December 21, 1995
Project EBXX-95-0136
Report E-56242
Mr. Duane Hopkins
Springfield Forest Products
P.O. Box 719
Springfield, Oregon 97477
Dear Mr. Hopkins:
Re: Parts Storage Building
Springfield Forest Products
1651 South F Street
Springfield, Oregon
P.O. #C0335 -B.P. No. 95-0238
:' ,J':\ 'J: ?; I:.!: j:+~ I ,:. ~'j
Project Information
December 19, 1995
Report
Performed visual inspection on the repair weldments on the W8x24 knee brace stiffners
near the west end of the building. The welds were checked for size (verified 1/4" by
Coakley Engineering), profile, and location (welded all-around), and appear acceptable as
per approved prints, engineers instructions, and'the AWS Dl.l Steel Welding Code.
Sincerely,
,qzJ ~~~~ft2B
iEu,geneBr~nch .... ,_. .-...--,...., '''_', .......
,
,,'
.'
:.!:.":
c: .CoakleyEngineei's'" '--'. ',_.~~ ",. .
City of Springfield
.._~ ".
....,...-.. .. . .~..._-".
- .. . ...
"- ':;:'.':':,".:-:;:.'";: .~..!.'
" ~ '.
".:1,
c:\wp51 \reports\welda\spr56242.spr
'r
BRAUN'M
I NTE RTEC
Braun Infertee Northwest,
2285 Nugget Way
Eugene, Oregon 97403
503.746.9649 Fax: 746,7163
Engineers and Scientists Serving
the Built and Natural Environments
November 10, 1995
Project EBXX-95-0136
Report E-56136
Mr. Duane Hopkins
Springfield Forest Products
P,O. Box 719
Springfield, Oregon 97477
. 'Dear Mr.' Hopkins:
Re: Parts Storage Building
Springfield Forest Products
1651 South F Street
Springfield, Oregon ,
P.O. #C0335 - B.P. No. 95;-0238 .
Project Information
Weldments
November 09, 1995
Report
Performed visual inspection on the completed field weldments connecting the knee-braces
to the columns and beams near the west end of the 50' x 120' parts storage building. The
. welds were checked for size, length, profile, location and workmanship, Welds on both
braces were marked for repair due to undercut, porosity, undersize, poor profile andlor
workmanship. Dick Duncan (Springfield Forest Products) was advised and was asked to
notify our office when additional services are needed.
Note: Contacted Bob Coakley (Coakley Engineering) to verify weld size requirement,
Was advised that 114" fillet welds are required on all sides of both connections.