November 26, 1996 .
Mr. Larry Goats
3823 Winslow Avenue
Springfield, Oregon 97477
Re: Residence
3823 Winslow Avenue
Springfield, Oregon
&\ qu.\ c'1 \
Braun Intertec Corporation
, 2285 Nugget Way
. . 'Eugene: Orego';' 97403'
541-746-9649 fax: 746-7163
',:.~~-.:"7.~ -::~.:; ". "., "":'.. .:~ .-- "'J':;."_.. ~_. .:-:.......-. . "':;1
,;. 'Engineers and Scientists Serving '.
- '~:-:~+-.h~t~e'fJuilf-and No!Uro/.Env;ronments....(1
Project: EBXX-96-0416
Report E58153
Epoxy Anchored Bolts
November 26, 1996
S. Wilder ICBO#72031
'" .
Partly Cloudy - 400
Report
1
Jj
Witnessed the installation of the epoxy anchored bolts for the HD hold downs. The 5/8"
all thread bolts were embedded a minimum of 14" and installed with Rawl Foil-Fast
Cartridge System adhesive in accordance with manufacturer's directions and in accordance
with Branch Engineering drawings dated October 16, 1996. All holes were cleaned with a
brush and compressed air prior to installing holts. Contractor stated bolts will be
tightened after adhesive has set. Contractor was asked to notify our office when additional
services are needed.