HomeMy WebLinkAboutComments FLS 8/1/2008
TENTATIVE SITE PLAN REVIEW APPLICATION
PRE-SUBMITTAL CHECKLIST
Deputy Fire Marshal: Gilbert Gordon
Case #: PRE2008-00051
FIRE
o Site Plan
Complete Incomplete See Fire
Note(s)
~
On-site vehicular circulation
o Improvement and Public Utilities Plan
Complete ,Incomplete See Fire
Note(s)
~
Location of existing and required fire hydrants and
similar public facilities
Fire Notes:
1.
Additional comments not related to the, completeness of the application:
1. An additional fire hydrant will need to be installed" near the back of the property due
to the distance from the public fire hydrant (H-1327) exceeding 600 feet to the farthest
point of the back of the proposed building per 2007 Springfield Fire Code 508.5.1,
Exception 2. " " " :
2. Also show locations of post indicator valves cont"roling the sprinkler system and
required fire hydrant meeting NFPA 24, "Standard for the Installation of Private Fire
Service Mains and Their Appurtenances," 2007 edition.
Date Received. 8/110 g
Planner: KG Lf:,
, Revised 9/24/07