DAiLY FIELD REPORT
Date Performed:
Client:
January 20, 2009
Ms. Lauretta Davies
Jerri"s Home Improvement
P.O Box 2611
Eugene, Oregon 97402
Report Number:
722-90008-4
Project Name:
Jerr)"s-Warehouse Renovations
Project Lo:::;ation:
2525 Oiympic Street
Springfield, Oregon
P.O. No.:
Type of Inspection:
Z4175LD
Soils Observation
BP# COM2008-01S9S
Weather:' Clear
Field Observations and Comments
On site to observe exposed subgrade soils/standing water for the truck ramp. The footing excavation was cut to grade
and the water was above that elevation. A soil probe was used to assist us in determining the stability of the in-place
soils. Soil probe penetrations were only 4 to.6 inches indicating a relatively firm stable subgrade. However, in orger to
place and compact the one-foot of rock that is required under the footings, the water level would need to be below the
excavation depth. We recommend pumping 1he water out and keeping it low enough until the rock has been placed,
compacted, and test~d. We also recommend placing a foundation drain around the footi~g. To the best of our
knowledge, the work inspected was in accordance with the building department approved design drawings,
specifications and applicable workmanship provisions of the International Building Code.
Inspector: Raymond Aliperti
CCB #176269
If you have any questions regarding this report, please feel free to contact us at 541-746-9649.
Respectfully Submitted,
-Mri''''''.'
David Smith
Branch Manager
c: City of Springfield
Chambers Construction - David Bakke
Robertson Sherwood Archi1ects - Scott Stolarczyk
Metzler Engineering - Scott Metzler
THIS REPORT IS PROVIDED FOR THE INFORMATION OF THE CLIENT ONL y, THE REPRODUCTION OF THIS REPORT, BY ANY METHOD, AN[J ITS TRANSMITTAL TO A THIRD
PARTY, BY ANY MEANS, EXCEPT IN FULL, WITHOUT THE WRITTEN PERMISSION OF PROFESSIONAL SERVICE INDUSTRIES, IS PROHIBITED.
Professional Service Industries, Inc.. 1040.A Shelley Street. Springfield, OR 97477 . Phone 541r146-9649 . Fax 541r146-7163
l...~;z Information
,.,..,. .To Build On
Engineering. Consulting . Testing
DAILY FIELD REPORT
Date Performed:
January 26, 2009
Report Number:
722-90008-7
Client:
Ms, Lauretia Davies
Jerry's Home Improvement
PO. Box 2611
Eugene, Oregon 97402
ProjeGt Name:
Jerr)"s~Warehouse Renovation
Project Location:
2525 Olym piC Street
Springfield, Oregon
COM2008-01595
Clear
P.O. No.:
Contractor;
Type of Inspection:
Z4175LD
Chambers Construction
Reinforcing Steel
\Pe[ITlit t-!,o.:
Weather;
Field Observations and Comments
Performed visual inspection of reinforcing steel at the following locations: Loading Dock Footing. Reinforcing steel was
secured using tie wire and will be supported on concrete dobie blocks during placement of concrete. To the best of our
knowledge, the work inspected above was in accordance with the building department approved design drawings,
specifications, and applicable workmanship provisions of the International Building Code.
Inspector; Chris McDonald ICC#5298238.47
CCB# 176269
If you have any questions regarding this report, please feel free to contact us at 541-746-9649.
Respectfully Su
D~
David Smith
Branch Manager
c: City of Springfield
Chambers Construction - David Bakke
Robertson Sherwood Architects - Scott Stolarczyk
Metzler Engineering - Scott Metzler
ttted,
rvic~ tstries, Inc.
THIS REPORT IS PROVIDED FOR THE INFORMATION OF THE CLIENT ONL Y. THE REPRODUCTION OF THIS REPORT, BY ANY METHOD, AND ITS TRANSMITTAL TO A THIRD
PARTY, BY ANY MEANS, EXCEPT IN FULL, WITHOUT THE WRITTEN PERMISSION OF PROFESSIONAL SERVICE INDUSTRIES,'IS PROHIBITED.
Professional Service Industries, Inc. .1Q40-A Shelley Street. Springfield, OR 97477. Phone 541f746-9649. Fax 541f746-7163
l n~;lInformation
",~. .To Build On
Engineering . Consulting . Testing
c'5- O\SCi'::>
)
DAILY FIELD REPORT
Date Performed: January 27, 2009 Report Number: 722-90008-8
Client: IVls. Lauretta Davies Project Name: Jer~r's~WarehDUS€ Renovations
Jerry's Home Improvement
P.O Box 2611 Project Location: 2525 Olympic Street
Eugene, Oregon 97402
Springfield, Oregon
P.O. No.: Z4175LD Permit No.:
Contractor: Chambers Construction Weather: Overcast
Type of Inspection: Reinforced Concrete
Field Observations and Comments
Performed visual inspection during the placement of concrete for the Truck Ramp Footings. Concrete was placed by
truck and mechanically consolidated. Cas1 one (1) set of four (4) (4x8) concrete test cylinders. To the best of our
knowledge, the work inspected above was in accordance with the building department approved design drawings,
specifications, and applicable workmanship provisions of the International Building Code.
Tvoe of Material
Supplier
Mix#
Slump
Air Content
Ambient Temperature
Material Temperature
'Time Placed
Design Strength (psi)
Number of Samples
Total Yarda!je Placed
Inspector: Pete Furlong ACI#00083536
CCB# 176269
Set #1
Knife River
2430NE5200
51/2"
38'
48'
10:10AM
3000
4
18
If you have any questions regarding this report, please feel free to contact us at 541-746-9649.
Respectfully Subm ted,
~prOfeSSional 5e ice In
\ /-
vid Smith '
Branch Manager
c: City of Springfield
Chambers Construction - David Bakke
Robertson Sherwood Architects - Scott StoJarczyk
Metzler Engineering - Scott Metzler
ries, Inc.
THIS R~PORT IS PROVIDED FOR THE INFORMATION OF THE CLIENT ONL Y. THE REPRODUCTION OF THIS REPORT, BY ANY METHOD, AND ITS TRANSMITTAL TO A THIRD
p_IO",I""'" lleMJe_rrIO's';Il\\G, W1U>WJA _H'WSl_''ll/iIiA!jlr.r;:WM\ff4i'jil;V~h&w!j41'rriW9g,rif.Sfi,j,l'5'4'tfIljEf.l', 63
l"'~;lInformation
,.,~. .To Build On
Engineering . Consulting . Testing
DAiLY FiELD REPORT
Date Performed:
January 21, 2009
Ms. Lauretta Davies
Jerr)"s Home Improvemem
P.O. Box 2611
Eugene, Oregon 97402
Report Number:
722-90008-5
Client:
Project Location:
Jerr)"s-Warehouse Renovations
2525 Olympic Street
Springfield, Oregon
Project Name:
P.O. No.:
Type of Inspection:
Z4175LD
Epoxy/Welding
BP# COM2008-01595
Wealher:-
Inside
Field Observations and Comments
As requested a PSI representative was on-site to inspect the following: 1) Epoxy anchored bolts for the door opening at
gridline F at 7 (detail 2/S1). The 5/8" diamter all thread rods were 14" long and embedded a minimum of 5" vertically
into the lintel. Three all thread rods were installed using Hilti Hit HY 150 epoxy with an ICC# 5193. 2) Exposed
subgrade soils for the interior truck ramp. Exposed soils visually appeared to be native black and brown clay. Soil
probe penetrations ranged in depth from 3 to 4 inches indicating a relatively firm, stable subgrade at this time. Both
footing and slab subgrade soils were observed. Each area is scheduled to receive a minimum of 12" of imported
crushed rock. Rock will be tested after it has been compacted. 3) Single Pass welds for door frames at gridline F at 7
and E.5 at 9. Welds were inspected for size, length, profile and location. To the best of our knowledge, the work
inspected was in accordance with the building department approved design drawings, specifications and applicable
workmanship provisions of the AWS D1.1 Code.
Inspector: Raymond V. Aliperti ICC#1017075-85
CCB #176269
If you have any questions regarding this report, please feel free to contact us at 541-746-9649.
Respectfully Sub
Professional Se
Q1il\
Branch Manager
c: City of Springfield
Chambers Construction - David Bakke
Robertson Sherwood Architects - Scott Stolarczyk
Metzler Engineering - Scott Metzler
THIS REPORT IS PROVIDED FOR THE INFORMA nON OF THE CLIENT QNL Y. THE REPRODUCTION OF THIS REPORT, BY ANY METHOD, AND ITS TRANSMITTAL TO A THIRD
PARTY, BY ANY MEANS, EXCEPT IN FULL, WITHOUT THE WRITTEN PERMISSION OF PROFESSIONAL SERVICE INDUSTRIES;IIS PROHIBITED
Professional Service Industries, Inc.. 1Q40-A Shelley Street. Springfield, OR 97477. Phone 5411746.9649. Fax 5411746-7163
l"'~;l lriformation.
",~. .To Build On
Engineering. Consulting. Testing
DAiLY F~ELD REPORT
Date Performed:
Client:
January 12, 2009
Ms. Lauretta Davies
Jerry's Horns Improvement
P.O Box 2611
Eugene, Oregon 97402
Report Number:
722-90008-1
Project Name:
Jerrl"s-Warehouse Renovations
2525 Olympic Street
Springfield, Oregon
Proje~t Lo~ation:
P.O. No.:
Type of Inspection:
Z4175LD
Epoxy
BPI! COM200S-0159S
, Weather:
Inside
Field Observations and Comments
Performed continuous inspection during the installation of three (3) 518" diameter all thread epoxied anchor bolts in the
following locations: Existing east CMU wall on line 9 between C and D at door header. Prior to Installation the predrilled
holes were cleaned using a nylon brush and compressed air. Verified minimum embedment depth of 5 inches for the
5/8" and 6 3/3" for the 3/4". The above listed epoxy anchors were installed using Hiltl Hit HY 150. Contractor stated the
nuts would be tightened after epoxy has cured. To the best of our knowledge, the work inspected was In accordance
with the building department approved design drawings detail A~A, specifications and applicable workmanship
provisions of the International Building Code.
Inspector: Steve Wilder
eeB #176269
If you have any questions regarding this report, pi ease feel free to contact us at 541-746-9649.
,
Respectfully Su~tted,
1;:s"f ~~ ItQm.., I'"
David F. Smith
Branch Manager
c: City of Springfield
Chambers Construction - David Bakke
Robertson Sherwood Architects - Scott Stolarczyk
Metzler Engineering - Scott Metzler
THIS REPORT IS PROVIDED FOR THE INFORMATION OF THE CLIENT ONL Y. THE REPRODUCTION OF THIS REPORT, BY ANY METHOD. AND ITS TRANSMITTAL TO A THIRD
PARTY, BY ANY MEANS, EXCEPT IN FULL, WITHOUT THE WRITTEN PERMISSION OF PROFESSIONAL SERVICE INDUSTRIES, IS PROHIBITED.
Professional Service Industries.. Inc.. 1040-A Shelley Street. Springfield, OR 97477. Phone 541/746"9649. Fax 541/746-7163
l ra~;l Information
,.,..,. .To Build On
Engineering. Consulting. Testing
Dt--iL Y rlELD REPORT
Date Performed:
Client:
January 16, 2009
Ms. Lauretta Davies
Jerrj"s Homs Improvement
PO Box 2611
Eugene, Oregon 97402
Report Number:
722-90008-3
Project Name:
Jerr)"s-Warehouse Renovations
Project Location:
2525 Qiympic Street
Springfield, Oregon
P.O. No.:
Type of Inspection:
Z4175LD
Welding
BP# COM200S-01595
Weather:
Inside
Field Observations and Comments
Performed periodic visual inspection of the following items at Gibson Steel Fabrication Shop: two (2) loading dock
embed frames Welds were inspected for size, length, profile and location. To the best of our knowledge, the work
inspected was in accordance with the building department approved design drawings, specifications and applicable
workmanship provisions of the AWS 01.1 Code.
'Inspector: David F. Smith ICC#0877340-85
CCB #176269
If you have any questions regarding this report; please feel free to contact us at 541-746-9649.
Respectfully Submitted,
Professional Service Industries, Inc.
~Dav
. Raymond V. Aliperti
Project Manager
c: City of Springfield
Chambers Construction - David Bakke
Robertson Sherwood Architects - Scott Stolarczyk
Metzler Engineering - Scott Metzler