CLIENT
DATE CAST
STRENGTH REQUIRED
STRENGTH PLACED
PRODUCT CODE
ADDITIVES
LOAD NO,
CONCRETE TEMP
AIR TEMP
POUR LOCATION
LOAD 3 SAMPLED
TEST
DATE
03-19-09
04-09-09
04-09-09
Hold
AGE
(DAYSl
7.
28
28
**1 - End Cones
GcvW " ,m & ConstrucOOn SeIvices
Compressive Strength ,of Concrete
(ASTM C 39) .
PROJECT
LCAFRC-BLM
Warehouse Addition
3110 Pierce Parkway
S~ringfieJd, Oregon
COM2009-00215
DATE'
PROJECT NO,
REPORT NO,
03-19-09
2097030
6267
B,P,NO:
03-12-09 CAST BY D, Delatte DATE RECEIVED 03-13.09
3000 psi SPECIMEN SIZE 4" x 8"
4000 psi SACKS SUPPLIER Knife River
40-1 K CEMENT MAX SIZE AGG, 3/4"
Hot water; AEA AIR CONTENT 6,0%
3 TICKET NO, 3354221 SLUMP 4 1/2"
68" F YARDAGE 10,75 OF 196,0 TIME 8:10 AM
36" F WEATHER Clear SPECIMEN STORAGE ASTM C31
Slab on grade with thickened areas within lines A to G, from 1 to 4 and sma!1 column near A 1,
Set 1
Near 3B,2
AREA
(IN,')
12,56
WEIGHT
(LBSl
8,27
TOTAL
LOAD (LBSl
53780
COMPRESStVE
STRENGTH (PSIl
4280
AVERAGE
STRENGTH
(PSIl
TIME OF
TEST
5:30 PM
TYPE OF
FRACTURE"
5
2 - Cone/Split
3 - Columnar
4 - Diagonal
5 - Side (top and bottom)
6 - Side (top 0' bottom)
REMARKS: Tony Dean (Wildish) was advised of on-site test results,
Reviewed By:
;J;, -;f~----
Michael L.vMe{),-
Technical Manager
c:
Barrantine Bates Lee - (e-mail)
kpff Consulting Engineers- (e-mail)
Oregon Military Dep!. - (e-mail)
Wild ish- Tony Dean (email)
City of Springfield
MLM:sc
This report and/or enclosed test data is the confidential property of the client to whom it is addressed and pertains to the specific
process and/or material evaluated. As such, information Contained herein shall not be reproduced in part or full and/or any part
thereof be disclosed without FEI Testing & Inspection, Inc.'s written. authorization.
750 WI C6meiJAvenue' Corvallis, Qegon 97330, phcne (541) 757-4698, fax (541) 757-2991
29540 B Airport Road ' Eugene, Qegon 97402 ' phone (541) 684--3849 ,fax (541) 684-;3851
63050 Corporate Place, Suite 2 ' Bend, Oregon 97701 'phone (541) 382,4844 , fax (541) 382-4846
Me. Jim Thomas
Wildish Building Co,
PO Box 7428
Eugene, Oregon 97401
{+)FEI
II~lrWf'l,"'I"':E:IIIJlr.m.
CLIENT
DATE CAST
STRENGTH REQUIRED
STRENGTH PLACED
PRODUCT CODE
ADDITIVES
LOAD NO,
CONCRETE TEMP
AIR TEMP
POUR LOCATION
LOAD 11 SAMPLED
TEST
DATE
03" 19-09
04-09-09
04-09-09
Hold
AGE
(DAYS)
7
28
28
**1 - End Cones
GoukG: dlical & Coostrudion Servires
Compressive Strength of Concrete
(ASTM C 39) .
PROJECT
LCAFRC-BLM
Warehouse Addition
3110 Pierce Parkway
Springfieid, Oregon
COM2009-00215
DATE
PROJECT NO,
REPORT NO,
03-19-09
2097030
6268
B,P,NO"
03-12'09 CAST BY 0, Delatte DATE RECEIVED 03-13-09
3000 psi SPECIMEN SIZE 4" x 8"
4000 psi SACKS SUPPLIER Knife River
40-1K CEMENT MAX SIZE AGG, 3/4"
,Hot water; AEA AIR CONTENT 5.4%
11 TICKET NO" 3354229 SLUMP 5"
67' F YARDAGE 10,75 OF 196,0 TIME 9:50 AM
40' F WEATHER Clear SPECIMEN STORAGE ASTM C31
Slab on grade with thickened areas within lines A to G, from 1 to 4 and small column near A1,
Set 2
Near 0-2
AREA
(IN.'!
12,56
WEtGHT
(LBS)
8,24
COMPRESSIVE
STRENGTH (PSI)
3910
AVERAGE
STRENGTH
(PSI)
TIME OF
TEST
5:35PM
TYPE OF
FRACTURE~
6
TOTAL
LOAD (LBSl
49170
2. - Cone/Split
3 - Columnar
4 - Diagonal
5 - Side (top and bottom)
6 - Side (top or bottom)
REMARKS: Tony Dean (Wildish) was advised of on-site test results,.
Reviewed By:
/1, Y-~
Michael L. Mt/er .'
Technical Manager
c:
Barrantine Bates Lee - (e-mail)
kpff Consulting Engineers - (e-mail)
Oregon Military Dept. - (e-mail)
Wildish- Tony Dean (email)
City of Springfield
MLM:sc
This.report and/or enclosed test data is. the confidential property of the client to whom it is addressed and pertains to the specific
process and/or material evaluated. As such, information contained herein shall not be reproduced in part or full and/or any part
thereof-be disclosed without FEI Testing & Inspection, Inc.'s written authorization.
7ffJ NN ComeII Avenue' CoMlilis, ()egJn 97330, phone (541) 757-4698' fax (541) 757-2991
29540 BAirport Road, Eugene, ()egJn 97402, ptme(541)684-J849' fax (541) 684-3851
63050 CorporatePlace, Suite 2 ' Bend, Oregon 97701 ' phone (541) 382-4844 ' fax (541) 382-4846
~. ....~
~tt~
Page 1 of 1 :
Gcu;~ " .;...,.) & Construclion SeIvices
Daily Field Report.
'J~'IlNW;41lt~':tUIIII~.lalfl
Client:
. Project:
,
LCAFRC-BLM
Warehouse Addition
3110 Pierce Parkway
Springfield, Oregon
Date:
Project No,:
Report No,: '
Inspector:
IDNo,:
Mr. Jim Thomas
Wildish Building Co,
PO Box 7428
Eugene, Oregon 97401
03-19-09
2097030
E-22587
D, Delatte
1080867-88
ICC
Inspection of: Epoxy Anchors
Contractor: Wildish Building Co,
Weather: Overcast
BP.No,: COM2009-00215
Continuous Inspection: 0
Periodic Inspection: 0
Observed the installation '~f seventy-two' (72) 3/4" x 10 1/2" and four (4) 1" x 10 1/2"
epoxy all thread anchors with four (4) anchors per location as follows: 3/4" anchors- at
lines 3,3B, 4A, 3,3A, lA,,1.2EA, 1C, 2C, 3C, 3,7C,1, C4, B4, X1E, X1F, X1G, 1,1G,
. 1,9G,,2E, 3E; 1" anchors" 3D and 2D, Prior to installation, the predrilled holes were
cleaned with. a brush and compressed air. Verified minimum embed 'depth of 8",
Anchors were secured with Hilti RE-500 (expiration date 12/2009),
Tony Dean (Wildish) was advised of our on-site observations and was asked to notify
our office when additional services are needed,
To the best of our knowledge; the work inspected was in accordance with plans dated
02:12-09 and applicable workmanship provisions of the I.B,C" except if noted above,
Reviewed By:
'tfJ;,~.~
Michael L Meyer
Technical Manager
c:
Barranline Bales Lee - (e-mail)
kpff Consulting Engineers - (e-mail)
Oregon Military Dept. --: (e-mail)
Wildish- Tony Dean (email)
City of Springfield
MLM:sc
This report andfor enclosed test data is the confidential property of the client to whom it is addressed and pertains to the specific
process and/or material evaluated. As such, information contained herein shall notbe reproduced in part Of full and/or any part
thereof be disclosed without FEI Testing & Inspection, Inco's mi.tten authorization.
7fJJ WI CanelIAvenue' CavaDis, Qegln 97330, phone (541) 757-4698, fax (541) 757-2991
29540 BAiI]lOl1Road' Eugene, Qegln97402' phone (541) 684-3849 '1ax(541)684-J851
63050 Corporate Place, Suite 2 ' Bend, Oregon 97701 'phone (541) 382-4844 ' fax (541) 382--4846
~.......
~yr-!:1
11:.'mlrt;"I~~':;;lllllt_
I,
Geotechnical & ConstrucOCJn Servires
Daily Field Report
Client:
Project: LCAFRC- BLM
Warehouse'Addition
3110 Pierce Parkway
Springfield, Oregon
Date:
Project No,:
Report No,:
Inspector:
10 No,:
Mr, Jim Thomas
Wildish Building Co,
PO Box 7428
Eugene, Oregon 97401
Page 1 of 1
03-12-09
2097030
E-22545
D, Delatte
1080867-88
ICC
Inspection of: Reinforced Concrete
Contractor: Wildish Building Co,
Weather: Clear
'BP No,: COM2009-00215
Continuous Inspection: 0
Periodic Inspection: It'!
Performed final inspection,on reinforcing steel for, slab on ,9rade with thickened areas
within liries A to G, from 1'to 4 and,small column near A1.. Preliminary reinforcing steel,
inspection was performed on 03-11-09 (FEI rep?rt number E-22538),
Observed the placement of 196 yards of Knife River 4000 psi concrete (3000 psi
required) (mix 40-1 K) for areas noted above, Concrete was placed' by pump and
mechanically consolidated, Cast two (2) sets of four (4) 4" x 8" Goncrete test cylinders,
The on'site test results areas follows: ' '
I Set 1- Load 3
I Concrete temperature- 68F
I Air temperature- 36F
I Slump- 41/2"
I Air content- 6,0%
Set 2- Load 11
Concrete temperature- 67F
Air temperature- 40F
Slump- 5"
Air content- 5,4%
Also, observed the installation of ten (10) #5 dowels, three (3) horizontal on each side
of new north elevator pit wall with four (4) vertical dowels into elevator pit slab and six
(6) #4 horizontal hook dowels into slab for new south elevator pit wall. Prior to
installation, ihe predrilledholes were cleaned with a brush and compressed air.
Verified embed depth'of 41/2", Dowels were secured with Hilti Hy 150 max epoxy
adhesive (ICC- ESR 1967/ expiration date 04/2009), The north and south walls were
originally cast in the wrong location, Needs EOR approval for as-built condition,
To the best of our knowledge, the work inspected was in accordance with plans dated
02-12-09 with note #1 clouded area and applicable workmanship provisions of 'the
I.B,C" except if noted above,
Reviewed By:
fJJ ,~/4.-
Michael L Meyef
Technical Manager
I
I
1
1
I
c:
Barrantine Bates Lee - (e-mail) Oregon MilitaryDepL - (e-mail)
kpff Consulting Engineers - (e-mail) Wildish- Tony Dean (email), City of Springfield MLM:sc
This report and/or enclosed test data is the confidential property of the cHent to whom it is addressed and pertains to the specific
process and/or material evaluated. As such, information contained herein shall natbe reproduced in part or full and/or any part
thereof be disclosed without FEI Testing & Inspection, lnc,'s written authorization.
7ffJ tom CaneD Avenue' CoovaIlis, Oregon 97330, phone (541) 757-4698, fax (541) 757-2991 .
29540 B Airport Road ' E(Jgene, 0egJn 97402 ' phone (541)684J849 , fax (541) 684-J851 .
63050 Corporate Place, Suite 2 ' Bend,: Oregon 97701 'phone (541) 382-4844 ' fax (541 ) 382-4846
SfEl
Gcv:c..; " ,Ca/ & Construction Servires
11~'llllet;<iI~~'~~'IIII~_
Client:
Project: lCAFRC- BlM
Warehouse Addition
3110 Pierce Parkway
Springfield, Oregon,
,6.Er'?~~
Mr, Jim Thomas
Wildish Building Co,
PO Box 7428
Eugene, Oregon 97401
,
Inspection of:, Reinforcing Steel/Epoxy Anchors
Contractor: Wildish Building Co,
Weather: Clear
BP No,: . Pending
Page 1 of 1
Daily Field Report
Date:
Project No,:
Report No,:
Inspector:
10 No,:
03-11-09
2097030
E-22538
D, Delatte
1080867-88
ICC
Continuous Inspection: 0
Periodic Inspection: 0
Performed inspection on reinforcing steel. for slab-on-grade with thickened areas within
lines A to G from 1 to 4 and small column near A 1, Reinforcing steel was checked for
grade, size, lap, placement and clearance, Reinforcing steel was secured with tie wire
and supported on concrete dobie blocks,
Also observed the placement of four (4) 1" x 39" all-thread anchors instailed into footing
for column near E4, The anchors that were instailed during concrete placement were
instailed at the wrong location, Prior to instailation the predrilled holes were cleaned
with a brush and compressed,air. 'Verified minimum embed depth of 24", The anchors
were secured with Hilt; RE:500 epoxy adhesive (ICC ESR 1682) with an expiration date
of July 2009, ,
To the best of our knowledge, the work inspected was in accordance with plans dated
02-12-09 with Note #1 clouded area, e-mail from Engineer of Record about anchor
bolts being epoxied dated 03-09-09 and applicable workmanship provisions of the
LB,C" except if noted above,
Reviewed By:
/h ' ~,;Jtv;________
Michael L Me{er ,
Technical Manager
c:
Barrantine Bates lee - (e-mail)
kpff Consulting Engineers - (e-mail)
Oregon Military Dept. - (e-mail)
Wildish- Tony Dean (email)
City of Springfield
MlM:ld
This report and/or enclosed test data is the confidential property of the client to whom it is addressed and pertains to the specific
process and/or material evaluated. As such, information contained herein shall not be reproduced in part or full and/or any part
thereof be disClosed without FEI Testing & Insp~ctjon, Inc.'s written authorization.