HomeMy WebLinkAboutPermit Construction Specification 2007-2-21 '-, -m ;",,' ." .,., ",ENGINEERING JUDGMENT FIRESTOP DETAIL '^~ PROJECT: THE ROYAL BUILDING SPRINGFIELD OR , 1 CONTRACTOR: MElLI CONSTRUCTION Au"" v, 1G1 < ,'If' F-RATING = 3-HR. V ~v f~ CROSS-SECTIONAL VIEW NO ACCESS THIS SIDE ~ 1 ? "',1, G\ . - ..1I'.tt"'~'1l11 ~ ^-r~ lllnte' L <1'4 "." ,,~,4Sl' ~m!1 S!I .. if 'X -"> lllllll 1,' . .. . ., Illllll cI ;?Il_' \--- . t .. .t,' 1. CONCRETE FLOOR ASSEMBLY (MINIMUM 6" THICK) (3-HR. FIRE-RATING). 2. CONCRETE BLOCK WALL ASSEMBLY (ULlcUL CLASSIFIED) (MINIMUM 8" THICK) (3-HR, FIRE-RATING), 3. MINIMUM 2" THICKNESS MINERAL WOOL (MIN. 4 PCF DENSITY) COMPRESSED 33% AND INSTALLED FLUSH WITH TOP SURFACE OF CONCRETE FLOOR.. 4. MINIMUM 1/8" DEPTH HILTI CP 672 SPEED SPRAY APPLIED TO COMPLETELY COVER MINERAL WOOL AND OVERLAPPING MINIMUM 1/2" ONTO CONCRETE FLOOR AND CURTAIN WALL. . 5, MINIMUM 4" THICKNESS MINERAL WOOL (MIN, 4 PCF DENSITY) COMPRESSED 50% AND INSTALLED FLUSH WITH BOTTOM OF FLOOR. I NOTES: 1, MAXIMUM WIDTH OF JOINT = 3"'- - I 2. T-RATING MAY NOT EQUAL F-RATING IN ACCORDANCE WITH UL 2079., THIS ENGINEERING JUDGMENT REPRESENTS A FIRESTOP SYSTEM THAT WOULD BE EXPECTED TO PASS THE STATED RATINGS IF TESTED, (REFERENCE: UL SYSTEM NO, FW.D-l013 & FW-D-l021) ~. M I HILTI Ine Sheet 1011 I OrawingNo. r ~ ~ oeSjgned~:lsa,Oklah~maUSA,~~;,O)879'~~~O Scale 11164"=1" Hilti Firestop Systen:ls .'~ ::'~~:; ::.?- ,:.-:.' ." :.7 I Oaf. Feb, 21, 2007 74878a , Savmg LIves through Innovation" and Education , "