COMPRESSION REPORT
Project No.: 722-80173-159
Proj, Name: Thurston Elementary School
Location: 7345 Thurston Road
Springfield, Oregon
Placement Data:
2nd fioor deck griclline A to B at 5 to 8
Maierlitf:Concrete
Location Sampled At:
2nd floor cleek grid line C to 0 at 6 to 6.2
Dale Cast: 12/23/08 Date Rec'd: 12/24/08
Ti~~;~~~; IMi:0~;~200 Weather: Cloudy
Design Strength (psi):
Cylinder No.
08-3971
08-3972
08-3973
08-3974
required 4,000
Test Date
Field Cure
(days)
Lab Cure
(days)
Age (days)
12/30/2008
1/20/2008
1120/2008
l'lold
7
28
28
H
1
6
27
27
H
3 - Columnar
H 1 "'Cone. (b9lh ends) 2 - CaneNerlical Cracks (one end)
Remarks:'
c:
Yardage
4
10/100
Load:
Total:
Supplier:
Knife River
Compressive Strength Data ASTM C39
placed 4,000
Diameter or
Dimensions.
(inches)
Cross Sect. AreE
(5.1.)
Cylinder WT.
(Ibs.)
Max Load (Ibs) Compo Strength Fracture.Type"
. . (psi)
C1231.03
4,00
4,00
4,00
12,57
12,57
12,57
8,5
8,5
8,5
58,125
77,435
76,905
4 - Dfagonal w no cracking at ends
5 - Side frac ures (at top of bottom)
SPRINGFIELD OFFICE
1040 - A Shelley Street
Springfield, Oregon 97477
(541)746-9649 - (541)746-7163 fax
January 22, 2009 CCB#176269
Date:
B,P, No.:
P.O, No.:
Cast By:
P0272-334-0809
Glenn Meeks Jr
Field Test Data
4"
3/4"
35"
52"
4x8
-
Test Time
Capping Method
Slump (in.): ASTMC143
Max. Aggr. Size:
Air Content: ASTM C23t
Air Temperature (F):
Material Temp; (F): ASTM C1064
Max Temp (F):
;Min ~emp (F\:
Speci~en Size:
Unit Weight (pcf): ASTM C138
Time Cast: 9:00 AM Curing Conditions: ASTM
Additives:---Hot water, AEA 1% non chloride accelerator
Results Reported To: Contractor
KPFF - ugocosta@kpff,com
Hyland Construction - markb@jhconst.com
Milstead & Associates - angus@milstead,us
Mahlum - rberndl@mahlum,com
Robertson/Sherwood & Architects - dguadagni@robertsonsherwood,com
Springfield School District - jsaracen@sps,lane,edu
Yolanda Bird - yolanda,bird@sps,lane,edu
City of Springfield
4,620
6,150
6,120
C617."03
3
3
3
8:45 AM
12:58 PM
1:01 PM
x
x
X
6 - Top fractures (same as #5 bul end'of cylinder ,is pointed)
Respectfully Submitted; ,
7{;ssion{/{i.~es Industries, Inc,
Ray~ Aliperti ~
Project Manager
THIS REPORT IS PROVIDED FOR THE INFORMATiON OF THE CLIENT ONL Y. THE REPRODUCTION OF THIS REPORT BY ANY METHOD, AND ITS TRANSMITTAL TO A THIRD PARTY BY ANY MEANS EXCEPT IN FULL. IS PROHIBITED
WITHOUT THE WRITTEN
PERMISSION OF PROFESSIONAL SERVICE INDUSTRIES.
.\
/
!
r
. t ft!!~ ~-;J Info"!'fltion
.1I:!!!..'iiJJ!U.To BUild On
Iii!ng.. ,,:.. ~ . 1'Nttnsr
Client:
Address:
Sprin9field School District
525 Mill Street
Springfield, OR 97477
c;<2 - ~61
COMPRESSION REPORT
Project No.: 722-80173-168
Proj. Name: Thurston Elementary School
Location: 7345 Thurston Road
Springfield, Oregon
Placement Data: Material: Concrete
'8" trash enclosure walls in heights ranging from 11' to 9'
Location Sampled At:
8" trash enclosure walls to 4'Y2' in height
Oate Cast: 01/06/09 Oate Rec'd: 01/07109
Ticket No.: IMiX No.: Weather:
3352179 40N15200 Cloudy
Design Strength (psi):
Cylinder No.
09-0005
0ge0006
09-0007
09-0008
required 4,000
. Test Dale
Field Cure'
(days)
Lab Cure
(days)
Age (days)
,1/13/2009
2/3/2Q09
2/3/2009
Hold
7
28
28
H
- u-1 - Cone (both ends) 2 - ConelVerticai Cracks (one end)
Remarks:
c:
koad:
Slump (iu.): ASTM Cf43 '
Max. Aggr. Size:
Air Content: ASTM C231
A.ir Temperature (F):
Material Temp. (F): ASTM C1064
Max Temp (F):
Min Temp (F):
'Specimen Size:
Unit Weight (pef): ASTM C138
Time Cast: 8:50AM
Additives:
Results Reported To:
Contractor
Curing Conditions:
ASTM
Yardage
1
10/20
Total:
Supplier:
Knife River
_ Compressive Strength Data ASTM C39
olaced 4,000
Diameter or
Dimensions
(inches)
Cross Sect. Mea Cylinder WT.
(s.L) (Ibs.)
Max Load (Ibs I Compo Strength Fractu,e Type *0 Test Time
. .. (psi)
C1ZJ1-0J
6
27
27
H
4,00
1,57
8,6
58,050
4,620
SPRINGFIELD OFFICE
1040 - A Shelley Street
Springfield, Oregon 97477
(541)746-9649 - (541)746-7163 fax
January 22, 2009 CCB#1.76269
Date:
B.P. No,:
P.O. No.:
Cast By:
P0272-334-0809
Glenn Meeks Jr
3 - Collrmnar - 4 - Diagonal w no cracking at ends
. . '. ~,-~ -
5 - Side fra< ~ures (at top-of be ltom)
I\PFF - ugo,costa@kpff,com
Hyland Construction' - markb@jhconst.com
Milstead & Associates - angus@milstead,us
Mahlum - rbernclt@mahlum,com
Robertson/Sherwood & Architects - dguadagni@robertsonsherwood,com
Springfield School District - jsaracen@sps,lane,edu
Yolanda Bird - yolanda,bird@sps,lane,edu
City of Springfield
Field Test,Data
.4 3/4"
3/4"
3.4%
50"
5r
4x8
Capping Method
C617-0J
2
11:21 AM
x
6 - Top fractures (same as #5 but end of cylinder is pointed)
'Respectfully' Submitted,
!1;resSi~~rVi?eS Industries, Inc,
~lJ IJvI{\{j\J~ .
Raymond Aliperti
Project Manager
THIS REPORT IS PROVIDED FOR THE'INFORMATlON OF THE CLIENT ONL Y. THE REPRODUCTiON OF THIS REPORT BY ANY METHOD, AND ITS TRANSMITTAL TO A THIRD PARTY BY ANY MEANS EXCEPT IN FULL IS PROHIBITED
WITHOUT THE WRITTEN
PERMISSION OF PROFESSIONAL SERVICE INDUSTRIES.
, .-f'"
1.;fi...~.IInfoimation
II':!!..~~, .To Build On
1&1fI1n..ring . ~ . 1'lN:rUnfI
t15- Y31
COMPRESSION REPORT
Client:
Add res,;;:
Springfield School Dislrict
525 Mill'Street
Springfield, OR 97477
Project No.: 722-80173-162
Proj. Name: Thurston Elementary ,School
Location: 7345 Thurston Road
Springfield, Oregon
SPRINGFIELD OFFICE
1040 - A Shelley Street
Springfield, Oregon 97477
(541 )746-9649 - (541)746-7163 fax
January 27, 2009 CCB#176269
Date:
B,P, No.:
P.O. No,:
,c:;ast By:
P0271-255-0809
Glenn Meeks Jr
Load:
Total:
Supplier:
Knife River
Yardage
2
10/50
Slump (in,): ASTM C143
Max. Aggr. Size:
Air Coritent: AStMC231
Air Temperature (F):
Material Temp. (F): ASTM Cl064
Max Temp (F):
:Min Temp (f):
Specimen Size:
Unit Weight (pef): ASTM C138
Time Cast: 8:20 AM
Additives:
Results Reported To: .
Field TestData
3 3/4"
3/4"
Placement Data: . Materiai: Concrefe
Roof9ridline B to D at 1 to :) and roof gridline C to D at 5 to 6
50'
59'
Location Sampled At:
Roof gridline C to D at 4,5 to 5
Dale Cast: 12/29/09 Dale Rec'd: 12/30/09
Ticket No.: IMiX No.: Weather:
3352103 40N15200 Cloudy with Rain & Wind
4x8
Curing Conditions:
1 day Remainder F,e. ASTM
Contractor
~
Design Strength (psi):
required 4,000
'Compressive Strength Data ASTM C39
olaced 4,000
Cylinder No.
TestDale
Age (days)
Field Cure
(days)
Lab Cure
(days)
Diameter or
Dimensions
(inches)
Cross Sect.;Area
(s.i.)
Cylinder WT.
(tbs,)
Max. Load (Ibs.) Compo Strength Fracture Type'*'
(psi)
.T~~t Time
Capping Method
C617-03
C1231-03
08-4018 1/5/2009 7
08-4019 1/26/2009 28
08-4020 1/26/2009 28
08-4021 H H
Remarks:
f 6 4,00 12,57 8,5 50,835 4,040 3 9':20 AM
27 4,00 12,57 8,6 69,190 5;500 ' 2 4:43 PM
___n_
27 4,00 12,57 8,5 73,055 5,810 2 4:47PM
H
x
x
X
cc:
I<PFF - ugo,costa@kpff,com
Hyland Construction - markb@jhconst.com
Milstead & Associates - angus@milstead,us
Mahium - rberndt@mahlum,com
Robertson/Sherwood & Architects - dguadagni@robertsonsherwood,com
Springfield School District - jsaracen@sps.lane,edu
Yolanda Bird - yolanda,bird@sps,lane,edu
City of Springfield
Respectfully Submitted,
P77sSion,al'(j7jes Induslries, In!;,
f(tkJl V Cei)
Raymond Aliperti
Project Manager
TIllS REPORT IS PROVIDED FOR THE INFORMATION OF THE CLIENT ONL Y. THE REPRODUCTION OF THIS REPORT BY ANY METHOD, AND ITS TRANSMITTAL TO A THIRD PARTY BY ANY MEANS EXCEPT IN FULL, 1$
PROHIBITED WITHOUT THE WRITTEN
PERMISSION OF PROFESSIONAL SERVICE INDUSTRIES. .
l>>~j lfonf};:::J:~n
"'8 I., .II w.g. ~ . ]1, .".A.I.JJ
Client:
Address:
Springfield School District
.525 Mill Street
Springfield, OR 97477
t~-L\31
COMPRESSION REPORT
SPRINGFIELD OFFICE
1040 - A Shelley Street
Springfield, Oregon 97477
(541)746-9649 - (541)746-7163 fax
January 28; 2009 CCB#176269
Project No.: 722-80173-174
Proj. Name: Thurston Elementary School
Location: 7345 Thurslon Road
Springfield, Oregon
Date:
,B,P. No.:
P.O: No,:
Ca~t By:
P0272-334-0809
Pete Furlong
Slump (in,): ASTM C143
Max. Aggr. Size:
Air Content: ASTM C231
Air Temperature (F):
"Material Temp. (F): ASTMC1064
Max Temp (F):
Min Temp (F):
Specimen Size:
Unit Weight (pef): ASTM C138
Time Cast: 7:55 AM
Additives:
Results Reported To:
Field Test Data
51/2"
3/4"
3.4%
30"
61"
Placement Data: Malerial: Concrete
'Concrete floor slab, 'second floor at gridline E to H from 5 to 8; and stairway walls in areas 1
and 2,
,Locatio~ Sampled At:
concrete filar slab from gridline 6,5 to 5,5
Date Cast: 01109109 Date Rec'd: 01112109
Ticket No.: IMiX No.: Weather:
3160666 2440N15200 Clear
Design Strength (psi):
"
Cylinder No.
09-.0053
09-0054
09-0055
09-0056
reauired 4,000
Test Date
Age (days)
Field Cure
(days)
Lab Cure
(days)
1/1612009
2/6/2009
2/6/2009
Hold
7
28
28
H
H .1-~:;t-one-{boifi 'ellds) ."2 - Cor eNerlicaT Cra( !(s'(one end)
Remarks:
c:
, ,
3 - Columnar
Yardage
4x8
Load:
Total:
Supplier:
Knife River
Curing Conditions:
2 day field cure remainder ASTM
10
Contractor
Compressive Strength Data ASTM C39
olaced 4,000
"
Diameter or
Dimensions
(inches)
Cross Sect. Area Cylinder'WT.
(5,1.) (Ibs,)
Test Time
Capping Method
Camp: Strength
Max. Load (Ibs.) (psi) Fracture Type .,
C6t7-03
C1231-03
6
27
27
H
12,57
41,675
4,00
8,5
3,320
3
9:08 AM
x
4. - Diagonal w no cracking at ends
5 - Side frar:ures (at top of bottom) .6 - Top frae'lures (sam-e as#5but end of cylinder IS poinled)-
Respectfully Submitted,'
Pc. feSSjO~Q;ces Industries, lnG, '
Ray ond Aliperti
Project Manager
KPFF - ugo,costa@kpff,com
Hyland Construction - markb@jhconst.com
Milstead & Associates - angus@milstead,us
Mahlum - rberndt@mahlum,com .
Robertson/Sherwood & Architects - dguadagni@robertsonsherwood,com
Springfield School District - jsaracen@sps,lane,edu
Yolanda Bird ..yolanda,bird@sps,lane,edu
City of Springfield
mls REPORT IS PROVIDED FOR THE INFORMA nON OF T/-IE CLIENT ONL y, THE REPRODUCTION OF THIS REPORT BY ANY METHOD, AND ITS TRANSMITTAL:TO A THIRD PARTY BY ANY MEANS EXCEPT IN FULL, IS
PROHIBITED WITI-Iour T1-/E WRITTEN
PERMISSION OF PROFESSIONAL SERVICE INDUSTRIES.
I~!!j!lfont;;::;:~n
li!nfIlneerlnfl . ~ . n..tIng
'C~- 4~r7
COMPRESSION REPORT
Client:
Address:
Springfield School District
525 Mill Street
Springfield, OR 97477
Project No.: 722-80173-175
Proj. Name: Thurston Elementary School
Location: 7345 Thurston Road
Springfield, Oregon
Placement Data:
Roof at Areas 2 and 3 Mechanical Pads
-Mateifal: Concrete
Slump (in.): ASTM C143
Max. Aggr. Size:
Air Content: ASTM C231
Air Temperature (F):
Material Temp. (F): ASTM Cl064
Max Temp (F):
Min Temp (F):
Specimen Size:
Unit Weight (pcf): ASTM C138
Time Cast: 11 :53 AM
Additives:
Results Reported To:
Contractor
Location Sampled At:
Roof Area 2, southside
Oale Cast: 01/13/09
Ticket No.: IMiX No.:
3160746 2440N15200
Yardage
Load: 1
Total: 10
Supplier:
Knife River
Oate Rec'd: 01/14109
Weather:
Clear
Desig,n Strength (psi):
required 4,000
Compressive Strength Data ASTM C39
olaced 4,000
Cylinder No.
09-0122
09-0123
09-0124
09-0125
Lab Cure Diameter or Cross Sect. Area Cylinder WT. Compo Strength Capping Melhod
(days) Dimensions (s.i.) (Ibs") Max. load (lbs.) (psi) Fracture Type .. Test Time
(inches) C617-03 C1231-03
6 4,00 12,57 8,5 55,400 4,410 3 12:18 PM X
Test Date
Field Cure
(days)
Age (days)
1/20/2009
2/10/2009
'2/10/2009
Hold
7
28
28
H
27
27
H
3 - Co-iumnar' 4' - 'Olagonafw no crac'king at ends '5-~ Sic{e frae :ures (cit'top of bottom)
u 1" ~ Cone"(both ends) '-2 ~-C-or eNert"i"cal CrackS-(one en-dj
Remarks:
c:
I<PFF - ugo,costa@kpff,com
Hyiand Construction - markb@jhconst.com
Milstead & Associates - angus@milstead,us
Mahlum - rberndt@mahlum,com
Robertson/Sherwood & Architects - dguadagni@robertsonsherwood,com
Springfield School District - jsaracen@sps,lane,edu
Yolanda Bird - yolanda,bird@sps,lane,edu
City of Springfield
SPRINGFIELD OFFICE
1040 - A Shelley Street
Springfield, Oregon 97477
(541)746-9649 - (541)746-7163 fax
January 28, 2009 CCB#176269
Date:
B,P. No.:
P.Q, No.:
Cast By;
P0272-334-0809
Pete Furlong
Field Test Data
,51/2"
3/4"
3.4%
43"
62"
4x8
Curing Conditions:
ASTM
6 - Top fractures (same as#5 bul end 01 cylinder-fs-polnted)
Respectfully Submitted,
7ffes~D~/Ofices Industries, Inc
k~d AliPertl~
Project Manager
THIS REPORT IS PROVIDED FOR'THE INFOR"-IA TlON OF THE CLlENTONL Y. THE REPRODUCTION OF THIS REPORT BY ANY METHOD, AND ITS TRANSMITTAL TO A THIRD PARTY BY ANY MEANS EXCEPT IN FULL, IS
PROHIBITED WITHOUT THE WRITTEN
. PERMISSION OF PROFESSIONAL SERVICE JiVDUSTRIES.
Ip~!l!Onf;:::;:~n
1I!IIg,:'j. ~ 1~",;:JIfI. ~. a.tIng
Client:
Address:
Springfield School District
525 Mill Street
Springfield, OR 97477
CJl- Lf6l
COMPRESSION REPORT
Project No.: 722-80173"183
Proj, Name: Thurston Elementary School
Location:
PI~cement Data: Material: Concrete
Stage at gridline F,5 to E between 1,95 and 4,5; 4 steps in area 2,
location Sampled At:
east end of stage
Date Cast: 1/202009
'Ticket No.: IMiX No.:
3352493 2440N15200
-
Dale Rec'd: 01/21/09
Weather:
Fog
Desi9n Stren9th (psi): required 4,000
Cylinder No. Test Date Age (days) Field Cure lab Cure
(days) (days)
09-0217 1/27/2009 7 6
09-0218 2/"t 7/2009 28 27
09-0219 2/17/2009 28 27 I
09-0220 Hold H H I
. ,
H 1 - Cone (both ends) 2 - ConeNertical Cracks (one:end)
Remarks:
c:
-3 - Columnar
Yardage
load:
Total:
Supplier:
Knife River
1
10
7345 Thurston Road
Springfield, Oregon
Slump (in,): ASTM C143
Max. Aggr. Size:
Air Content: ASTM C231
Air Temperature (F):
M~terial Tem'p. (F): ASTM C1064
Max Temp (F):
Min Temp (F):
Specimen Size:
Unit Weight (pct): ASTM C138
Time Cast: 8:45 AM
Additives:
Results Reported To:
Compressive Strength Data ASTM C39
olaced 4,000
Diameter or
Dimensions
(inches)
Cross Sect. Area
(s.i.)
4,00
12,57
Cylinder WT.
(lbs.)
Max. Load (Ibs.)
Date:
B.P. No.:
P.O. No.:
Cast'By:
Fil~/d Test Data
6"
3/4"
310
620
4x8
Curing Conditions:
Contractor
Compo S~rength FraCture Type ..
(psi)
4,700
2
SPRINGFIELD OFFICE
1040 - A Shelley Street
Springfield, Oregon 97477
(541)746-9649 - (541)746-7163 fax
January 29, 2009 CCB#176269
P0272-334-0809
Pete Furlong
ASTM
Test Time
Capping Method
4 - Diagonal wIno cracking at ends
KPFF - ugo,costa@kpff,com
Hyland Construction - markb@jllconst.com
Milstead & Associates - angus@milstead,us
Mahlum - rberndt@mahlum,com
Robertson/Sherwood & Architects - dguadagni@robertsonsherwood,com
Springfield School District - jsaracen@sps,lane,edu '
Yolanda Bird - yolanda,bird@sps,lane.edu
City of Springfield
8,5
59,040
C617-03
C1231-QJ
1:30 PM
x
5 - Side fra( :ures (at lop of bottom) 6 - Top fractures (same as #5 but end 01 cylinder is pointed)
Respectfully Submitted,
<<:;~~/res Industries, Inc.
Raymond Aliperti
Project Manager
THIS REPORT IS PROVIDED FOR THE /NFOR^,fATlON OF THE CLIENT ONL Y. THE REPRODUCTION OF THIS REPORT BY ANY METHOD, AND ITS TRANSMITTAL TO A THIRD PARTY BY ANY MEANS EXCEPT IN FULL, 1$
PROHIB/TEDW/THour THE WRITTEN
PERMISSION OF PROFESSIONAL SERVICE INDUSTRIES.
lp.$: lforifj;:::l:~n
~~ - 'L{01
COMPRESSION REPORT
!ZngInG8'*. . ConsuftIng 0 T\L. "'.,1 J ,I
Client:
Address:
Springfield School District
525 Mill Street
Springfield, OR 97477
SPRINGFIELD OFFICE
1040 - A Shelley Street
Springfield, Oregon 97477
(541)746-9649 - (541)746-7163 fax
January 29, 2009 CCB#176269
Project No.: 722-80173-182 '
Proj. Name: Thurston Elementary School
Location: 7345 Thurston Road
Springfield, Oregon
Placement Data: Malerfal: Concrete
DP2 Type AUger Piers for covered play area al 9ridlines 11 and 12 at X, Y, and Z; 1 DP1
Auger Pier at service yard, 4 DP1 Type Auger Piers on 8 between 0.5 and G.5~
Location Sampled At:
Lines 11 at X for Play Area
Dale Cast: 01/19109 Date Rec'd: 01/20/09
Ticket No.: I Mix No.: Weather:
3352491 2440N15200 Clear
I Yardage
Load: 1
ITotal: 6,5
IsuPPlier:
Knife River
Date:
B.P. No,:
P,O. No,:
Cast By:,
P0272-334-0809
Dale Russell
Slump (in.): ASTM C'43
Max. AggL Size:
Air Content: ASTM C231,
Air Temperature (F):
Material_ Temp. (F): ASTM C1064
Max Temp IF):
Min Temp (F):
Specimen Size:
Unit Weight (pcf): ASTM C13B
Time Cast: 2:50 PM
Additives:
'Results Reported To:
Field Test Data
43/4"
3/4"
1.6%
42'
53'
76'
43',
4x8
Cl!ring Conditions:
ASTM
Contractor
Desi!jn Stren!jth (psi):
required 4,000
Compressive Strength Data ASTM C39
olaced 4.000
,
Cylinder No.
09-0213
09-0214
09-0215
09-0216
Test Date
Field Cure
~days)
Lab Cure Diameter or Cross Sect. Area Cylinder WT. Compo Strength Capping Method
.(~aysl Dimensions (5.1,) (Ibs,) Max. l~ad (lbs.) (psi) Fracture Type .. Test Time
(inches) C617-03 C1231-03
6 5,99 28,2,1 28.4 135,490 4,800 . 2 4:27 PM X
Age (days)
1/26/2009
2/16/2009
2/16/2009
Hold
~* 1 - Cone (both ends) 2 - ConeNertical Cracks "(one end) 3 - Columni:lr 4- - Diagonal w no cracking at ends
Remarks:
c;
7
28
28
H.
27,
27
H
5 - Side frac ures(at top of bC"Uom) 6 - Topfractures(same 8s#5 but-end at cylinde~ is,pointed)
"Respectfully Submitted, "'.~' .
k~JIJ~ces Industries, I!)c
Raymond Aliperti '
Project Manager
THIS REPORT IS PROVIDED FOR THE INFORMA T10N.oF THE CLIENT GNL Y. THE REPRODUCTION OF THIS REPORT BY ANY METHOD, AND ITS TRANSMITTAL TO A THIRD PARTY BY ANY MEANS EXCEPT IN FULL. IS
PROHIBITED WITHOUT THE WRITTEN
PERMISSION OF PROFESSIONAL SERVICE INDUSTRIES.
KPFF c ugo,costa@kpff,com
Hyland Construction '- markb@jhconst.com
Milstead & Associates - angus@milstead,us
Mahlum - rberndt@mahlum,com
Robertson/Sherwood & Architects c dguadagni@robertsonsherwDod,com
Springfield School District - jsaracen@sps,lane,edu
Yolanda Bird - yolanda,bird@sps,lane,edu
City of Springfield
lPsili::f%:::::~n
l/!!nglneering . c-..IfIng . 7[",,,,,,, ,J
Client:
Address:
Springfield School District
525 Mill Street
Springfield, OR 97477
t '6v L{31
COMPRESSION REPORT
Project No.: 722-80173-176
Proj. Name: Thurston Elementary School
location: 7345 Thurston Road
Springfield, Oregon
'Placement Data: Materj'a'l: Concrete
Skybridge from griclline D to F between 5 to 5,1; Stairs at area 2,from g"ridline F,2 to 6
between 5.5 to 6; and Stairs at area 3 from g~idline B to"B.7 between 5,5 and 6.
Location Sampled At:
Stairs at area 3
Date Cast:
Ticket No.:
3354005
1/162009
1~;:4~~;152n0
. c
Design Strength (psi):
Cylinder No..
09-0195
09-0196
09.0197
09-0198
Test Date
1/23/2009
2/13/2009
2/13/2009
Hold
Date Rec'd; 01/19/09
Weather:
Fo~
required 4,000
Age (days)
Field Cure
(days)
lab Cure
(days)
_koad~
Yardage
1
10
Slump (in,); ASTM C143
Max. Aggr. Size:
Air Content: ASTM C231
Air Temperature (F):
Material Temp, (F); ASTM C1064
Max Temp fFl;
Min Temp IF':
Specimen Size:
Unit Weight (pet): ASTM C138
Time Cast: 9:10AM
Additives:
Results Reported To:
, ,
Contractor
7
28
28
H
Total:
Supplier:
Knife River
Compressive Strength Data ASTM C39'
olaced 4,000
Diameter or
Dimensions'
(inChes)
Cross Sect. Area
(s.L)
Cyfinder WT.
Ilbs,)
SPRINGFIELD OFFICE
1040 - A Shelley Street
Springfield, Oregon 97477
(541)746-9649 - (541)746-716.3 fax
January 29, 2009 CCB#176269
Date:
B.P, No.:
P,O, No,:
Cast By:
P0272-334-0809
Pete Furlong
6
27
27
H
4,00
12,57
Field Te-stData
5"
3/4"
35'
60'
4x8
Curing Conditions:
ASTM
Max. Load (Ibs.)
Compo Strength Fracture Type *'
(psi)
C617,OJ
'C12J1-0J
8,5
49,690
... f~'Cone--(both ends) 2. ConeNertic'al 'c';'racks "(one end) 3'~ Columnar 4 - Diagon<31 w no cracking at ends
RemarKS: -
c: KPFf'- ugo,costa@kpff,com
Hyland Construction - markb@jhconsLcom
Milstead & Associates - angus@milstead,us
Mahlum - rberndt@mahlum,com
Robertson/Sherwood & Architects - dguada9ni@robertsonsherwood,com
Springfield School District - jsaracen@sps,lane,edu
Yolanda Bird - yolanda,bird@sps,lane,edu
City of Springfield
5 - Side frac_ures ("a~,top of but om)
Test Time'
Capping Method
3,950
3
12:35 PM
x
6-~ Top fr_ictures '(same as #S'bul en-d-ol ~Y(inderfsP~inled)
Respectfully Slibrriitted, ' ..
k!::;;J7W;fVices Industries, tnG,
Raymond.Aliperti
Project Manager
rHIS REPORT IS PROVIDED FOR THE INFORMA TlON OF THE CLIENT ONL Y. THE REPRODUCTION OF THIS REPORT BY ANY METHOD, AND ITS TRANSMITTAL TO A THIRD PARTY BY ANY MEANS EXCEPT IN FULL, IS
PROHIBITED WITHOUT THE WRITTEN
PERMISSION OF PROFESSIONAL SERVICE INDUS-TRIES.
C<iS- 461
l.. ~ ., Injonnation
",..,. .To Build On
Engineering . Consulting. Testing
DAILY FIELD REPORT
Date Performed:
January 9, 2009
Springfield School District
525 Mill Street
Springfield, OR 97477
Report Number:
722-80173-167
Client:
Project Name:
Thurston =Iementary School
Project Location:
7345 Thurston Road
Springfield, Oregon
Contractor:
Fabricator:
Type of Inspection:
John Hyland
Axis Crane
Welding
P.O. No:
Shop/ Field:
Weather:
P0272-334-0809
Field
Inside
Field Observations and Comments
Performed periodic visual inspection of the following items: Area #1
1), Roof Puddle welds and Seam welds are complete,
2), Lejune HSB connections are completed except for the following areas:
-1 st floor A to 0 from 5 to 5,3 some of the bolts are not snapped off
-2nd floor A,7 to 7.8 one bolt needs to'be snapped off,
3), Welded connections are completed except for the following areas:
-1st floor beam to beam at 0 to 5,2
-2nd floor beam to beam B to C from 7,8 to 8
Weldments were inspected for size, length, profile and locations, To the best of our knowledge, the work inspected is in
conformance with approved drawings, specifications,and applicable AWS 01,1 and AWS 01,3 codes, The following
items were in non-conformance: (see above), Contractor was asked to notify our office when additional services are
needed,
Inspector: Raymond Aliperti, Certification #1017075-86
eBB #176269
If you have any qu'estions regarding this report, please feel free to contact us at 541-746-9649,
Respectfully Submitted,
~s::JGf;.ce Industries, Inc,
Raymond Aliperti
Project Manager
c: KPFF - ugo,costa@kpff,com
Hyland Construction - markb@jhconst.com
Milstead & Associates - angus@milstead,us
Mahlum - rberndt@mahium,com ,
RobertsonlShervvood & Architects - dguadagni@robertsonshervvood,com
Springfield School District - jsaracen@sps,lane,edu
Yolanda Bird - yolanda,bird@sps,lane,edu
City of Springfield
THiS REPORT IS PROVIDED FOR THE: INFORMATION OF THE CLIENT ONL Y. THE REPRODUCTION OF THIS REPORT. BY ANY METHOD, AND ITS TRANSMITTAL TO A THIRD
PARTY f:lV AMY M~AN<:: FX:(;FPT IN FIlii WITf.fOIIT THF WRITTEN p;:r:U.AI",SION OF PROFESSIONAL SERVICE INDUSTRIES. IS PROHIBITED
Professional Service Industri~s, Inc.. 1040-A Shelley Street. Springfield, OR 97477. Phone 541046-9649. Fax 541n46-7163
l..~;lInformation
I"oiJI. .To Build On
Engineering . Consulting. Testing
Date Performed:
January 19, 2009
Springfield School District
, 525 Mill Street
Springfield, OR 97477
Client:
P,O, No.:
Type of Structure:
Type of Inspection:
P0272-334-0809
C}6 - L\:~O
DAiLY FiELD REPORT
Report Number:
722-80173-177
Project Name:
Thurston Elementary School
7345 Thurston Road
Springfield, Oregon
Project Location:
Weatner:
Clear
Reinforced Concrete
Field Observations and Comments
'Performed visual inspection of reinforcing steel at the following locations: 6 DP2 Type Augered Piers for covered play
area at gridlines 11 and 12 at X,Y,and i.; 1 DP1 Type Augered Pier at Service Yard; and 4 DP1 Type AUgered Piers on
gridline 8 at 0,5 and G,5, Reinforcing steel was checked for grade, size, placementand clearances where applicable,
Reinforcing steel was secured using tie wire and supported on concrete dobie blocks, Performed visual inspection
during placement of concrete in the locations listed above, Concrete was placed' by truck and mechanically
consolidated, Cast one (1) set of four (4) (6x12) concrete test cylinders. To the best of our knowledge, the work
Inspected was in accordance with the building deparment approved design drawings, specifications, and applicable
workmanship provisions of the International Building Code, Contractor was asked to notify our office when additional
services are needed,
Tvo" of Mat"riaj
Supplier
Mix#
Slump
Air Content
Ambient Temperature
Material Temperature
Time Placed
Design Strength (psi)
Number of Samples
Total Yardage Placed
Inspector: Steve Wilder/Dale Russell
CCB# 176269
Set #1
Knife River
2440N15200
43/4"
1,6%
42
53
2:50 PM
4,000
4
6,5
If you have any questions regarding this report, please feel free to contact us at 541-746-9649,
Respectfully Submitted,
prK;~;~Tv~e In~ustries, Inc,
Raymond V, AliP&
Project Manager
cc: KPFF - ugo.costa@kpff,com
Hyland Construction - markb@jhconst.com
Milstead & Associates - angus@milstead,us
Mahlum. rberndt@mahlum,com
Robertson/Sherwood & Architects - dguadagni@robertsonsherwood,com
Springfield School District - jsaracen@sps.lane,edu
Yolanda Bird - yolanda,bird@sps,lane,edu
City of Springfield
THIS REPORT IS PROVIDED FOR THE INFORII(IATlON OF THE CLIENT ONL Y. THE REPRODUCTION OF THIS REPORT, BY ANY METHOD, AND ITS TRANSMITTAL TO A THIRD
PARTY, BY ANY MEANS, EXCEPT IN FULL, WITHOUT THE WRITTEN PERMISSION OF PROFESSIONAL SERVICE INDUSTRIES, IS PROHIBITED.
Professional Service Industries, Inc.. 1040-A Shelley Street. Springfield, OR 97477. Phone 541(746-9649. Fax 541f746-7163
l...~ ;ZInfonnation
,.,~. .To Build On
Engineering . Consulting. Testing
C~ - Y3J7
DAILY FIELD REPORT
Date Performed: January 19, 2009 Report Number: 722-80173-178
Client: Springfield School District Project Name: Thurston Elementary School
525 Mill Street
Springfield, OR 97477 Project Location: 7345 Thurston Road
Springfield, Oregon
Building Permit No,: COM2008"OO437 P,O. No.: P0272-334-0809
Type of Inspection: Soils Observation Weather: Clear
Field Observations and Comments
As requested, a representative from PSI was on-site to observe augering for piers at the following locations: 4 piers on
east side of building for two staircases, 6 piers south of building for covered play area, Two foot embedment into the
underlying gravels was verified, See attached sketch for locations and depth of holes,
Inspector: Anthony J. Deluca
CCB #176269
If you have any questions regarding this report, please feel free to contact us at 541-746-9649,
Respectfully Submitted,
K:~n~~~~dustries, /nc,
Raymond Aliperti
Project Manager
c:
KPFF - ugo,costa@kpff,com
Hyland Construction - markb@jhconst.com
Milstead & Associates - angus@milstead,us
Mahlum" rberndt@mahlum,com
Robertson/Sherwood & Architects - dguadagni@robertsonsherwood,com
Springfield School District - jsaracen@sps,lane,edu
Yolanda Bird - yolanda,bird@sps.lane,edu:,
City of Springfield
Attachment: Site Plan
THIS REPORT IS PROVIDED FOR THE INFORMA nON OF THE CLIENT ONL Y THE REPRODUCTION OF THIS REPORT, Bl' ANY METHOD, AND ITS TRANSMITTAL TO A THIRD
PARTY, BY ANY MEANS, EXCEPT IN FULL, WITHOUT THE WRITTEN PERMISSION OF PROFESSIONAL SERVICE INDUSTRIES. IS PROHIBITED.
Professional Service Industries, Inc.. 1Q40-A Shelley Street. Springfield, OR 97477. Phone 541fi46-9649. Fax 541/746.7163.
l..~;lInformation
I"oWI1. .To Build On
Engineering . Consulting . Testing
,
C<3 - Lf37
DAiLY FIELD REPORT
Date Performed:
Client:
January 20, 2009
Springfield School District
525 Mill Street
Springfield, OR 97477
Report Number:
722-80173-174
Project Name:
Project Location:
Thurston Elementary School
7345 Thurston Road
Springfield, Oregon
P,O, No,:
Type of Structure:
Type of Inspection:
P0272-334-0809
Permit No,:
Weather:
COM2008-00437
F09
Reinforced Concrete
Field Observations and Comments
'Performed visual inspection during placement of concrete for the Stage at F,5 to E between 1,95 and 4,5; and 4 steps in
Area#2, Concrete was placed by pump and mechanically consolidated, Cast one (1) set of four (4) (4x8) concrete test
cylinders, To the best of our knowledge, the work inspected was in accordance with the building deparment approved
design drawings, specifications, and applicable workmanship provisions of the International Building Code, Contractor
was asked to notify our office when additional services are needed,
'[yo.. of Material
Supplier
Mix#
Slump
Air Content
Ambient Temperature
Material Temperature
Time Placed
Design Strength (psi)
Number of Samples
Total Yardage Placed
Inspector: Pete Furlong
CCB# 176269
Set #1
Knife River
2440N15200
6"
31
62
8:45 AM
4,000
4
16
If you have any questions regarding this report, please feel free to contact us at 541-746-9649,
Respectfully Submitted,
71essiona' Service Industries, Inc,
\~{\j. ~
Raymona V, Aliperti
Project Manager
cc: KPFF - ugo,costa@kpff,com
Hyiand Construction - markb@jhconst.com
Milstead & Associates - angus@milstead,us
Mahlum - rberndt@mahlum,com
Robertson/Sherwood & Architects - dguadagni@robertsonsherwood,com
Springfield School District - jsaracen@sps,lane,edu
Yolanda Bird - yolanda,bird@sps,lane,edu
City of Springfield
THIS REPORT IS PROVIDED FOR THE INFORMATION OF THE CLIENT ONL Y. THE REPRODUCTION OF THIS REPORT, BY ANY METHOD, ANf! ITS TRANSMITTAL TO A THIRD
PARTY, BY ANY MEANS, EXCEPT IN FULL, WITHOUT THE WRITTEN PERMISSION OF PROFESSIONAL SERVICE INDUSTRIES,IS P':'?QHIBITED.
Professional Service Industries, Inc.. 1040-A Shelley Street. Springfield, OR 97477 . Phone 541/746-9649 .'Fax 541/746-7163
t~ - LL~'l
l"~;lInfonnation
,.,..,. .To Build On
Engineering. Consulting. Testing
DAILY FIELD REPORT
Date Performed: January 7, 2009 Report Number: 722-80173-165
Client: Sprin;!field School District Project Name: Tnurston ",iementary School
525 Mill Street
Springfield, OR 97477 Project Location: 7345 Thurston Road
Springfield, Oregon
Building Permit No,: COM200S-00437 P,O, No,: P0272-33L:-OS09
Type of Inspection: Reinforcing Steel Weather: Cloudy
Field Observations and Comments
Performed visual inspection of reinforcing steel and nelson studs at the following iocations: Inspected the 2nd floor
reinforcing at gridline E to H at 5 to S, This area requires all trash including excess nelson studs and metal to be
removed, Also inspected the roof reinforcing at gridiine J to L at 5 to 6, Both areas require reinspection prior to
placement of concrete, Reinforcing steel was checked for grade, size, lap, placement and clearances where applicable,
Reinforcing steel was secured using tie wire and supported on concrete dobie blocks, Reinforcing was placed in
accordance with the latest revisions dated 5/1/08, Contractor was asked to notify our office when additional services are
needed,
Inspector: Glenn Meek Jr. ICC#5071538-49
CCB #176269
If you have any questions regarding this report, please feel free to contact us at 541-746-9649,
Respectfully Submitted,
rJ~essid~ Z~:C~dustries, Inc,
~AIi~
Project Manager
c: KPFF - ugo,costa@kpff,com
Hyland Construction - markb@jhconst.com
Milstead & Associates - angus@milstead,us
Mahlum - rberndt@mahlum,com
Robertson/Sherwood & Architects - dguadagni@robertsonsherwood,com
Springfield School District - jsaracen@sps.lane,edu
Yolanda Bird - yolanda,bird@sps.lane,edu
City of Springfield
THIS REPORT IS PROVIDED FOR THE INFORMATION OF THE CLIENT ONL Y. THE REPRODUCTION OF THIS REPORT, BY ANY METHOD, AND ITS TRANSMITTAL TO A THIRD
PARTY, BY ANY MEANS. EXCE?T IN FULL. WITHOUT THE WRITTEN PERMISSION OF PROFESS/DNA!. SEF1V1CE INDUSTRIES, 1$ pROHIBITED.
Professional Service Industries, Inc.. 1Q40-A Shelley Street. Springfield, OR 97477. Phone 541(746-9649. Fax 541(746-7163
c~ - y~,\
l..~;, Infonnation
"~.lTo Build On
Engineering. Consulting . Testing
DAILY FiELD REPORT
Date Performed:
January 16, 2009
Springfield School District
525 Mill Street
Springfield, OR 97477
Report Number:
722-80173-172
Client:
Project Name:
Thurston Elementary School
7345 Thurston Road
Springfield, Oregon
Project Location:
P.O, No.:
Type of Structure:
Type of Inspection:
P0272-334-0809
Permit No,:
Weather:
COM2008-00437
Foggy
Reinforced Concrete
Field Observations and Comments
I Performed visual inspection of reinforcing steel and embeds at the following 10cations:Performed visual inspection 01
reinforcing steel at the following locations: inspected the reinforcing at the stage slab gridline E to E,1 at to 4,8 Skybridge
D to E at 5 to 5,1, stair #2 F,2 to Gat 5,5 to 6 and stair #3 B to B,7 at 5,5 to 6, Reinforcing steel was checked for grade,
size, placement and clearances where applicable, Reinforcing steel was secured using tie wire and supported on
concrete dobie blocks, Reinforcing steel was placed in accordance with the latest revisions dated 5/1/08, Performed
visual inspection during placement of concrete in the locations listed above, Concrete was placed by boom pump and
mechanically consolidated, Cast one (1) set of four (4) (4x8) concrete test cylinders, Additional Comments: stage
slab not poured. Contractor was asked to notify our office when additional services are needed,
Tvop. of Mo:ttp.riill
Supplier
Mix#
Slump
Air Content
Ambient Temperature
Material Temperature
Time Placed
Design Strength (psi)
Number of Samples
Total Yardaqe Placed
Inspector: Glenn Meeks Jr, ICC #5071538-49
CCB# 176269
Set #1
Knife River
2440N15200
5"
35'
60'
9:10AM
4,000
4
30
If you have any questions regarding this report, please feel free to contact us at 541-746-9649,
Respectfully Submitted,
PR:F\JtfJjJfe Industries, Inc.
Raymond V, Aliperti
Project Manager
cc: KPFF - ugo,costa@kpff,com
Hyland Construction - markb@jhconst.com
Milstead & Associates - angus@milstead,us
Mahlum - rberndt@mahlum,com
Robertson/Sherwood & Architects - dguadagni@robertsonsherwood,com
Springfield School District - jsaracen@sps,lane,edu
Yolanda Bird - yolanda,bird@sps,lane,edu
City of Springfield
THIS REPORT IS PROVIDED FOR THE INFORMATION OF THE CLIENT ONL Y. THE REPRODUCTION OF THIS REPORT, BY ANY METHOD, AND ITS TRANSMITTAL TO A THIRD
PARTY, BY ANY MEANS, EXCEPT IN FULL, WITHOUT THE WRITTEN PERMISSION OF PROFESSIONAL SERVICE INDUSTRIES, IS PROHIBITED
Professional Service Industries, Inc.. 1040-A Shelley Street. Springfield, OR 97477. Phone 541n46-9649. Fax 541r146-7163
Reinforced Concrete
Field Observations and Comments
'Performed visual inspection during placement of concrete at the foliowing locations: roofs 2 and 3 Mechanical pads,
Concrete was placed by pump and mechanically consoidated, Cast one (1) set of four (4) (4x8) concrete test cylinders,
Additional Comments: fioor was cleaned of all trash and nelson studs prior to placement of concrete, Contractor was
asked to notify our office when additional services are needed, To the best of our knowledge, the work inspected above
was in accordance with the building department approved design drawings, specifications and applicable workmanship
provisions of the International Building Codes,
l}!OA of M"tA,i,,1
Supplier
Mix#
Slump
Air Content
Ambient Temperature
Material Temperature
Time Placed
Design Strength (psi)
Number of Samples
Total YardaQe Placed
Inspector: Pete Furlong, ICC#00083536
CCB# 176269
l....~;l Information
",..,. .To Build On
Engineering. Consulting . Testing
Date Performed:
Client:
January 13, 2009
Springfield School District
525 Mill Street
Springfield, OR 97477
P.Q, No.:
Type of Structure:
Type of Inspection:
P0272-334-0809
DAILY FiELD REPORT
Report Number:
722-80173-170
Project Name:
Thurston Elementary School
7345 Thurston Road
Springfield, Oregon
Project Location:
Permit No,:
Weather:
COM2008-00437
Clear
Set #1
Knife River
2440N 15200
51/2"
430
620
11:35AM
4,000
4
If you have any questions regarding this report, please feel free to contact us at 541-746-9649,
Respectfully Submitted, ,
t:JN~ice Industries, /nc,
Raymond V, Aliperti
Project Manager
cc: KPFF - ugo,costa@kpff,com
Hyland Construction - markb@jhconst.com
Milstead & Associates - angus@milstead,us
Mahlum - rberndt@mahlum,com
-Robertson/Sherwood & Architects - dguadagni@robertsonsherwood,com
Springfield School District - jsaracen@sps,lane,edu
Yolanda Bird - yolanda,bird@sps,lane,edu
City of Springfield
THIS REPORT IS PROVIDED FOR THE INFORMATION OF THE CLIENT ONL Y. THE REPRODUCTION OF THIS REPORT, BY ANY METHOD, AND ITS TRANSMITTAL TO A THIRD
PARTY, BY ANY MEANS, EXCEPT IN FULL, WITHOUT THE WRITTEN PERMISSION OF PROFESSIONAL SERVICE INDUSTRIES, 1$ PROHIBITED.
Professional Service Industries, tnc.. 1040-A Shelley Street. Springfield, OR 97477. Phone 541n46.9649. Fax 541n46-7163
t ~-401
l... ~., Infonnation
"'~.lTo Build On
Engineering . Consulting' Testing
DAILY FIELD REPORT
Date Performed: January 12, 2009 Report Number: 722-80173-169
Client: Springfield School District Project Name: Thurston Elementary School
525 Mill Street
SpringfIeld, OR 97477 Project Location: 7345 Thurston Road
Springfield, Oregon
Contractor: John Hyland P,O, No: P0272-334-0809
F ahricator: Axis Crane Shop/ Field: Field
Type of Inspection: Epoxy, Welding Weather: Inside
Field Observations and Comments
'On-site to inspect the following:
1), Re-inspection/final on seam welds and nelson studs for Area #2 Mechanical Roof E to F from 5 to 6; and Area #3
Mechanical Roof J to L from 5 to 6 (reference our previously submitted preliminary report from January 7, 2009,) Seam
welds and nelson studs have been completed and are in accordance with the project documents.
2), Re-inspection/Final inspection on epoxy dowels for concrete infill' at panel #38, Vertical bars were installed at 9" on
center with an average embedment's depth of 5" due to rebar, Epoxy dowels were installed using Hilti Hit RE500 SO
epoxy in accordance with the manufactures directions, (Reference our previously submitted report from December 31,
2008 report # 722-80173-161), Epoxy dowels at panel #38 are completed,
3), Area #2 roof seam welds and'puddle welds have been inspected and completed E to H from 5 to 8, To the best of
our knowledge, the work inspected above was in accordance with the building department approved design drawings,
specifications and applicable workmanship provisions of the International Buildinq Codes,
Inspector: Raymond Aliperti, Certification #1017075.86
CBB #176269
If you have any questions regarding this report, please feel free to contact us at 541-746-9649,
Respectfully Submitted,
k:J~~ce Industries, /nc,
Raymond Aliperti
Project Manager
c: KPFF - ugo,costa@kpff,com
Hyland Construction - markb@jhconstcom
Milstead & Associates - angus@milstead,us
Mahlum - rberndt@mahlum,com
Robertson/Sherwood & Architects - dguadagni@robertsonsherwood,com
Springfield School District - jsaracen@sps,lane,edu
Yolanda Bird - yoJanda,bird@sps,lane,edu
City of Springfield
THIS REPORT IS PROVIDED FOR THE INFORMATION OF THE CLIENT ONL Y. THE REPRODUCTION OF THIS REPORT, BY ANY METHOD, AND ITS TRANSMITTAL TO A THIRD
PARTY, BY ANYI>1EANS, EXCEPT IN FULL, WITHOUT,THE WRITTEN PERMISSION OF PROFESSIONAL SERVICE INDUSTRIES, IS PROHIBITED,
Professional Service Industries,./nc. - 1040-A Shelley Street- Springfield, OR 97477 - Phone 541/746--9649 -Fax 541/746-7163
l....~ ;ZInjormntion
I"-e3I1. .To Build On
Engineerlng . Consulting. Testing
Date Performed:
Client:
January 9, 2009
Springfield School District
525 Mill Street
Springfield, OR 97477
P,O, No,;
Type of Structure:
Type of Inspection;
P0272-334-0809
DAILY FIELD REPORT
Report Number;
722-80173-166
Project Name:
Thurston Elementary School
7345 Thurston Road
Springfield, Oregon
Project Location:
Permit No,:
Weather:
COM2008-00437
Clear
Reinforced Concrete
Field Observations and Comments
Reinforcing steel was previously inspected on 1/7/09, Performed visual inspection during placement of concrete at the
following locations: floor slab, 2nd fioor at gridline E to f:I between 5 and 8, Stairway walls in building 1 and 2, Concrete
was placed by pump, Cast one (1) set of four (4) (4x8) concrete test cylinders, Additional Comments: floor was cleaned
of all trash and nelson studs prior to placement of concrete, Contractor was asked to notify our office when additional
services are needed, To the best of our knowledge, the work inspected above was in accordance with the building
department approved design drawings, specifications and applicable workmanship provisions of the International
Building Codes,
Tvne of Materi::.1
Supplier
Mix#
Slump
Air Content
Ambient Temperature
Material Temperature
Time Placed
Design Strength (psi)
Number of Samples
Total Yardage Placed
Inspector: Pete Furlong, ICC#00083536
CCB# 176269
Set #1
Knife River
2440N 15200
51/2"
30"
61"
7:55 AM
4,000
4
115
If you have any questions regarding this report, please feel free to contact us at 541-746-9649,
Respectfully Submitted,
p~\) nv~c~ndustrjes, Inc,
Raymond V, ~
Project Manager
cc: KPFF - ugo,costa@kpff,com
Hyland Construction - markb@jhconst.com
Milstead & Associates - angus@milstead,us
Mahlum - rberndt@mahlum,com
Robertson/Sherwood & Architects - dguadagni@robertsonsherwood,com
Springfield School District - jsaracen@sps.lane,edu
Yolanda Bird - yolanda,bird@spslane,edu
City of Springfield
THIS REPORT 15 PROVIDED FOR THE INFORMA TION OF THE CLIENT ONL y, THE REPRODUCTION OF THIS REPORT, BY ANY METHOD, AND ITS TRANSMITTAL TO A THIRD
PARTY, BY ANY MEANS. EXCEPT IN FULL, WITHOUT THE WRITTEN PERMISSION OF PROFESSIONAL SERVICE INDUSTRIES. IS PRQ.'i/BITED.
Professional Service Industries, Inc.. 1040-A Shelley Street. Springfield, OR 97477. Phone 541/746-9649. Fax 541/746-7163
l... ~;z Infonnation
,.,~. .To Build On
Engineering. Consulting . Testing
DAILY FIELD REPORT
Date Performed:
Client:
January 6, 2009
Springfield School District
525 Mill Street
Springfield, OR 97477
P,Q. No,:
Type of Structure:
Type of Inspection:
P0272-334-0809
Report Number: '
722-80173-163
Project Name:
Thurston Elementary School
7345 Thurston Road
Springfield, Oregon
Project Location:
Permit No,:
Weather:
COM2008-00437
Cioudy
Reinforced Concrete
Field Observations and Comments
Performed visual inspection of reinforcing steel at the following locations: 8" trash enclosure wall reinforcing for
clearance prior to placement of concrete, Reinforcing steel was checked for grade, size, placement and clearances
where applicable, Reinforcing steel was secured using tie wire and supported on plastic chairs, Reinforcing steel was
placed in accordance with the latest revisions dated 5/1/08, Performed visual inspection during placement of concrete in
the locations listed above, Concrete was placed by boom pump and mechanically consolidated, Cast one (1) set of four
(4) (4x8) concrete test cylinders, Contractor was asked to notify our office when additional services are needed,
Tvoe of Ma~
Supplier
Mix#
Slump
Air Content
Ambient Temperature
Material Temperature
Time Placed
Design Strength (psi)
Number of Samples
Total Yardaqe Placed
Inspector: Glenn Meeks Jr, ICC #5071538-49
CCB# 176269
Set #1
Knife River
40NI15200
4 3/4"
3.4%
50'
57'
8:50 AM
4,000
4
20
If you have any questions regarding this report, please feel free t'2. contact us at 541-746-9649,
Respectfully Submitted,
p~JDa: ~ndUSfrieS' /nc,
Raymond V. Aliperti
Project Manager
cc: KPFF - ugo,costa@kpff,com
Hyland Construction'- markb@jhconst.com
Milstead & Associates - angus@milstead,us
Mahlum - rberndt@mahlum,com
Robertson/Sherwood & Architects - dguadagni@robertsonsherwood,com
Springfield School District - jsaracen@sps,lane,edu
Yolanda Bird - yolanda,bird@sps,lane,edu
City of Springfield
THIS REPORT 1$ PROVIDED FOR THE INFORMATION OF THE CLIENT ONL Y. THE REPRODUCTION OF THIS REPORT, BY ANY METHOD, AND ITS TRANSMITTAL TO A THIRD
PARTY, BY ANY MEANS. EXCEPT IN FULL. WITHOUT THE WRITTEN PERMISSION OF PROFESSIONAL SERVICE INDUSTRIES. IS PROHIBITED.
Professional Service Industries, Inc.. lQ40-A Shelley Street. Springfield, OR 97477 . Phone 5411746.9649 . Fax 541046-7163
l~- L\~1
l...~ ;ZInjormation
,.,~. .To Build On
Engineering . Consulting. Testing
DAILY FIELD REPORT
Date Performed:
Client:
January 7, 2009
Springfield School District
525 Mill Street
Springfield, OR 97477
Report Number:
722-80173-164
Project Name:
Thurston Elementary School
7345 Thurston Road
Springfield, Oregon
Project Location:
Contractor:
Fabricator:
Type of Inspection:
John Hyland
P.Q, No:
Shop! Field:
Weather:
P0272-334-0809
Field
Cloudy
Welding
Field Observations and Comments
Performed periodic visual inspection of the followin9 items: preliminary inspection on seam welds and nelson studs for
Area #2 Mechanical Roof E to F from 5 to 6 and Area #3 Mechanical Roof J to L from 5 to 6, 'Note: Areas were not yet
completed final inspection is required prior to placing concrete, Weldments were inspected for size, length, profile and
locations, To the best of our knowledge, the work inspected is in conformance with approved drawings, specifications
and applicable International BuildinQ Codes,
Inspector: Raymond Aliperti, Certification #1017075-86
CBB #176269
If you have any questions regarding this report, please feel free to contact us at 541-746-9649,
Respectfully Submitted,
'nofe~sional ~~TIiC~ Industries, /nc,
\\[J,iIJ. ~
Raymond Aliperti
Project Manager
c: KPFF - ugo,costa@kpff,com
Hyland Construction -, markb@jhconst.com
Milstead & Associates - angus@milstead,us
Mahlum - rberndt@mahlum,com
Robertson/Sherwood & Architects - dguadagni@robertsonsherwood,com
Springfield School District - jsaracen@sps.lane,edu
Yolanda Bird - yolanda,bird@sps.lane,edu
City of Springfield
THIS REPORT IS PROVIDED FOR THE INFORMA TION OF THE CLIENT ONL Y. THE REPRODUCTION OF THIS REPORT. BY ANY METHOD, AND ITS TRANSMITTAL TO A THIRD
n. q:l', BY "'MV UC^.,~ cvrco, I., r::,,, / 1"'"T/_InIIT Tric W~lrrcN PcRMI<::<::ION OF PROFc.C:;.<::lnNAI .<::;FRVICf INDUSTRIES. IS PROHIBITED.
Professional Service Industries, Inc,.. 104Q-A Shelley Street. Springfield, OR 97477 . Phone 5411746-9649 . Fax 541n 46-7163
l ~- 431
l "'~;lInformation
,.,..,. .To Build On
Engineering . Consultfng . Testing
DAILY FIELD REPORT
Date Performed:
January 14, 2009
Springfield School District
525 Mill Street
Springfield, OR 97477
Report Number:
722-80173-173
Client:
Project Name:
Thurston Elementary School
Project Location:
7345 Thurston Road
Springfield, Oregon
Contractor:
Fabricator:
Type of Inspection:
John Hyland
Axis Crane
Welding
P,O, No:
Shop/ Field:
Weather:
P0272-334-0809
Field
Inside
Field Observations and Comments
Performed periodic visual inspection of the following items: Area#1- Welds have been completed for Area #1 but the
high strength Lejune bolts have not yet been completed, Contractor will re-schedule that inspection at a later date,
Please note that the above listed welds complete a portion of the inspection deficiencies noted in our report dated
January 9, 2009 including: 1 st floor beam to beam at grid line D at 5.2 and 2nd floor beam to beam from grid line B to C
from 7,8 to 8, To the best of our knowledge, the work inspected above was in accordance with the building department
approved design drawings, specifications and applicable workmanship provisions of the International Building Codes
and AWS 01,1 codes,
'Inspector; Raymond Aliperti, Certification #1017075-86
CBB #176269
If you have any questions regarding this report, please feel free to contact us at 541-746-9649.
Respectfully Submitted,
jfeSS~~~ Service Industries, /nc,
~hdAIiP~
Project Manager
c: KPFF - ugo,costa@kpff,com
Hyland Construction - markb@jhconst.com
Milstead & Associates - angus@milstead,us
Mahlum - rberndt@mahlum,com
Robertson/Sherwood & Architects - dguadagni@robertsonsherwood,com
Springfield School District - jsaracen@sps,lane,edu
Yolanda Bird - yolanda,bird@sps,lane,edu
City of Springfield
THIS REPORT IS PROVIDED FOR THE INFORMATION OF THE CLIENT ONL y, THE REPRODUCTION OF THIS REPORT, BY ANY METHOD, AND ITS TRANSMITTAL TO A THIRD
PARTY, BY ANY MEANS, EXCEPT IN FULL. WITHOUT THE WRITTEN PERMISSION OF PROFESSIONAL SERVICE INDUSTRIES, IS PROHIBITED.
Professional Service Industries, In~.. 1Q40.A Shelley Street. Springfield, OR 97477. Phone 541f746-9S49 . Fax 541f746.7163
l '"~;lInformation
,.,~. .To Build On
Engineering. Consulting . Testing
DAILY FIELD REPORT
Date Performed:
Client:
January 26, 2009
Springfield School District
, 525 Mill Street
Springfieid,"OR 97477
Report Number:
722-80173-184
Project Name:
Thurston Elementary School
7345 Thurston Road
Springfield, Oregon
Project Location:
P,O, No.:
Type of Structure:
Type of Inspection:
P0272-334-0809
Permit No,:
Weather:
COM2008-00437
'Clear
Reinforced Concrete
Field Observations and Comments
'Performed visual inspection of reinforcing steel at the following locations: Footings for covered play ground, Reinforcing
steel was checked for grade, size, placement and clearances where applicabie, Reinforcing steel was secured using tie
wire and supported on concrete dobie blocks, Performed visual inspection during placement of concrete in the
locations listed above, Concrete was placed by truck and mechanically consolidated, Cast one (1) set of four (4) (4x8)
laboratory cured concrete test cylinders and one (1) set of four (4) (4x8) field cured concrete test cylinders, To the best
of our knowledge, the work"inspected was In accordance with the building deparment approved design drawings,
specifications, and applicable workmanship provisions of the International Building Code, Contractor was asked to notify
our office when additional services are needed, Contractor to place insulating blankets due to expected cold weather,
Tvoe of Material c_
Supplier
Mix#
Slump
Air Content
Ambient Temperature
Material Temperature
Time Placed
Design Strength (psi)
Number of Samples
Total Yardage Placed
Inspector: Chric McDonald ICC# 5298238-47
CCB# 176269
Set #1 , Set #2
Knife 'River Knife River
2440N15200 2440N15200
5"
1,7%
46
53
3:00 PM
4,000
4
30
5"
1,7%
46
53
3:00 PM
4,000
4 (F,C,)
30
If you have any questions regarding this report, please feel free to contact us at 541-746-9649,
Respectfully Submitted,
t::Da/~ Industries, Inc,
Raymond V, Alipertl
Project Manager
cC:, KPFF - ugo,costa@kpff,com
Hyland Construction - markb@jhconst.com
Milstead & Associates - angus@milstead,us
Mahlum - rberndt@mahlum,com
Robertson/Sherwood & Architects - dguadagni@robertsonsherwood,com
Springfield School District - jsaracen@sps,lane,edu
Yolanda Bird - yolandabird@sps,lane,edu
City of Springfield
THIS REPORT IS PROVIDED FOR THE INFORMATION OF THE CLIENT ONL Y. THE REPRODUCTION OF THIS REPORT, BY ANY METHOD, AND ITS TRANSMITTAL TO A THIRD
PARTY, BY ANY MEANS, EXCEPT IN FULL, WITHOUT THE WRITTEN PERMISSION OF PROFESSIONAL SERVICE INDUSTRIES, IS PROHIBITED.
Professional Service Industries, Inc.. 1040-A Shelley Street. Springfield, OR 97477. Phone 541((46-9649. Fax 541((46-7163