Geotechnical & Consln.dion Services
Compressive Strength of Concrete
(AsTM C 39)
11~'llllrt;"l~~':J~'I(IJI\.IfI.
CLIENT
EWEB
500E. 4th Ave.
Eugene, Oregon
PROJECT Hayden Bridge Water
. Filtration Plant Expansion
Springfield, Oregon
DATE
PROJECT NO.
REPORT NO.
02-20-09
2087168
6164
B.P. NO. . .-2008-00225
DATE CAST 01-09-09 CAST BY J. Keller DATE RECEIVED 01-10-09
STRENGTH REQUIRED . 4000 psi SPECIMEN SIZE 4" x8"
STRENGTH PLACED 4000 psi SACKS SUPPLIER Knife River
PRODUCT CODE 2440K1UOKS . CEMENT MAX SIZE AGG. 3/4"
ADDITIVES Super; Eclipse; Hot water AIR CONTENT 6.0%
LOAD NO. 1 TICKET NO. 3160681 SLUMP . 8"
CONCRETE TEMP 63' F YARDAGE 6.0 OF TIME 10:10AM
AIR TEMP 41' F WEATHER Overcast SPECIMEN STORAGE ASTM C31
POUR LOCATION Elevated walkway above wall #23.
AVERAGE
TEST AGE AREA WEIGHT TOTAL COMPRESSIVE STRENGTH TIM E OF TYPE OF
DATE (DAYSl (IN.'1 (LBSl LOAD (LBS\ STRENGTH (PSII (Psn TEST FRACTURE-
01-16-09 7 12.50 7.9 32800 2620. 1:20 PM 5
02-06-09 28 12.56 8.0 40900 3260 10:10AM 3
02-20-09 42 12.69 8.1 44060 3470 8:10AM 5
03-06-09 56
"*1 - End Cones 2 - Cone/Split 3 - Columnar 4 - Diagonal 5 - Side (top and bottom) 6 - Side (top or bottom)
REMARKS: Mike Stickling (EWEB) was advised of on-site test resuits.
Reviewed By:
fh . '-f:. /1... -------
Michaell. Me~er;---
Technical Manager
c:
EWEB- Mike Stickling (email)
'EWEB- Wally McCullough (email)
OBEC- Pete Slocum (email)
Wildish Building Co.- Kevin Fitzjarreil (email)
Wildish Building Co.- Jake Stucky (email)
City of Springfieid
Knife River
MLM:sc
This report and/or enclosed test data is the confidential property of the client to whom it is addressed and pertains to the specific
process and/or material evaluated. As such, information contained herein shall not be reproduced in part Of full and/or any part
thereof be disclosed 'Nithout FEI Testing & Inspection,. Inc.'s written authorization.
750 NW CaneII A_ue' CavaDis, Qeg:x197330' phme (541) 757-4698, fax (541) 757-2991
29540 B AirPort Road . Eugene, Qeg:x1 97402 . phme (541) f384..3849 . fax (541) 684-3851
63050 Corporate Place, Suite 2 . Bend, Oregon 97701 . phone (541) 382-4844 . fax (541) 382-4846
SfEl
11:"llm,;.,~~'Jta'IIII~.I~l.
CLIENT
EWEB
500E. 4th Ave.
Eugene, Oregon
DATE CAST
STRENGTH REQUIRED
_STRENGTH PLACED
PRODUCT CODE
ADDITIVES
LOAD NO.
CONCRETE TEMP
. AIR TEMP
POUR LOCATION
LOAD 3 SAMPLED
Geotechnical & Construction Services
Compressive Strength of Concrete
(ASTM C 39)
PROJECT
Hayden Bridge Water
Filtration Plant Expansion
Springfield, Oregon
DATE
PROJECT NO.
REPORT NO.
02-27-09.
2087168
6186
B.P. NO.
200a~0-0225
01-30-09 CAST BY A. Fenstennacher DATE RECEIVED 01-31-09
4000 psi SPECIMEN SIZE 4" x 8"
4000 psi SACKS SUPPLIER Knife River
40-SE7 CEMENT MAX SIZE AGG. 3/4"
Super; Eclipse; Hot water AIR CONTENT 3.5%
3 TICKET NO. 3354055 SLUMP 8 1/4"
580 F YARDAGE 10.0 OF 44.0 TIME 10:30 AM
380 F WEATHER Fog SPECIMEN STORAGE ASTM C31
Ramp slab on grade up to sump area; elevated walkway above wall #21; east and west raw water
channel walls above wall #24..
From west end of ramp slab.
AVERAGE
TEST AGE AREA WEIGHT TOTAL COMPRESSIVE STRENGTH TIME OF TYPE OF
DATE (DAYS) (IN.') (LBS) LOAD (LBS) STRENGTH (PSIl (PSIl TEST FRACTURE-
I 02-06-09 7 12.56 8.4 54600 4350 10:40 AM 4
I 02-27-09 28 12.56 8.5 78745 6270 10:15AM 2
I . 02-27-09 28 12.56 8.5 81390 6480 6375 10:20 AM 2
I Hold
.*1 - End Cones 2 - Cone/Split 3 - Columnar 4 - Diagonal 5 - Side (top and bottom) 6 - Side (top or bottom)
REMARKS: Jake Stucky (Wildish) was advised of on-site test results.
Reviewed By:
fJ;. '1'. ~
Michael L. Meyer{/
Technical Manager
c:
EWEB- Mike Stickling (email)
EWEB- Wally McCullough (email)
OBEC- Pete Slocum (email)
Wildish Building Co.- Kevin Fitzjarrell (email)
Wildish Building Co.- Jake Stucky (email)
City of Springfield
Knife River
MLM:sc
This report and/or enclosed test data is the confidential property of the client to whom it is addressed and pertains to the specific
process and/or material evaluated. As such, information contained herein shall not be reproduced in part or full and/or any part
thereof be disclosed without FEI Testing & Inspection, Inc,'s written authorization.
,
750 NN CanElI Avenue' CavaIIis, 0regcx197330 . phone (541) 757-4698 . fax (541) 757-2991
29540 B Airpat Road . Eugene, 0regcx197 402 . phone (541) 684-3849 . fax (541) 684-3851
63050 Corporate Place, Suite 2 . Bend, Oregon 97701 . phone (541) 382-4844 . fax (541) 382-4846
~ftj
Page 1 of 1
11~'lmrl;.I~~'~a.lIIIJ~i/1 M.
Cc.v~.,j ,,1iCaI & Construction Servires
Daily Field Report
Client: EWEB' Project: Hayden Bridge Water Filtration Date: 02:24-09
500E. 4'h Ave. Plant Expansion Project No.: 2087168
Eugene, Oregon Springfield, Oregon Report No.: E-22437
Inspector: A. Fenstermacher
10 No.:
5258882-49
ICC
Inspection of:' Epoxy Anchors/ Dowels Weather: Showers/Inside Continuous Inspection: 0
Contractor: WiJdish Building Co. BPNo.: 2008c00225 Periodic Inspection: 0
Performed continuous inspection during the installation of eight (8) 5/8" x 10" vertical
stainless steel all.thread anchors into suspended slab for two (2) filter aid polymer
storage tank pads and eight (8) 5/8" x 21" stainless steel all thread dowels, three (3)
vertical and five (5) horizontal in gailery for new south clearwell opening add-on.. Prior
to installation, the predrilled holes were cleaned with compressed air and a brush.
Verified minimum embedment of 4" for storage tank and 6" for c1earwell.
Anchors/dowels were secured with Epcon A7 (ICC"ES ESRc2351, expiration date 11-
07'09).
Brady (Wildish Building) was asked to notify our office when additional services are
needed.
. To the best of our knowledge, the work inspected was in accordance with plans dated
02/2008 and applicable workmanship provisions of the I.B.C., except if noted above.
Reviewed By:
(JJ .'1:.~
Michael L ~eye(l .
Technical Manager
c:
EWEB- Mike Stickling (em ail)
EWEB- Wally McCullough (email)
OBECc Pete Siocum (email)
Wildish Building Co.- Kevin Fitzjarrell (em ail)
Wildish Building CO.c Jake Stucky (email)
City of Springfield .
MLM:sc
. This report and/or enclosed,test.data is the confidehtial property of the client to whom it is addressed and pertains to the specific
process and/or material evaluated. As such, information contained herein shall not be reproduced in part or full and/or any part
~thereof be disclosed without FE! Testing & Inspection, Inc.'s lNfitten authorization.
7ffJ NN ComeIIAvenue' ConiaIlis, Ci"egm 97330' phone (541) 757-4698, fax(541) 757-2991
29540 BAirportRood. Et.gene, Ci"egm97402' phone(541)f384:3849 .fax(541)684.J851
63050 Corporate Place, Suite 2 . Bend, Oregon 97701 . phone (541) 382-4844 . fax (541) 382-4846
~.....
~'rtJ
".
Page 1 of 1
"~'lmrt;"I~"':t="ll'li_
Geotedmical & Construc:OOn Seivices
Daily Field Report
Client: EWEB Project: Hayden Bridge Water Filtration Date: 02-27"09
500E. 4'h Ave. Plant Expansion Project No.: 2087168
Eugene, Oregon Springfield, Oregon Report No.: E-22463
Inspector: D. Delatte
ID No.: 1080867-88
Ice
Inspection of: Epoxy Anchors Weather: Inside... Continuous Inspection: 0
Contractor: Wildish Building Co. BP No.: 2098-00225 Periodic Inspection: 0
Observed the placement of six (6) vertical and twenty-three (23) horizontal 5/8" x 21" all
thread anchors and four (4) 1/2" x-5" horizontal anchors installed into existing tank walls
as follows: three (3) 5/8" vertical and eleven (11)'horizontal anchors at two (2) new
collar walls at penetration, one wall has twelve (12) horizontal anchors. The 1/2"
anchors were installed in the gallery area. Prior to installation, the predrilled holes were
cleaned with a brush and compressed air. Verified the minimum embed depth of 6" for
5/8" anchors and 3" for 1/2" anchors. Anchors were secured with Epcon A" 7 epoxy
adhesive (ICC- ESR 2351/ expiration date 11-07-09).
Jake Stucky (Wildish) was asked to notify our office when additional services are
needed.
To the best of our knowledge, the work inspected was in accordance with plans dated
02/2008 and applicable workmanship provisions of the I.B.C., except if noted above.
Reviewed By:
/lJ.'j.~
Michael L. Mefer
Technical Manager .
c:
EWEB- Mike Stickling (email)
EWEB- Wally McCullough (email)
OBEC- Pete Slocum (email)
Wildish Building Co.- Kevin Fitzjarrell (email)
Wildish Building Co.- Jake Stucky (em ail)
City of Springfield.
MLM:sc
This report and/or enclosed test data is the confidential property of the client to whom it is addressed and pertains to the specific
process and/or material evaluated. As such, information contained herein shall not be reproduced in part or full and/or any part
thereof be disclosed without FEI Testing & Inspection, Inc.'s written authorization.
7ffJ NN Cornell Avenue. Cavalis, Oegon 97330 . phone (541) 757-4698 . fax (541) 757-2991
29540 B Airport Road . Eugene, Oegon 97402 . phone (541) 6M3849 . fax (541) 684-J851
63050 Corporate Place, Suite 2 . Bend, Oregon 97701 . phone (541) 382-4844 . fax (541) 382-4846
<-'
TEST AGE AREA WEIGHT TOTAL COMPRESSIVE
DATE (DAYSl (IN.') (LBS) LOAD (LBSl STRENGTH (PSIl
02-09-09 7 12.50 8.20 30900 2470
03-02-09 28 12.56 8.22 48830 3890
03-02-09 28 12.56 8.21 50365 4010
Hold.
~fE'
11.'mll'l;"lllio'~aIlLIJI'.III"
CLIENT
EWEB
500E. 4th Ave.
EUgene, Ore90n
DATE CAST
STRENGTH REQUIRED
STRENGTH PLACED
PRODUCT CODE
ADDITIVES
LOAD NO.
CONCRETE TEMP
AIR TEMP
POUR LOCATION
LOAD 2 SAMPLED
U1 - End Cones
G-.v~ " .;caJ & Construction Servires
Compressive Strength of Concrete
(ASTM C 39)
PROJECT
Hayden Bridge Water
Filtration Plant Expansion
Springfield, Ore90n
DATE
PROJECT NO.
REPORT NO.
03-02-09
2087168
6187
B.P. NO. _ - 2008"00225
02-02-09 CAST BY A. Fenstermacher DATE RECEIVED 02-03-09
3000 psi SPECIMEN SIZE 4" x 8"
3000 psi SACKS SUPPLIER Knife River
30-1K CEMENT MAX SIZE AGG. 3/4"
AEA; Fibers; Hot water AIR CONTENT 5.3%
2 TICKET NO. 3352725 SLUMP 6 1/2"
580 F YARDAGE 10.0 OF 30.0 TIME 9:30 AM
410 F WEATHER Clear SPECIMEN STORAGE ASTM C31
Alum tank pedestais and elevated walkway support walls at southwest comer of coa9ulant building.
From 1" lift in southeast pedestal.
AVERAGE
STRENGTH
(PSIl
TIME OF
TEST
9:15AM
8:00 AM
8:05 AM
TYPE OF
FRACTURE~
5
5
5
3950 .
2 - Cone/Split
3 - Columnar
4 -Diagonal
5 - Side (top and bottom)
6 - Side (top or bottom)
REMARKS: Jake Stucky (Wildish) was advised of on-site test results.
Reviewed By:
JJJ. ;;.~
Michael L. Meye
Technical Man er
c:
EWEB- Mike Stickling (em ail)
EWEB- Wally McCullough (email)
OBEC- Pete Slocum (email)
Wildish Building Co.- Kevin Fitzjarrell (emall)
Wild ish Building Co.- Jake Stucky (email)
City of Springfield
Knife River
. MLM:sc
This report and/or enclosed test data is the confidential property of the client to whom it is addressed and pertains to the specific
process and/or material evaluated. As such, information contained herein shall not be reproduced in part or full and/or any part
thereof be disclosed without FEI Testing & Inspection, Inc.'s written authorization.
7ffJ NJV CaneIIAvenue' CavalIis. 0egJn 97330, phone (541) 757-4698, fax (541) 757-2991
29540 BAirpOO Road . Eugene, 0egJn 97402 . rtme (541) I3lJ4.;J849 . fax (541) 684-3851
630ffJ Corporate Place, Suite 2 . Bend, Oregon 97701 . phone (541) 382-4844 . fax (541) 382-4846