Compressive Strength of Concrete
(ASTM C 39)
CLIENT
Mr. Joe McCormack
Lane Transit District
PO Box 7070
Eugene, Oregon 97403
'PROJECT
L TO Gateway Mall Station
3000 Gateway Street
Springfield, Oregon
DATE
PROJECT NO.
REPORT NO.
. 02-06-09
2087170
.6165
, B.~. NO: ~~M2008-00440-1
DATE CAST
STRENGTH REQUIRED
STRENGTH PLACED
PRODUCT CODE
ADDITIVES
LOAD NO.
CONCRETE TEMP
AIR TEMP
POUR LOCATION
01.09-0g CAST BY A. fen.stermacher DATE RECEIVED
3000 psi SPECIMEN SIZE,
3000 psi SACKS SU!'PLlER
313065 CEMENT MAX SIZE AGG.
AEA; WRA; Color; 1% Accelerator; Hot water AIR CONTENT
1 TICKET NO. 60010635 SLUMP
68" F YARDAGE 8.5 OF 8.5 TIME
42" F WEATHER Partly Sunny SPECIMEN STORAGE
Colored section of crosswalk between pedestrian walkway and mall.
01-10-09
4" x8"
ESG
3/4"
8.0
6"
2:45 PM
ASTM C31
AVERAGE
TEST AGE AREA WEIGHT - TOTAL COMPRESSIVE. STRENGTH TIME OF TYPE OF
DATE (DAYS) tiN.') (LBS) LOAD (LBS) . STRENGTH (PSI) (PSIl TEST FRACTURE'"
01-16-09 7 12.50 8.1 38000 3040 1:30 PM 5
02-06-09 28 12.56 8.2 50700 4040 10:20 AM 5
02-06-09 28 12.56 8_2 48200 3840 3940 10:25 AM 4
Hold
"1 - End Cones 2 - Cone/Split 3 - Columnar 4 - Diagonal S. -:- Side (top and bottom) 6 - Side (top or bottom)
REMARKS: Adam Hughes (Brown Contracting) was advised of on-site test results.,
Reviewed By:
fh~4r.
Michael L. Meyer
Technical Manager.
c:
Rowell Brokaw- Mark Young (email)
Ang Engineering- Jok Ang (emaH)
Balzhiser Hubbard- Tina Guard (email)
Brown Contracting- Adam Hughes (email)
City of Springfield- Denny Wright (emall)
MLM:sc
This report and/or enclosed test data is the confidential property of the client to whom it is addressed and pertains to the specific
process andlor material evaluated. As such, information contained herein shaU not be reproduced in part or full andlor any part
thereof be disclosed without FEI Testing & Inspection, Inc.'s written authorization:
7ffJ NN CaneI Avenue' CavaJIis, Oregm 97330. phone (541) 757-4698 -fax(541) 757.2991
29540 BAirpat Road . Eugene, Oregm 97402 ' phone (541) 684-3849' fax (541) 684-3851
63050 Corporate Place, Suite 2 . Bend, Oregon 97701 . phone (541) 3824844 . fax (541) 382-4846
~.,..~~
~r_l
11:"lmef;.I\~'.a'lIlml.11~ll
Gc.v~ " ~...,J & Coiistruclion SeMces
Compressive Strength of Concrete
(ASTM C 39)
CLIENT
Mr. Joe McCormack
Lane Transit District
PO Box 7070
Eugene, Oregon 97403
PROJECT L TD Gateway Mall Station
3000 Gateway Street
Springfield, Oregon
DATE
PROJECT NO.
REPORT NO.
02-05-09
2087170
6158 1
'B.P. NO. COM2008-00440 )
~---_.- ~.
~~_._-----
DATE CAST 01-06-09 CAST BY A. Fenstermacher DATE RECEIVED 01-07-09
STRENGTH REQUIRED 3,000 SPECIMEN SIZE 4" x 8"
STRENGTH PLACED 3,000 SACKS SUPPLIER ESG
PRODUCT CODE 313065 CEMENT MAX SIZE AGG. " 3/4"
ADDITIVES Hot waler, VMA, WRA, AEA AIR CONTENT,
LOAD NO. t TICKET NO. 58006668 SLUMP 51/2"
CONCRETE TEMP 66" F YARDAGE 9.5 OF 9.5 TIME 8:15AM
. AIR TEMP 490 F WEATHER Overcast SPECIMEN STORAGE ASTMC31
POUR LOCATION South site-wall
AVERAGE
TEST AGE AREA WEIGHT TOTAL COMPRESSIVE STRENGTH TIME OF TYPE OF
DATE (DAYS) (IN.') (LBS) LOAD (LBS) STRENGTH (PSI) (PSI) TEST FRACTURE- .
01-13-09 7 12.50 I 8.2 23400 1870 8:15AM 5
02-03.Q9 28 12.62 I 8.2 33800 2680 9:25 AM 5
02-05-09 30 12.56 I 8.2 31700 2520 8:00 AM 5
03-03-09 56
**1 - End Cones 2 - Cone/Split
3 - Columnar
4 - Diagonal
5 - Si.de (top and bottom)
6 - Side (top or bottom)
REMARKS: Adam Hughes (Brown Contracting) was advised of on-site test results.
Reviewed By:
AX~
Michael L. M r
Technical Mager
c: .
Rowell Brokaw- Mark Young (em ail)
Ang Engineering- Jok Ang (email)
Balzhiser Hubbard- Tina Guard (email)
Brown Contracting- Adam Hughes (email)
City of Springfield- Denny Wright (email)
MLM:ld
This report and/or enclosed test data is the confidential property of the client to whom it is addressed and pertains to the specffic .
process and/or material evaluated. As such, information contained herein shall not be reproduced in part or full and/or any part
thereof be disclosed without FEI Testing & Inspection, Inc.'s written authorization.
7fIJ tw Canel1Avenue' CorvaIls. Qeg:n97330' phooe (541) 757-4698 'raX(541) 757-2991
29540 BAjrportRoad' Eugene, Qeg:n 97402 . phcne (541) I3&h3849 . fux (541) 6!J4.J851
63050 Corporate Place, Suite 2. Bend, Oregon 97701 . phone (541)382-4844' fax (541) 382-4846
~..r
~rc_
. 1OOWi!"''''''''"''llIliI!I Gcv..-';-,,1icaI & ConsbucIion Services
Page 1 of 1
Report of Inspection Services
Weldin~/High-Strength Boltin~
Client: Mr. Joe McCormack
Lane Transit District
PO Box 7070
Eugene, Oregon
Project: L TD Gateway Mall Station
3000 Gateway Street
. Springfield, Oregon
L TD Gateway Mall Station
Date:
,
Project No.:
Report No.:
Inspector:
ID No.:
02-04-09
2087170
E-22324
K. Green
8003776
ICC
Field: 0
Inside
COM2008-00440
Inspection of:
Fabricator or Erector:
Contractor:
Welding
Gibson Steel
Brown Contracting
Shop:' 6il
Weather:
"'--BP'No." .
Performed visual inspection of the following fabricated structural.steel canopy compon~nts: platform roof
frame number 26 and six (6) platform gutters MK #10-A. Completed welds were checked for size, length,
profile and location. . " .
Gentry (Gibson Steel) was asked to notify our office when additional services are needed.
To the best of our knowiedge, the work checked is. in conformance with drawings dated 06-07-08 and
applicabie AWS D1.1 code, except if noted abov.e.
Reviewed By:
j?J . 7f. /Ju; f
Michael L Me~r
Technicai Manager
c:
Rowell Brokaw- Mark Young (email)
Ang Engineering- Jok Ang (email)
Balzhiser Hubbard- Tina Guard (em ail)
Brown Contracting- Adam Hughes (email)
City of Springfield- Denny Wright (em ail)
MLM:sc
This report and/or enclosed test data is the confidential property of the client to whom it is addressed and pertains to the specific
process and/or material evaluated. ,As such"information contained herein shall not be reproduced in part or full and/or any part
thereofbe.discJosed 'Nithout'FEI Testing & Inspection, Inc.'s written authorization.
750 rwv Cornell Avenue' Corvallis, Oregon 97330' phone (541) 757-4698' fax (541) 757-2991.
29540 B Airport Road. Eugene, Oregon 97402. phone (541) 684-384g. fax (541) 684-3851
63050 Corporate Place, Suile 2. Bend, Oregon 97701 . phone (541) 3824844'. fax (541) 382-4846
6JfEJ
".'IINlMIl.""'IIIIMIII. Gootechnical & Construction Servires
Pag,:, 1 of 1
Report of Inspection Services
Weldin~/HiQh-Strength BoltinQ
Inspection of:
Fabricator or Erector:
Contractor:
Welding
Gibson Steel
Brown Contracting
Project: L TD Gateway Mall Station Date: 01-30-09
3000 Gateway Street Project No.: 2087170
Springfield, Oregon ~eport No.: E-22300
Inspector: K. Green
ID No.: 8003776
ICC
Shop: 1!1 Field: 0
Weather: Inside ___
CSP-No.:---COM200B':00440
Client: Mr. Joe McCormack
Lane Transit District
PO Box 7070
Eugene, Oregon
Performed visual inspection on fabricated structural steel platform roof frames: 18A, 20A, 21A, 22A and
24A, and column assembly 3B. Completed welds were checked for size, length, profile and location.
Gentry (Gibson) was asked to notify.our office when additional services are needed.
To the best of'our knowledge, the work checked is in conformance with shop drawings dated 06-07-08
and applicable AWS D1.1 code, except if noted above.
Reviewed By:
A.~~
Michael L. Meyer
Technical Manager
c:
Rowell Brokaw- Mark Young (email)
An9 Engineering- Jok Ang (email)
Balzhiser Hubbard- Tina Guaid (email)
Brown Contracting- Adam Hughes (email)'
City of SpringfieJd- Denny Wright (em ail)
MLM:sc
This report and/or enclosed test data is the confidential property of the client to whom it"is addressed and pertains to !he specific
process and/or material evaluated. As such, information contained herein shall not.be reproduced in part or full andlor any part
thereof be disclosed without FE! Testing & Inspection, Inc.'s written authorization.
750NW Comell Avenue' C01vallis, Oregon 97330, phone (541) 757-4698, fax (541) 757-2991
29540 B Airport Road, Eugene, Oregon 97402. phone (541 ) 684-3849, fax (541) 684-3851
63050 Corporate Place, Suite 2 . Bend, Oregon 97701 . phone (541) 382-4844 . fax (541) 382-4646
S. .....l
-'. p,..
.4 .....
11~'lIl1rj;~".mlll",lm" Geoted1nical & Construdion SeMces
Page 1 of 1
Report of Inspection Services
Welding/High-Strength Bolting
Inspection of:
Fabricator or Erector:
Contractor:
Fabrication Welding
Gibson Steel
Brown Contracting
Project: L TO Gateway Mall Station Date: 02-02-09
3000 Gateway Street Project No.: 2087170
Springfield, Oregon, Report No.: E-22312
L TO Gateway Mall Station Inspector: L. Postier
ID No.:. 06120541
. AWS CWI
Shop: Ii!l Field: D
Weather: Inside
( - -------- .------ -- -. - -
.\.-.. B.!'. No.: _ _ C0!:12008-004!O
Client: Mr. Joe McCormack
Lane Transit District
PO Box 7070
Eugene, Oregon
Performed visual inspection on the following struc1ural steel gutter support assembly frames: 9A, (4) 10A,
(2) 11A and 12A. 'Completed welds were checked for size, length, profile and location.
Gentry (Gibson Steel) was asked to notify our office when additional services are needed.
To the best of our knowledge, the work inspected is in conformance with shop drawings dated 06-07-08
and applicable AWS 01.1 code, except if noted above.
Reviewed By:
jJa~~.1!:tr
Technical Manager
c:
Rowell Brokaw-Mark Young (email)
Ang Engineering- Jok Ang (email)
Balzhiser Hubbard- Tina Guard (email)
Brown Contracting- Adam Hughes (email)
City of Springfield- Denny Wright (email)
MLM:sc
This report andlor enclosed test data is the'confidential property of the c1ienl to whom it is addressed and pertains to the specific
process and/or. material evaluated. As such, infonnation contained herein shall no! be reproduced in part or full and/or any parf
" thereof be disclosed without FEI Testjng & Inspection, Inc.'s written authorization.
750 NW Comell Avenue' Corvallis, Oregon.97330 . phone (541) 757-4698 . fax (541) 757-2991
29540 BAirport Road' Eugene, Oregon 974D2' phone (541)684-3849' fax (541) 684-3851
63050 Corporate Place, Suite 2. Bend, Oregon 97701 . phone (541) 382-4844' fax (541) 382-4846