HomeMy WebLinkAboutComments FLS 8/1/2008 TENTATIVE SITE PLAN REVIEW APPLICATION PRE-SUBMITTAL CHECKLIST Deputy Fire Marshal: Gilbert Gordon Case #: PRE2008~00049 FIRE Date ReceiVed:~t Planner: MM f/"(..5vb",:::r o Site Plan Complete Incomplete See Fire Note(s) ~ III On-site vehicular circulation' o Improv~ment and Public Utilities Plan Complete Incomplete See Fire Note(s) f.'0!! ~ !II Location of existing and required fire hydrants and similar public facilities Fire Notes: <.. 1.' , Additional comments not related to the completeness of the application: 1. The distance from the fire hydrant to the most remote point on the proposed modular building exceeds the maximum 400 foot distance for a commercial non-sprinklered building per 2007 Springfield Fire Code 508.5.1. Two possible options: A. Provide sprinkler protection to the proposed building meeting NFPA 13 standards. This will in turn allow the distance to the fire hydrant from the furthest point on the building be increased to 600 feet per SFC 508.5.1, Exception 2. The scaled distance to the fire hydrant on 16th and G Streets is approximately 500 feet. The scaled distarice to the fire hydrant on 16th and H Streets is approximately 430 feet. However, the poposal would eliminate access from H Street. B. Provide a fire hydrant within the 400 foot maximum distance to the furthest point on the proposed building. Contact Bart McKee or Rebecca Templin at Springfield Utility Board Water Department, 541-726-2396. Revised 9/24/07