HomeMy WebLinkAboutPermit Field Test & Inspection Report 2009-1-21
~"''''I
~~tt
11~'IlIlltI;"I~'I.':n.IIIH.IN.
CLIENT
EWEB
500E, 4th Ave,
Eugene, Oregon
DATE CAST
STRENGTH REQUIRED
STRENGTH PLACED
PRODUCT CODE
ADDITIVES
LOAD NO.
CONCRETE TEMP
AIR TEMP
POUR LOCATION
LOAD 1 SAMPLED
TEST
DATE
01,21,09
02,11-09
02,11,09
Hold
AGE
(DAYS)
7
28
28
"1 - End Cones
Geotechnical & Construction Servires
Compressive Strength of Concrete
, (ASTM C 39)
PROJECT
01,21,09
2087168
6177
ATE
ROJECT NO,
REPORT NO.
. B,P. NO. 2008,00225
"...
01,14,09 CAST BY A, Fenstermacher DATE RECEIVED 01,15,09
4000 psi SPECIMEN SIZE 4" x 8"
4000 psi SACKS SUPPLIER Knife River
40,SE7 CEMENT MAX SIZE AGG, 3/4"
Super; Eclipse; AEA AIR CONTENT 5,3%
1 TICKET NO. 3160789 SLUMP 7"
590 F YARDAGE 9,0 OF 18,0 TIME 1:00 PM
420 F WEATHER Fog SPECIMEN STORAGE ASTM C31
Elevated slabs above East side of wall number 30 and above wall 24; east and west side wails above
wall number 25,
Set3
From slabs:
AREA
(IN')
12,50
TOTAL
LOAD (LBS)
51600
COMPRESSIVE
STRENGTH (PSIl
4130
AVERAGE
STRENGTH
(PSI)
TIME OF
TEST
10:50 AM
TYPE OF
FRACTUREH
4
WEIGHT
(LBS)
8,2
2 - Cone/Split
4 - Diagonal
5 - Side (top and bottom)
6 - Side (top or bottom)
3 - Columnar
REMARKS: Jake Stucky (Wildish) and Mike Stickling (EWES) was advised of on,site test results,
Reviewed Sy:
A,~~--
Michael L. ~eye,tJ
Technical Manager
c:
EWES, Mike Stickling (email)
EWES, Wally McCullough (email)
OBEC, Pete Slocum (email)
Wildish Building Co,, Kevin Fitzjarrell (email)
Wild ish Building Co" Jake Stucky (email)
City of Springfield
Knife River
MLM:sc
This report and/or enclosed test data is the confidential property of the client to whom it is addressed and pertains to the specific
process and/or material evaluated. As such, information contained herein shall not be reproduced in part or full and/or any part
thereof be disclosed without FEI Testing & Inspection, lnc.'s written authorization.
7'3,) MN ComeIIAvenue' a:.vanis, O'egon 97330, phrne(541) 757-4698, fax (541) 757-2991
29540 BAirpatRoad' Eugene, O'egon 97402 'phone(541)684J849' fax (541) 684J851
630'3,) Corporate Place, Suite 2 ' Bend, Oregon 97701 'phone (541) 382-4844 ' fax (541) 382-4846
~Ftl
Geoted1nica1 & Construction Servires
Compressive Strength of Concrete
(ASTM C 39)
11~'llilll;.I~\~':Il;'.IIIJ~.I~I.
CLIENT
EWEB
500E, 4th Ave,
Eugene, Oregon
PROJECT
Hayden Bridge Water
Filtration Plant Expansion
Springfield, Oregon
DATE
PROJECT NO.
REPORT NO.
01,21,09
2087168
6176
B.P. NO.
2008,00225
DATE CAST 01,14,09 CAST BY A. Fenstermacher DATE RECEIVED 01,15,09
STRENGTH REQUIRED 3000 psi ' SPECIMEN SIZE 4" x8"
STRENGTH PLACED 3000 psi SACKS SUPPLIER Knife River
PRODUCT CODE 30,1K CEMENT MAX SIZE AGG, 3/4"
ADDITIVES AEA; Hot water; Fibers AIR CONTENT 6,1%
LOAD NO. 8 TICKET NO. 3160787 SLUMP 6"
CONCRETE TEMP 620 F YARDAGE 10,00 OF 88,0 TIME 12:15 PM
AIR TEMP 430 F WEATHER Fog SPECIMEN STORAGE ASTM C31
POUR LOCATION Coagulant building slab on grade,
Set2
LOAD 8 SAMPLED Near northwest comer of slab,
TEST
DATE
01,21,09
02,11,09
02,11,09
Hold
AGE
(DAYS)
7
28
28
AREA
(IN')
12,50
WEIGHT
{LBSI
8,1
TOTAL
LOAD (LBS)
33600
COMPRESSIVE
STRENGTH (PSI!
2690
AVERAGE
STRENGTH
(PSI!
TIME OF
TEST
10:45 AM
TYPE OF
FRACTURE-
5
**1 - End Cones 2 - Cone/Split
3 - Columnar
4 - Diagonal
5 - Side (top and bottom)
6 - Side (top or bottom)
REMARKS: Jake Stucky (Wildish) and Mike Stickling (EWEB) was advised of on,site test results,
Reviewed By:
fJJ.x,~
Michael L, Mey!l
Technical Manager
c:
EWEB, Mike Stickling (email)
EWEB, Wally McCullough (email)
OBEC, Pete Slocum (email)
Wildish Building Co,, Kevin Fitzjarrell (email)
Wildish Building Co,, Jake Stucky (email)
City of Springfield
Knife River
MLM:sc
This report and/or enclosed test data is the confidential property of the client to whom it is addressed and pertains to the specific
process andler malerial evaluated. As such, information contained herein shall not be reproduced in part or full and/or any part
thereof be disclosed without FE1 Testing & Inspection, Inc.'s written authorization.
7fJJ t-NV ComeIIAvenue' CavaJIis, O'egxl 97330, ptme(541) 757-4698' fax (541) 757-2991
29540 BAirpcxt Road ' Eugene, 0'egxl97402' ptme (541) 684-3849 'fax(541)684-3851
630fJJ Corporate Place, Suite 2 ' Bend, Oregon 97701 'phone (541) 382-4844 ,fax (541) 382-4846
~fEI
11~'llflrr;"I~"'~I'IIII~.IH.
CLIENT
EWEB
500E, 4th Ave,
Eugene, Oregon
DATE CAST
STRENGTH REQUIRED
STRENGTH PLACED
PRDDUCT CODE
ADDITIVES
LOAD NO,
CONCRETE T.EMP
AIR TEMP
POUR LOCATION
LOAD 3 SAMPLED
TEST
DATE
01,21,09
02,11,09
02,11,09
'Hold
AGE
(DAYS)
7
28
28
Gcv~'''lica1 & Constn.xfun Services
Compressive Strength of Concrete
(ASTM C 39)
PROJECT
Hayden Bridge Water
Filtration Plant Expansion
Springfield, Oregon
DATE
PROJECT NO,
REPORT NO.
B.P. NO, ',. 2008,00225
01,14,09 CAST BY
3000 psi
3000 psi SACKS
30,1K CEMENT
AEA; Hot water; Fibers
3 TICKET NO.
640F YARDAGE
390 F WEATHER
Coagulant building slab on grade,
Set 1
From. thickened edge near northwest comer.
DATE RECEIVED
SPECIMEN SIZE .
SUPPLIER
MAX SIZE AGG,
AIR CONTENT
SLUMP
TIME
SPECIMEN STORAGE
A, Fenstermacher
3160782
10,0 OF 88,0
Fog
AREA
(IN.')
12,50
WEIGHT
lLBS\
8,0
COMPRESSIVE
STRENGTH (PSIl
2760
AVERAGE
STRENGTH
lPSIl
TIME OF
TEST
10:40 AM
TOTAL
LOAD lLBS)
34500 I
I
I
I
3 - Columnar
4 - Diagonal
5 - Side (lop and bottom)
6 - Side (top or bottom)
REMARKS: Jake Stucky (Wildish) and Mike Stickling (EWEB) was advised of on,site test results,
H1 _ End Cones 2 - Cone/Split
Reviewed By:
fJ;. ';(. ~
Michael L. MeJ'
Technical Manager
c:
EWEB, Mike Stickling (email)
EWEB, Wally McCullough (email)
OBEC, Pete Slocum (email)
Wildish Building Co,, Kevin Fitzjarrell (email)
Wildish Building Co,, Jake Stucky (email)
City qf Springfield
Knife 'River
MLM:sc
01,21,09
2087168
6175
01,15,09
4" x 8"
Knife River
3/4"
7,3%
6"
1 0:30 AM
ASTM C31
TYPE OF
FRACTURE'.
5
REC(/VED
JAN 2 8 2008
This report and/or enclosed test data is the confidential property of the client to whom it is addressed and pertains to the specific
process and/or material evaluated. As such, information contained herein shall not be reproduced in part or full and/or any part
thereof be disclosed without FEI Testing & Inspection, lnc.'s written authorization.
7fil tw CaneIIAvenue' CavaDis, CIreg:x197330' Jtlone(541) 757-4698, fax (541) 757-2991
29540 BAirpatRoad 'Eugene, <Jrei:pl97402' phone (541) 684-3849 , fax (541 )68<h3851
63050 Corporate Place, Suite 2 ' Bend, Oregon 97701 'phone (541) 382-4844 ' fax (541) 3824846
~r"~ :
~, . ....".
Page 1 of 1
11~'lmct;"I~~'~I'IIII~_
Geotechnical & Construction Services
Daily Field Report
Client:
EWEB
500E, 4th Ave,
Eugene, Oregon
Project:
Hayden Bridge Water Filtration
Plant Expansion
Springfield, Oregon
Date:
Project No.:
Report No.:
Inspector:
10 No.:
01,20-09
2087168
E"22238
A, Fenstermacher
5258882-49
ICC
Inspection of: Reinforcing Steel
Contractor: Wildish Building, Co,
Weather:_Clear
BP-No.: 2008-00225
Continuous Inspection: 0
Periodic Inspection: 0
Performed preliminary inspection on the reinforcing steel for elevated walkway above
wall 22, east and west walls of raw water channel above wall 26 and coagulant building
alum tank pedestals,' Reinforcing steel was checked for size, grade, laps, quantities,
locations, ties, clearance and supports, A final inspection will be performed prior to
concrete placement. '
Brady (Wildish) was asked to notify our office when additional services are needed,
To the best of our knowledge, the work inspected was in accordance with plans dated
02/2008 and applicable workmanship provisions of the I.B,C" except if noted above,
Reviewed By:
f}; .'i.~
Michael L. Me(.lr
Technical Manager
c:
EWEB- Mike Stickling (email)
EWEB- Wally McCullough (em ail)
OBEC- Pete Slocum (email)
Wildish Building Co,- Kevin Fitzjarrell (email)
Wildish Building Co,- Jake Stucky (email)
City of Springfield
Irf'
C f'/I/
J4J!1 ~ "to
, (j //1
.d(l8
MLM:sc
This report and/or enclosed test data is the confidential property of the client to wftom it is addressed and pertains to the specific
process and/or material evaluated. As such, information contained herein shall not be reproduced in part or full and/or any part
thereof be disclosed without FEI Testing & Inspection, Inc.'s written authorization.
7ffJ NN Cornell Avenue 'Cavalfis, Qegon 97330, phrne(541) 757-4698 'fax(541) 757-2991
29540 BI'IiIportRoad' Eugene, Qegon 97402, phme (541)684J849 , fax(541)~1
63050 Corporate Place, Suite 2 ' Bend, Oregon 97701 'phone (541) 382-4844 ' fax (541) 382-4846
- ~-.,----..,...~~'- - .--
-~.~-
i. 'I,
'I"
I ::,,_. .'., ,'1
.,-.."'->- ~~.
SfEJ
Page 1 of 1
11~'llm..;4JI~~':i;..lIlml.'h'l.
Geotechnical & Construction Services
Daily Field Report ,
Client:
EWEB
500E. 4th Ave,
Eugene, Oregon
Project:
Hayden BridgeWater Filtration
Plant Expansion
Springfield, Oregon
Date:
Project No.:
Report No.:
Inspector:
10 No.:
01-09-09
2087168
E-22151
A. Fenstermacher
5258882-49
ICC
Inspection of: Reinforcing Steel
Contractor: Wildish Building Co,
Weather: Overcast
, " ....,' - ,'. "'''''''-''-.-.' ....
'BPNo.: . , ,2008'00225
c-'-~> ....',
,
Continuous Inspection: 0
Periodic Inspection: 0
Performed preliminary inspection on the reinforcing steel 'for elevated slab above 'east
side of wall #30; east side of wall above #25; elevated slab above #24, Reinforcing
steel was checked for grade, size, laps, quantities, locations, ties, clearance and
supports, A final inspection will be performed prior to concrete placement.
Jake Stucky (Wildish) was asked to notify our office when additional services are
needed,
To the best of our knowledge, the work inspected was in accordance with plans dated
02/2008 and applicable workmanship provisions of the I.B,C" except if noted above,
Reviewed By:
A .'-;(.~
Michael L. Meyer
Technical Manager
c:
EWEB- Mike Stickling (email)
EWEB- Wally McCullough (email)
OBEC- Pete Slocum (ema!l)
Wildish Building Co.- Kevin Fitzjarrell (email) ,
Wi/dish Building Co,, Jake Stucky (em ail)
City of Springfield
r
MLM:sc
This report a'nd/or enclosed test data is the confidential property of ~he client to whom it is addressed and pertains to the specific
process and/or material evaluated. As such; information contained herein shall not be reproduced in part or full and/or any part
thereof be disclosed withOut FEI Testing & Inspection, tnc.'s written authorization. .
750 NN ComeII Avenue' CavaIIis, Oregon 97330, phone (541) 757-4698, fax (541) 757,2991
29540 BAirportRoad 'Eugene, Oregon 97402 'phone(541)684J849' fax (541)684-3851
63050 Corporate Place,Suite 2 ' Bend, Oregon 97701 'phone (541) 382-4844 ' fax (541) 382-4846
R~C
./4;/1 ~I '" ~
./ (J ()
./6'0'0'
~ftl
Page 1 of 1
11~'llflrt;"li~'~a..I(III.I~l.
Geolect1rOCaI & O:lnstrucfun Servires
Daily Field Report ,
Client:
EWEB
500E, 41h Ave.
Eugene, Oregon
Project:
Hayden Bridge Water Filtration
Plant Expansion
Springfield, Oregon
Date:
Project No.:
Report No.:
Inspector:
ID No.:
01-22-09
2087168
E-22255
A. Fenstermacher
5258882-49
ICC
Inspection of: Reinforced Concrete
Contractor: Wildish Building, Co,
Weather:, Overcast
BP No.:' 2008'00225
Continuous Inspection: 0
Periodic Inspection: Ii"!
Performed final inspection on the reinforcing steel for elevated walkway above wall 22,
east and west walls of raw water channel above wall 26, A preliminary inspection was
performed on 01-20-09 (reference FEI report E22238), Also, performed inspection on
the reinforcing steel for west wall of raw channel above wall 30, Reinforcing steel was
checked for grade, size, laps, quantities, locations, ties, clearance and supports,
Observed the placement of 20 yards of Knife River 4000 psi concrete (mix 40-SE7) into
areas noted above, Concrete was placed by pump and was mechanically
consolidated, Cast one (1) set of four (4) 4" x 8" compressive strength cylinders,
Notified Jake Stucky (Wildish) of on-site results, Concrete temperature- 65F; air
temperature- 42F; slump- 6"; air content- 3,8%,
Mr. Stucky was asked to notify our office when additional seniices are needed,
To the best of our knowledge, the work inspected was in accordance with plans dated
02/2008 and applicable workmanship provisions of the I.B,C" except if noted above.
Reviewed By:
jJl.'i,~
Michael L.'MeVer
.Technical Manager
c:
EWEB- Mike Stickling (email)
EWEB- Wally McCullough (em ail)
OBEC- Pete Slocum (email)
Wildish Building Co,- Kevin Fitzjarrell (email)
Wildish Building Co,- Jake Stucky (email)
City of Springfield
MLM:sc
This report and/or enclosed test data is the confidential property of the client to whom it is addressed and pertains to the specific
process and/or material evaluated. As such, information contained herein shall not be reproduced in part or full andlor any part
thereof be disclosed without FEI Testing & Inspection, Inc,'s written authorization.
7fIJ NN CaneII Avenue' CavaIIis, Oegoo 97330, p'lme(541) 757-4698, fax (541) 757,2991
29540 BAirpatRoad 'Eugene, Oegoo 97402, phme(541)lJ84.3849' fax (541 )684J851
630fIJ Corporate Place, Suite 2 ' Bend, Oregon 97701 'phone (541) 382-4844 ' fax (541) 382-4846
~""'I
~yrt
11.'llflrt;.I~Il'~~'IIIJ~.I~l.
CLIENT
EWEB
500E, 4th Ave,
Eugene, Oregon
DATE CAST
STRENGTH REQUIRED
STRENGTH PLACED
PRODUCT CODE
ADDITIVES
LOAD NO.
CONCRETE TEMP
AIR TEMP
POUR LOCATION
LOAD 2 SAMPLED
TEST
DATE
01,23,09
02-13,09
02,13,09
Hold
AGE
(DAYSl
7
28
28
Geotechnical & Construction Servia3s
PROJECT
Compressive Strength of Concrete
(ASTM C 39)
Hayden Bridge Water
Filtration Plant Expansion
Springfield, Oregon
. ,_:~ :;',~ '...
B,P:NO: ' 2008,00225
01,16,09 , CAST BY
4000 psi
4000 psi SACKS
40,SE7 CEMENT
AEA; Super; Eclipse; Hot water
2 TICKET NO.
620F YARDAGE
380 F WEATHER
Wall number 20,
From 2nd lift,
AREA
(IN,')
12,62
WEIGHT
(LBSl
8.4.
TOTAL
LOAD (LBS)
47000
**1 - End Cones 2'- Cone/Split
3 - Columnar
REMARKS: Jake Stucky was,advised of on, site test results,
Reviewed By:
)11. '7f.~
Michael L. Meyer
Technical Manager
c:
EWEB, Mike Stickling (email)
EWEB, Wally McCullough(email)
OBEC, Pete Slocum (email)
Wildish Building Co,, Kevin Fitzjarrell (email)
Wildish Building Co,, Jake Stucky (email)
City of Springfield
Knife River
MLM:sc
A, Fenstermacher
3354009
10,0 OF 28,0
Fog
COMPRESStVE
STRENGTH (PSn
3720
DATE
PROJECT NO.
REPORT NO.
DATE RECEIVED
SPECIMEN SIZE
SUPPLIER
MAX SIZE AGG,
AIR CONTENT
SLUMP
TIME
SPECIMEN STORAGE
AVERAGE
STRENGTH
(PSn
TIME OF
TEST
8:15AM
01,23,09
2087168
6178
01,17,09
4" x8"
Knife River
314"
3,8%
6114"
9:30 AM
ASTM C31
TYPE OF
FRACTURE~
5
4 - Diagonal
5 - Side (top and bottom)
6 - Side (top or bottom)
This report and/or enclosed test data is the confidential property of the client to whom it is addressed and pertains to the specific
process and/or material evaluated. As su'ch, information contained herein shall not be reprod,uced in part or full and/or any part
thereof be disclosed without FEI Testing & Inspection, Ine.'s written authorization.
7ffJ rwJ CanelIAvenue' CoIvaIlis, Oregon 9733O' phone (541) 757-4698, fax (541) 757-2991
29540 BAirpatRood: Eugere, Oregon 97402, phone (541)684-3849' fax(541)68<h3851