HomeMy WebLinkAboutComments FLS 6/20/2006
Page 1 of 1
L1MBIRD Andrew
From: GORDON Gilbert
Sent: Tuesday, June.20, 2006 9:14 AM
To: L1MBIRD Andrew
Cc: GERARD Alan;'FECHTEL Melissa; MCKEE Bart (SUB)
Subject: Springfield Justice Center"RevlsedSite Plan DRC2006-00033 City of Springfield-Police
Andy,
J Access is,okay. The site has public roads on all four sides.
Water supply is shown on Plan sheet C1 and appears okay. The minimum water supply shall
be 2250 gallons per minute based on a total square footage of 112, 776 square feet of Type I-
I B construction (based on my phone conversation with Carl Sherwood with Robertson-
Sherwood Architects) with automatic sprinkler protection per 2004 Springfield Fire Code Table
B105.1 and Section B105.2 Exception.Two hydrants are already in place and meet the
spacing requirements of 2004 Springfield Fire Code Table C105.1. Plan Sheet C1 also shows
a new 8-inch water line running along the west side of 4th Street.
~
Gilbert R. Gordon
. Deputy Fire Marshal
. Springfield Fire and Life Safety
225 Fifth Street
Springfield, Oregon 97477
541-726-2293
ggordon@ci.sRrinafield.or.us
Date Received' ~/)o~t'6
Planner: AL 7"
6/20/2006