April 16, 1.996
~.....
~
Dana Evan..
1474 Goodpasture Island Rd.
f:ugene, OR 97401
RE : lillLMO\l"ke.t._~c::t-.
W.O. j/B970-RDR
SDr inaf iel.;L:-...F-oundat12lLS 1.a b In s peg.tt!.2Il
As you requested, an inspection was
adequacy of the existing patio slab and
wall load from the proposed addition.
performed to determine the
slab edge to support roof and
The approxlmately 20-25 year old slab on grade is void of any v.i l1u'1l
structura 1 detects with little or no cracking and no evidence- ot
heaving due to expansive soils. The approximately B inch deep by 10
inch (mllxlmuro) wide unreinforced expanded slab edge shows no
struct.ura 1 defect. Al though the bottom of the footing is above the
code requ.i red frost depth, no evidence of damage due to frost heave
was observed.
Thp. mAximum calculated soil pres'Hlr.p. based upon an average 8 inch
wldr.h 1s 650 psf. The allowable soil pressure for this type of 9011
is 1000 psf. Based on observations at the site and 60il pres~ure
calcul ati ons, the slab and slab edge 1.s adequate to support the
proposed roof and wall vertical load.
r hope you find this report adequate for your purposes at this tim".
Please contact me if you have further questions. Thank you for thi f.:
opportunity to be of service.
Very truly yours,