Loading...
HomeMy WebLinkAboutComments FLS 8/1/2008 TENTATIVE SITE PLAN REVIEW APPLICATION PRE-SUBMITTAL CHECKLIST Deputy Fire Marshal: Gilbert Gordon Case #: PRE2008-00051 FIRE o Site Plan Complete Incomplete See Fire Note(s) ~ On-site vehicular circulation o Improvement and Public Utilities Plan Complete ,Incomplete See Fire Note(s) ~ Location of existing and required fire hydrants and similar public facilities Fire Notes: 1. Additional comments not related to the, completeness of the application: 1. An additional fire hydrant will need to be installed" near the back of the property due to the distance from the public fire hydrant (H-1327) exceeding 600 feet to the farthest point of the back of the proposed building per 2007 Springfield Fire Code 508.5.1, Exception 2. " " " : 2. Also show locations of post indicator valves cont"roling the sprinkler system and required fire hydrant meeting NFPA 24, "Standard for the Installation of Private Fire Service Mains and Their Appurtenances," 2007 edition. Date Received. 8/110 g Planner: KG Lf:, , Revised 9/24/07