG SLJ,..",_,."..L.,-/Jt€ ./1:),-. PROJECT NO, ~ -3'~ , q~ #/0 -11?/t:.L..A~1F .,-,..~ ~pd.G77'C'S,ATE ~;/.pAY -~ //1t1esl-r~;'~~. ~ez-?4;~ /7i1rce er",c/";/i c:J..,& ~J,;~- d!!H~,d; Ca'//-,~ /n~ 5q'~~~. /t~e-'/Ltt<:.. t-l t1~/.,,, .~ - ~ - IPHUI F/~.a:.. ! ,C:1'~ toM / / a-H..-::l.. '\. - -,- ;ed. re"ne~~ i ~ ,.,e;( Ck,4Mb~,~ c;~~~ ~ ~6:h?/ ,4rc~ ~ ~rth'e~ 4"~ ~ f;f/ p/~ tfC t2!.,; ~ /z. f-"tt) "'% e~a/-(...I t~.I"[/, (fY.c. ~('!,- :;:#,u) . ;t!&r"Ntd tY~dt'~.c ,'- , ~/I'&1P';t- /2'~a. ~~,J,S , .. .$;:t'ced.- 4' J!.. t'k, I' ! (~/c:. ~e'" C~'d."G) 1 /(/II~~ ~ ::J(/j"/"I.'rzf' /tJ~ # I I I -r-==:-"" ,:."..~: ''''~=' '"=~c- ~'=',: = I' -- -_. - --- .- . - --1- -',-' I -, I, I -'. -.-- i , .,-- 'I . - -,-I '''-'-1 ~-.-i ,~-I _I . - - .' 1 . 4f ""J', . ---'f :.~ . '--..: ! '2/.,o.t' 0./ -1 '-.. "...-- :;..rc::::. --, '! Tel? -!f"~ ~oZ.,<z-.o/,.'r?,=- -!:5Z .# ; , r:5~ /~O/?% =- 3~ /.k,~~~ .r=brce (s'/'Sfl?/G) V'/.3c: 23/f(9J Z. r:;a:s::. (), ~ (7 x. /. If) J<. &'. 75" >< 57&. -fill: .P~ a- C _ /. e, I'" #..,t::- =- $~.~A'-~ e~~, M/J~. ~ ,t:J.~,_"- 6ni:. . r~5"t?/'; e- /,,"/H.,t-,., &.p,- -. '2". ~..:.,c.. , , k/t. =- j?,e; )C.. I':z:. 0 - pee; &_51'9'#"'- ".-er:e"'I'"It'! - - ':iZ86' ~ ",en~t5 <:!J 2t::>O #- "wIn' F?<~ !!!Jx.20 "" ~o -r;,.. P"'-I?ori.., U/I.re-I!S H/~-tV 7:i,/t/ ~a..?~.!J~ ..=d:J.7S ;r:-; 5' ,K. Z- ,-: ~ u __ .;' tp .A ..L.. . , '---"'ft'~ t'I . 0"- _, or ~$r- /1?4>C/H-fUP? ~rcc.; 4te-~,'!nL'~d -:z -;~. /;v t?"''''C/~'' a--I;-e' 6 ~-C- ~ - /?~ '" ~ /,,S,c ~.5"1'6 IZZ.~ - G7c;.A ~~~., /5 /70'" -..-. .,_A' _/... I . g .# ,Y;t?/c~ ~!!i'1"YP.e.Wt:l~ tt:' ~ ~ S6-; c:e. ~S"' /~ ZiP ~""';'7 O'<L. ~'~4.r~ A// ~,..tU-~~ Cd-"','1e.~~ i/a,t!eUO-4 '7 Za:;J..JiII': e",::IPt:'l(.,. CONSULTING ENGINEERS. SURVEYORS AND PLANNE~S 388 HIGH STREET EUGENE, OREGON 97401 Schaudt, Stemm & Wild, Inc.