DAILY FIELD REPORT
Date Pertormed:
Client:
May 9, 2007
Mr. Eric Patterson
Lith ia Toyota
360 East Jackson Street
Medford, Oregon 97501 .
Report Number:
722-60359-67
Lithia Toyota -
Quick Lube
863 Main Street
Springfield, Oregon
Project Name:
Project Location:
B,P, No,:
Type of Inspection:
,COM 06-0868
Welding Inspection
,Weather:
Inside/Overcast
Field Observations and Comments
Performed periodic visual inspection of the following items: Coiumn and bucket paddles single pass fiilet welds PC# (1)
10A, (1) 11A, (1') 12A, (1) 13A, (1) 14A, (4) 15A and (1)16A. Weldments were inspected for size, length, profile and
locations. To the best of our knowledge, the work inspected is in conformance with approved drawings, specifications
and applicable D1.1 (static) codes, Fabricator was asked to notify our office when additional services are needed..
'Inspector: David Smith, Certification# 0877340-B5
If you have any questions ~egarding this report, please feel free to contact us at 541-746-9649.
Respectfully Submitted,
Professional Service 'ndustries, 'nc,
~ard~
Department Manager.
c: City of Springfield
'John Hyland Construction
Doug 'Snider Architect
THIS REPORT IS PROVIDED FOR THE.INFORMA TION OF THE CLlE,,!T ONL Y. THE REPRODUCTION OF THIS REPORT, BY ANY METHOD, AND ITS TRANSMITTAL TO A THIRD
. PARTY, BY ANY MEANS, EXCEPT IN FULL WITHOUT THE WRITTEN PERMISSION OF PROFESSIONAL SERVICE INDUSTRIES, IS PROHIBITED
Street. Springfield.. OR 97477. Phone 541/746-9649. Fax 541/746-7163
l ~~;lInfonnation
,.,~. .To Build On
Engineering . Consulting . Testing
DAILY FIELD REPORT
Date Performed:
June 14, 2007
Mr. Eric Patterson
Lithia Toyota
360 East Jackson Street
Medford, Oregon 97501
Report Number:
722-60359-71
Client:
Project Name:
Lithia Toyota
863 Main Street
Springfield, Oregon
Project Location:
B,P, No.:
Type of Inspection:
COM 06-0868
Reinforcing Steel
Weather:
Clear
Field Observations and Comments
'Performed continuous' inspection during the installation of #5 epoxied rebar dowels in ihe following locations: New
concrete slab to existing concrete footing at the southeast quarter of service reception 101 (8 total), Prior to installation
the predrilled holes were cleaned using a nylon brush and compressed air. Verified minimum embedment depth of 8
inches, The above listed epoxy anchors were installed USin9 Hilti Hit Hy150 epoxy with ICC#5193. The epoxy anchors
were installed in accordance with latest revisions dated May 31, 2007 detail 2/SLI. Contractor was asked to notify our
office when additional services are needed, To the best of our knowledge, the work inspected above was in accordance
with the building department approved design drawings, revisions, specifications and applicable workmanship provisions
,of the International Buildinq Code,
Inspector: Ray Aliperti, ICC# 1017075-88
If you have any questions regarding this report, please feel free to contact us at 541-746-9649.
Respectfully Submitted,
Professional Service 'ndustries, 'nc,
pL~
Joseph Vardner, EIT
Department Manager
c: City of Springfield
John Hyland Construction
Doug Snider Architect
THIS REPORT IS PROVIDED FOR THE INFORMATION OFTHE CLIENT ONL Y. THE REPRODUCTION OF THIS REPORT, BY ANY METHOD, AND ITS TRANSMITTAL TDA THIRD
PARTY, BY ANY MEANS, EXCEPT IN FULL. WITHOUT THE WRITTEN PERMISSION OF PROFESSIONAL SERVICE INDUSTRIES. IS PROHIBITED.
Professional Service Industries, Inc.. 1Q40-A Shelley Slreet- Springfield, OR.97477. Phone 54~f746-9649. Fax 541n46.7163
,-
l"~;lInformation
,.,~. .To Build On
Engineering . Consulting . Testing
DAILY FIELD REPORT
Date Performed:
June 14, 2007
Report Number:
722-60359-70
Client:
Mr. Eric Patterson
Lith ia Toyota
360 East Jackson Street
. Medford, Oregon 97501
Project Name:
Lithia Toyota,
863 Main Street
Springfield, Oregon
Project Location:
B,P. No,:
Type of Inspection:
COM 06-0868
Reinforcing Steel
Weather:'
Clear
Field Observations and Comments
Performed visual inspection of reinforcing steel at the following locations: Concrete slab on grade at the S9 quarter of
reception 101 (details 8/54; 12/S4), Reinforcing steel was checked for grade, size, lap, placement, and clearances
where applicable. Reinforcing steel was secured using tie wire and supported on concrete dobie blocks. Reinforcing
steel was placed in accordance with approved design drawings and specifications. Note: Rebar will be placed on
concrete dobies prior to placement of concrete, Contractor was asked to notify our office when additional services
are needed. To the best of our knowledge, the work inspected above was in accordance with the building department
aooroved desion drawina.s, sOf'cifications and aoolicable workmanship provisions of the International Buildino Code,
Inspector: Ray Aliperti, ICC #101705-88
If you have any questions regarding this report, please feel free to contact us at 541-746,9649.
Respectfully Submitted,
Professional Service 'ndustries, Inc,
0/ t<:/
~Ph Vardner, EIT
Department Manager
c: City of Springfield
John Hyland Construction
Doug Snider Architect
THIS REPORT IS PROVIDED FOR THE INFORMA nON OF THE CLIENT ONL Y. THE REPRODUCTION OF THIS REPORT, BY ANY METHOD, AND ITS TR/WSMITT AL TO A THIRD
P'.eW..,RY AN>' M",NSnF.XCEPeTsIN FULJ-1/4/LrHOIJJ:hTH1 E WRiTTEN eERMISSION 8FRPROFESSIONAL SERVIC" INOUSTRIES, is PROHiBITEO,
onar::ssrvn:;Sl au5m~ ,inC. U4U-A1:i1 eney titreet. tipnngtieJd, 97477. Phone 541n46-9649. Fax 5411746.7163
~.
L "'~;l Information
",~. .To Build On
Engineering. Consulting . Testing
DAILY FIELD REPORT
Date Performed:
June 5, 2007
Report Number:
722-60359-69
Client:
Mr, Eric Patterson
Lithia Toyota
360 East Jackson Street
Medford, Oregon 97501
Project Name:
Lithia Toyota
863 Main Street
Springfield, Oregon
Project Location:
B,P, No.:
Type of Inspection:
COM 06-0868
Reinforcing Steel
Weather:
Showers
Field Observations and Comments
Performed visual inspection of reinforcing steel and anchor bolts at the following locations: F1 and' F3 footings at tciol
room; 107 west wall and center of room; parts room 114 and parts room 114 to tool room 107, Reinforcing steel was
checked for grade, size, lap, placement, and clearances where applicable, Contractor was asked to notify our office
when additional services are needed. To the best of our knowledge, the work inspected above was in accordance with
the building department approved design drawings, specifications and applicable workmanship provisions of the
International Building Code.
Inspector: David Smith, ,ICC #0877340-88, OBOA #442
.If you have any questions regarding this report, please feel free to contact us at 541-746-9649.
Respectfully Submitted,
Pro'essional Service 'ndustries, 'nc,
-P<
c~__
Joseph Vardner, EIT
Department Manager
c: City of Springfield
John Hyland Construction
Doug Snider Architect
THIS REPORT /s PROVIDED FOR THE INFORMA nON OF THE CLIENT ONL Y. THE REPRODUCTION OF THIS REPORT, BY ANY METHOD, AND ITS TRANSMITTAL TO A THIRD
. PARTY,'BY ANY MEANS. EXCEPT IN FULL. WITHOUT THE WRITTEN PERMISSION OF PROFESSIONAL SERVICE INDUSTRIES, 1$ PROHIBITED.
. -
Professional Service Industries, Inc.. 1040-A Shelley Street. Springfield, OR 97477. Phone 5411746-9649. Fax 541f746-7163
1.-"
-l~~;J Info11rUltion
"''''.lTo Build On
Engineering. Consulting. Testing
DAILY FIELD REPORT
Date Performed:
June 5, 2007
Report Number:
722-60359-68
Client:
Mr. Eric Patterson
Lithia Toyota
360 East Jackson Street
Medford, Oregon 97501
Project Name:
Project Location:
Lithia Toyota
863 Main Street
Springfield, Oregon
B,P. No.:
Type of Inspection:
COM 06-0868
Welding
. Weather:
Shop/Inside
Field Observa~ions and Comments
I Performed periodic visual inspection of the following items: Final weldments to columns MK #16A and 17 A and to
brackets MK #18A(quantity 3). Also verified applicable welder certifications, WPS's and mill test reports are on file at
fabricators office, Weldments were inspected. for size, length, profile and locations. To the best of our knowledge, the
work inspected is in conformance with approved drawings, specifications and applicable AWS D1.1 codes. Fabricator
was asked to notifv our office when' additional services are needed.
Inspector: Chris Thomason, Certification 35069949-85
If you have any queslions regarding this report, please feel free to contact us at 541-746-9649.
Respectfully Submitted,
Professional Service 'ndustries, 'nc.
~.~
Joseph Vardner, EIT
Department Manager'
c: City of Springfield
John Hyland Construction
Doug Snider Architect
THIS REPORT IS PROVIDED FOR THE INFORMATION OF THE CLIENT ONL Y. THE REPRODUCTION OF THIS REPORT, BY ANY METHOD, AND ITS TRANSMITTAL TOA THIRD
PARTY, BY ANY MEANS, EXCEPT IN FULL, WITHOUT THE WRITTEN PERMISSION OF PROFESSIONAL SERVICE INDUSTRIES, IS PROHIBITED.
Professional Service In~ustries, Inc.. 1"040-A Shelley Stree.t. Springfield, OR 97477. Phone 541n46-9649. Fax 541n46-7163.