Steve,
Scott Morris and I met this morning to review fire hydrant distances for the Aramark project.
Scott noted that there will be a gated access on the northwest corner of the property for truck
access to serve this occupancy via' private access easement per Plan S~eet C2. This will allow
a fire hydrant located to the north ofthe property, H-1325 shown onPlan Sheet C1, to be
within 600 feet of the required distance to the proposed building. Since this gate will be an
electric rolling gate, a Knox keyed gate switch will be required for fire department access' (this
also applies to the electric rolling gates at the main entrance). Therefore, o'1e existing fire
hydrant can meet part of the water flow requirements. .
Another fire hydrant will still need to be installed near the main entrance to meet water supply
requirements.