Attached are the pre-submittal comments for this project from Springfield Fire and Life Safety. I
will be unable to attend this meeting due to required training at the Peace Health Sacred Heart
Hospital project on Friday.
Gilbert R. Gordon
Deputy Fire Marshal
Springfield Fire and Life Safety
225 Fifth Street
Springfield, OR 97477
Phone: 541-726-2293
E-Mail: aaordonlalcLsorinafield.oLus
r.
Date ReceIVed:-A'hoo!
PI~nner: At
6/24/2008
Date Received:
TENTATIVE SITE PLAN REVIEW APPLICATION
PRE-SUBMITTAL CHECKLIST
Deputy Fire Marshal: Gilbert Gordon
Case #: PRE2008-00041
FIRE
o Site Plan
Complete Incomplete See Fire
Note(s)
[g]
[J
. On-site vehicular circulation
o Improvement and Public Utilities Plan
Complete Incomplete See Fire
Note(s)
~
[J
Location of existing and required fire hydrants and
similar public facilities
Fire Notes:
1.
Additional comments not related to the completeness of the application:
1. The 16 foot wide fire apparatus access road does not meet fire code minimum width
of 20 feet. The fire apparatus access road shall have an unobstructed clear width of not
less than 20 feet and and unobstructed vertical clearance of 13 feet 6 inches per 2007
Springfield Fire Code 503.2.1. The entire width has to support the 80,000 lb. load
required by SFC 503.2.3 and SFC Appendix 0102.1.
2. The depth of the turnaround needs to be extended to 70 feet per SFC Appendix 0,
Figure 0103.1. .
3. "No Parking, Fire Lane" signs shall be posted on both sides of the fire apparatus
access road per SFC 503.3 and SFC Appendix 0103;6. The spacing shail be guided by .
the Manual on Uniform Traffic Control Devices, 2003 edition, Section 2B.41.
. )
4. A fire hydrant is required to serVe the proposed project due to the distance from the
back of Unit 4 to the existing fire hydrant exceeding 600 feet per SFC 508.5.1, Exception
1. Contact Bart McKee or Rebecca Templin at Springfield Utility Board Water Department
at 726-2396.
,