HomeMy WebLinkAboutPermit Field Test & Inspection Report 2008-12-23
~ftl
, ,~.IclJL(\eK
~?tj ~""\ Page 1 of1
. 11~'lh'lrt;41Iiro'ilUIIIU.w!l
Geotechnical & Construction Services '
Daily Field Report ,
Client:
,
EWEB
500E, 4th Ave,
Eugene, Oregon
Project:
Hayden Bridge Water Filtration
Plant Expansion
Springfield, Oregon
Date:
Project No.:
Report No.:
Inspector:
10 No.:
12-23-08
208~168
E-22072
A, Fenstermacher
5258882-49
ICC
Inspection of: Reinforcing Steel/
Epoxy Dowels
Contractor: Wildish Building Co,
Weather: Overcast
BP No.: ,2008.00225
Continuous Inspection: 0
Periodic Inspection: I!'l
Performed preliminary inspection on the reinforcing steel for slab numbers 12, 14 and
6; wall number 30. wall section south of wall #28; eievated slab on top of wall #26; west
wail on top of elevated slab on top of wall #25; ramp walls, Reinforcing steel was
checked for size, grade, laps, quantities, locations, ties, clearance and ,supports, A
final inspection wiil be performed prior to concrete placement.
\
Also, performed continuous inspection during the installation of forty-eight (48) 5/8" x 3'
horizontal all thread stainless steel dowelsinto existing structure for slab and wall tie-in,
Prior to installation, the predrilled holes were cleaned with compressed air and a brush,
Verified minimum embedment of 5", Dowels were secured with Epcon A7 epoxy (ICC-
ES ESR 235/expiration date 11-07-09),
Jake Stucky (Wildish) was asked to notify our office when additional seivices are
needed,
To the best of our knowledge, the work inspected was in accordance with plans dated
02/2008 and applicable workmanship provisions of the I.B,C" except if noted above,
Reviewed By:
f}I,~~
Michael L. Meftr
Technical Manager
c:
EWEB- Mike Stickling (email)
EWEB- Wally McCullough (email)
OBEC- Pete Slocum (email)
Wildish Building Co,- Kevin Fitzjarrell(email)
Wildish Building Co,- Jake Stucky (email)
City of Springfield
RECEIVED
DEe 2 6 l008
MLM:sc
This report and/or enclosed test data is the confidential property of the cli~nt to whom it is addressed and pertains to the specific
process and/or material evaluated. As such, information contained herein shall not be reproduced in part or full and/or any part
thereof be disclosed without.FEI Testing & Inspection, fnc.'s written authorization.
700 WI! CanelI Avenue' Cavallis, Oregon 97330, phooe(541) 757-4698, fax (541) 757-2991
29540 BJ\jtpOrtRcad 'Eugene, Oregon 97402 'phone(541)684J849' fax(541)684J851
63050 Corporate Place, Suile2' Bend, Oregon 97701 'phone(541)382-4844' fax (541) 382-4848
"
-'.l
~fEl
~51
t~er
11:"llllrt;.II~';.'l'I[lJ~li1lil.
GOOtechniml & Construction Servires
Compressive Strength of Concrete
0<b ...(,'L~ (ASTM C 39) .
CLIENT
EWEB
500E, 4'h Ave,'
Eugene, Oregon
PROJECT, Hayden Bridge Water
Filtration Plant Expansion
Springfield, Oregon
DATE
PROJECT NO.
REPORT NO,
12-08-08
2087168
6130
B.P.NO,
2008-00225
DATE CAST 12-01-08 CAST BY A. Fenstermacher DATE RECEIVED 12-02-08
STRENGTH REQUIRED 4000 psi SPECIMEN SIZE 4" x8"
STRENGTH PLACED 4000 psi SACKS SUPPLIER Knife River
PRODUCT CODE 40-SE7 CEMENT MAX SIZE AGG, 3/4"
ADDITIVES Super, Eclipse AIR CONTENT 4,9%
LOAD NO, 2 TICKET NO. 3160466 SLUMP 8"
CONCRETE TEMP 66" F YARDAGE 10,00 OF 55,0 TIME 12:45 PM
AIR TEMP 56"F WEATHER Overcast SPECIMEN STORAGE ASTM C31
POUR LOCATION Top half of walls 22 and 27, and all of wall 26,
Set 2
LOAD 2 SAMPLED From 4'h lift in wall 22,
TEST
DATE
12-08-08
12-29-08
12-29-08
Hold
AGE
(DAYS)
7
28
28
AREA
(IN.')
12,50
WEIGHT
(LBS)
8,3
TOTAL
LOAD (LBS)
52500
COMPRESSIVE
STRENGTH (PSI)
4200
AVERAGE
STRENGTH
(PSIl
TIME OF
TEST
3:05 PM
TYPE OF
FRACTURE~
6
**1 - End Cones 2 - Cone/Spli't
3 - Columnar
4 - Diagonal
5 - Side (top and bottom)
6 - Side (lop or bottom)
REMARKS: Jake Stucky (Wildish) was advised of on-site test results,
Reviewed By:
fJJ,';(,~
Michael L. MeU'r ,
Technical Manager
c:
EWEB- Mike Stickling (email)
EWEB- Wally McCullough (email)
OBEC- Pete Slocum (email)
Wildish Building Co,- Kevin Fitzjarrell (email)
Wild ish Building Co,- Jake Stucky (email)-
City of Springfield
Knife River
RtCt/l/12
OI:L' ~ ,l)
1 D l008
MLM:sc
This report and/or enclosed test data. is the confidential property of the client to whom' it is addressed and pertains to the specific
process and/or material evaluated. As such, information contained herein shall not be reproduced in part or fu\l'andJor any part
thereof be' disclosed without FEl Testing & Inspection, Inc.'s written authorization.
'700 Nvv Ci:JiJ1€IiAveoDe' CorVallis, Oregon 97330' ph<ire(541) 757-'4698' taX(541) 757-2991- '
2li54o BAirport Road, Eugene, Oregon 97402, phone (541) 684J849 ' fax (541 )684.J851
63050 Corporate Place, Suite 2 ' Bend. Oregon 97701 'phone (541) 382-4844 ' fax (541) 382-4848
A:!rrl
W-ft
Page 1 of 1
..
11~'II~lrl;.lflo'~t'llllitWI
Geotechnical & Construction Seivices ,
, Daily Field Report
Client: ,EWEB Project: Hayden Bridge Water Filtration Date: 12-01-08
500E, 4'h Ave, Plant Expansion Project No.: 2087168
Eugene,Oregon Springfield, Oregon Report No.: E-21906
Inspector: A, Fenstermacher
10 No.: 5258882-49
ICC
Inspection of: Reinforced Concrete Weather: Overcast Continuous Inspection: 0
Contractor: Wildish BPNo.: 2008-00225 Periodic Inspection: 0
Perforrned inspection on the reinforcing steel for wall #26, Reinforcing steel was
checked for' size, grade, laps, quantities, locations, ties, clearance and supports, Also,
performed'final inspection on the reinforcing steel for wall #22 and 27, A preliminary
inspection was performed on 11-25-08 (reference report number E21882),
Observed the placement of 20 yards of Knife River 4000 psi concrete (mix 40-SE7 with
fibers) into first two lifts in walls 22 and 27 and 40 yards of Knife River 4000 psi
concrete (mix 40-SE7) into remainder of areas noted above, Concrete was placed by
pump and was mechanically consolidated, Tested load 1 of mix 40-SE7 for mix design
compliance: slump- 6"; concrete temperature- 70F; air temperature- 50F; air content-
5,8%, Cast one (1) set of four (4) 4" x 8" compression test cylinders from each mix,
I Set 1 (mix 40-SE7 with fibers)
I Concrete temperature- 66F
I Air temperature- 57F
I Slump- -=, 3/4"
I Air content- 3,5%
Set 2 (mix 40-SE7)
Concrete temperature- 66F
Air temperature- 56F
Slump- 8"
Air content- 4,9%
Jake Stucky (Wildish) was advised of on-site test results and was asked to notify our
office when additional services are needed,
To the best of our knowledge, the work inspected was in accordance with pians dated
02/2008 and applicable workmanship prpvisions of the I.B,C" except if noted above,
Reviewed By:
A.~jk1
Michael L. Me~r
Technicai Manager
.~
RECEIVED
DEe 1 5 Z008
c:
EWEB- Mike Stickling (email)
EWEB- Wally McCullough (email)
OBEC- Pete Slocum (email)
Wildish Building Co,- Kevin Fitzjarrell (email)
Wild ish Building Co,-'Jake Stucky (email)
City of Springfield '
_ ''__'' , '" ' ,. , MLM:sc
This report and/or enclosed test data is the confidential property of the client to whom jUs addressed and pertains"to the specific
process.and/or material evaluated. As such, information contained herein shall not'be reproduced in part or full and/or any part
thereof be disclosed without FEI Testing & Inspection, Inc,'s ;written authorization.
7ffJ tw Cornell Avenue' CoovaIlis, Oregm 97330 ' phone (541) 757-4698 ,fax (541) 757-2991
29540 BAirportRoad' Eugene, 0regm97402' phone (541)684-3849 'fax(541)684-3851
630ffJ Corporate Place, Suile2' Bend, Oregon 97701 ' phone (541) 382-4844 ,fax (541) 382-4846
.. -".'.',~.;r-~-,;~,:',;,' r'~'J-- "
--....
S,;)
Page 1 of 1
11~'llml;.I~..'1jatllll~..u.L!
Gcu",,"; "lic:al & Construction Ser\iices
Daily Field Report
Client: EWEB Project: Hayden Bridge Water Filtration Date: 12-03-08
500E, 4'h Ave, Plant Expansion Project No.: 2087168
Eugene, Oregon Springfield, Oregon Report No.: E-21924
Inspector: A. Fenstermacher
ID No.:. 5258882-49
ICC
Inspection of: Epoxy Dowels' Weather: Overcast Continuous Inspection: 0
Contractor: Wild ish Construction BP No.: 2008-00225 Periodic Inspection: [;'1
Performed continuous inspection during the installation of:seven (7) 5/8" x 3' horizontal
stainiess steei all thread dowels into existing footing at the southwest corner of slab
#16, Prior to installation, the predrilled holes were cleaned with compressed air and a
brush, Verified minimum embedment of 5", Dowels were secured with Epcon A7 (ICC-
ES ESR- 2351, expiration dated 11-07-09), '
Aiso, performed preliminary inspection on the reinforcing steel for slab #16 and
remainder of footing along north side at west end, Reinforcing steel was checked for
size, grade, lap, quantities;' locations, ties, clearance and supports, A final inspection
will be performed prior to concrete placement.
Jake Stucky (Wildish) was asked to notify our office when additional services are
needed,
To the best of our knowledge. the work inspected was in accordance with plans dated
02/2008 and applicable workmanship provisions of the I.B,C" except if noted above,
Reviewed By:
A.~,~
Michael L. Me-tl - .
Technical Manager
c:
EWEB- Mike Stickling (em ail}
EWEB- Wally McCullough (em ail)
OBEC- Pete Slocum (email)
Wildish Building Co,- Kevin Fitzjarrell (email)
Wildish Building Co,- Jake Stucky (email)
City of Springfield
MLM:sc
This report and/or enclosed test data is the confidential property of the client to who'm it is addressed an-d pertains"to the specific
process and/or material evaluated. As such, information contained herein shall not be reproduced in part or full and/or any part
thereof be disclosed without FEI Testing & Inspection, Inc. 'swritten authorization.
7fJJ NN Cornell Avenue' Crniallis, Oregon 97330, phone (541) 757-4698 ,fax (541) 757-2991
29540 B Airport Road ' Eugene, Oregon 97402 ' phone (541) 684J849 ,fax (541) (i84;3851
63050 Corporate Place, Suite 2 ' Bend, Oregon 97701 'phone (541) 382-4844 ' fax (541) 382-4846
---
(j ~' "'PI
.,.'. "..~..
'. .,,-
1I~'IINft;tll,..'~aIlIJ/.lm.
CLIENT
EWEB
500E, 4th Ave,
Eugene, Oregon
DATE CAST
STRENGTH REQUIRED
STRENGTH PLACED
PRODUCT CODE
ADDITIVES
LOAD NO.
CONCRETE TEMP
AIR TEMP
POUR LOCATION
LOAD 6 SAMPLED
Gcv\cJ ,,,ical & Construction Services
Compressive Strength of Concrete
(ASTM C 39)
PROJECT
DATE
PROJECT NO.
REPORT NO.
12-02-08
2087168
6099
Hayden Bridge Water
Fiitration Plant Expansion
Springfield, Oregon
B,P, NO,
2008-00225
11-04-08 CAST BY
4000 psi
4000 psi SACKS
40KIUOZF CEMENT
ADVA. ECLIPSE; Fiber; AEA
6 TICKET NO,
66" F YARDAGE
50" F WEATHER
Slab numbers 9 and 10,
DATE RECEIVED
SPECIMEN SIZE
SUPPLIER
MAX SIZE AGG,
AIR CONTENT
SLUMP
TIME
SPECIMEN STORAGE
11-05-08
4" x 8"
Knife River
3/4"
4,0%
51/2"
10:30 AM
ASTM C31
A, Fenstermacher
,3160127
10,0 OF 60,0
Showers
From north end of slab #9,
AVERAGE
TEST AGE AREA WEIGHT TOTAL COMPRESSIVE STRENGTH TIME OF TYPE OF
DATE (DAYS) (IN.') (LBS) LOAD (LBS) STRENGTH (PSI) (PSI) TEST FRACTURE~
11-11-08 7 12,56 8,3 53400 4250 7:30 AM 5
12-02-08 28 12,62 8.4 79900 6330 5:15 PM 1
12-02-08 28 12,62 8.4 78200 6200 6265 5:20 PM 1
Hold
**1 - End Cones 2 - COne/Split 3 - Columnar 4 - Diagonal 5 - Side (top and bottom) 6 - Side (top or. bottom)
REMARKS: Jake Stucky (Wildish) was advised of on-site test results,
Reviewed By:
~~e~'~
Technical Manager
c:
EWEB- Mike Stickling (email)
EWEB- Wally McCullough (email)
OBEC- Pete Slocum (email)
Wildish Building Co,- Kevin Fitzjarrell (email)
WildishBuilding Co,- Jake Stucky (email)
City of Springfield
Knife River
MLM:sc
This report and/or enclosed test data is the confidential property of the client to whom iUs addressed and pertains to the specific
process and/or material evaluated. As such, information contained herein shall not be reproduced in part or full and/or any part
thereof be disclosed without FEl Testing & Inspection, Inc. 's written authorization.
7fJJ t-NV Camel Avenue' COIvall~, Oregon 97330, phone (541 ) 757-4698 'fax(541) 757-2991
29540 BAirportRood' Eugene, Oregon 97402 'phone(541)684-3849' fax (541) 684-3851
63050 Corporate Place, Suite 2, Bend, Oregon 97701 'phone (54))382-4844' fax (541) 382-4846
~.......
~rt.
Page 1 of 1
11:"II~lrl;.lI~.'~UIIII\'_
Gou~c...: ,,,ical & Construdion Servires
Daily Field Report
Client: EWEB Project: f-iayden Bridge Water Filtration Date: 12-08-08
500E, 4'h Ave, Plant Expansion Project No.: 2087168
Eugene, Oregon Springfield, Oregon Report No.: E-21967
Inspector: A. Fenstermacher
ID No.: 5258882-49
ICC
Inspection of: Reinforced Concrete Weather: Fog Continuous Inspection: 0
Contractor: Wildish Construction BPNo.: 2008"00225 Periodic Inspection: III
Performed inspection on the reinforcing steel for wall #28 and raw water channel
suspended slab at the NE corner, Reinforcing steel was checked fir size, grade, alps,
quantities, locations, ties, clearance and supports, '"
>.,'.'
Observed the placement of 27 yards of Knife River 4000 psi concrete (mix 40SE7) into
areas noted above, Load 1 was tested for mix design ,compliance: slump- 6 1/4",
concrete temperature- 65F; air temperature- 45F; air content- 5,2%;'-Cast one (1) set
of four (4) 4" x 8" compressive strength cylinders from load 2, Notified Mike Stickling
(EWEB) of on-site results: slump- 5 314"; concrete temperature- 65F; air temperature-
47F; air content- 5,2%,
Mr, Stickling was asked to notify our office when additional services are needed,
To the best of our knowledge, the work inspected was in accordance with plans dated
02/2008 and applicable workmanship provisions of the I.B,C" except if noted above,
Reviewed By:
fJ,,<i,~
Michael L. Me"r
Technical Manager
RECEIVED
DEe 1 5 ZOOR
c:
EWEB- Mike Stickling (emaii)
EWEB- Wally McCullough (email)
OBEC- Pete Slocum (email)
WiidishBuilding Co,- Kevin Fitzjarrell (email)
Wildish Building Co,- Jake Stucky (em ail)
City of Springfield
RFCEIVED
L '" l"" .. -....,
'>-..... 1. i} ~Jt..l;)
MLM:sc
This report and/or enclosed test data is the confidential property of the client to whom it is addressed and pertains to the specific
process and/or material evaluated. As such, information contained. herein shall not be reproduced in part or futl and/or any'part
thereof be disclosed ,without FEI Testing & Inspection, Inc,'s written authorization.
7m NN 0:meII Avenue' CavalJis, Oregon 9,7330' p/l<re(541) 757-4698' fax (541) 757-2991
29540 BAirpcrtRoad 'Eugene, Oregon 97402, phme(541)684J849' fax (541) 68<h'l851
63050 Corporate Place, Suite 2 ' Bend, Oregon 97701 ' phone (541) 382-4844 ' fax (541) 382-4846
~"P~
~Yttl
Geotechnk:al & Cons1ruclion SeMres
Compressive Strength of Concrete
(ASTM C 39) ,
'1~'II~I~;<!III~.':ia'llllIl_
CLIENT
EWEB
500E, 4th Ave,
Eugene, Gregon
PROJECT
Hayden Bridge Water"
Filtration Plant Expansion
Springfield, Gregon
DATE
PROJECT NO.
REPORT NO.
12-08-08
2087168
6129
B.P. NO.
2008-00225
DATE CAST 12-01-08 CAST BY A. Fenstermacher DATE RECEIVED 12-02-08
STRENGTH REQUIRED 4000 psi SPECIMEN SIZE 4" x 8"
STRENGTH PLACED 4000 psi SACKS SUPPLIER Knife River
PRODUCT CODE 40-SE7 (with fibers) CEMENT MAX SIZE AGG, 3/4"
ADDITIVES Super, Eclipse, Fiber AIR CONTENT 3.5%
LOAD NO. 2 TICKET NO. 3160461 SLUMP 7 3/4"
CONCRETE TEMP 660 F YARDAGE 10.00 OF 20,00 TIME 11:15AM
AIR TEMP 5r F WEATHER Overcast SPECIMEN STORAGE ASTM C31
Po.UR LOCATION 1" and 20d lift in wall #'s 22 and 27,
Set 1
LOAD 2 SAMPLED From 20d lift,
TEST
DATE
12-08-08
12-29-08
12"29-08
Hold
AGE
(DAYSl
7
28
28
AREA
(IN.'!
12,50
WEIGHT
(LBSl
8.4
TOTAL
LOAD (LBS)
60100
COMPRESSIVE
STRENGTH (PSI\
4810
AVERAGE
STRENGTH
(PSI)
TIM E OF
TEST
3:10 PM
TYPE OF
FRACTURE-
6
*"1 - End Cones
2 - Cone/Split
3 - Columnar
4 - Dtagonal
5 - Side (top and bottom)
6 - Side (top or bottom)
REMARKS: Jake Stucky (Wildish) was advised of on-site test results,
Reviewed By:
, fh.';(.~
Michael L. Mey{/
Technical Manager
c:
EWEB- Mike Stickling (emaii)
EWEB- Wally McCullough (email)
GBEC- Pete Slocum (email)
Wildish Building Co,- Kevin Filzjarrell (email)
Wildish Building Co,- Jake Stucky (email)
City of Springfield
Knife River
MLM:sc
This report andlor enclosed lest data is the confidential property of the client to whom it is addressed and pertains to. the specific
process and/or material evaluated. As such, information contained herein shall not be reproduced in part or full and/or any part
I.hereof be disclosed without FEl Testing ~ Inspection, Inc.'s written authorization.
7fIJ MN CaneII Avenue' CavalfIS, Oregon 97330, phone (541 )757-4698' fax (541) 757-2991
29540 BAirportRoad' Eugene, Oregon 97402, phone (541) 684-3849 'fax(541)684J851
63050 Corporate Place, Suite 2 ' Bend, Gregon 97701 'phone (541) 382-4844 ' fax (541 ) 382-4846
~fE'
11~'mlrl;4m..'~a.t1I'm'lH_
~;....; " ,;.:at & Construction Servires
Compressive'Strength of Concrete
(ASTM C 39) ,
CLIENT
EWEB
500E, 41h Ave,
Eugene, Oregon
PROJECT
Hayden Bridge Water
Filtration Plant Expansion
Springfield, Oregon
DATE
PROJECT NO,
REPORT NO,
12-08-08
2087168
6104
B,P, NO.
2008-00225
DATE CAST 11-10-08 CAST BY A, Fenstermacher DATE RECEIVED 11-11-08
STRENGTH REQUIRED 4000 psi SPECIMEN SIZE 4" x8"
STRENGTH PLACED 4000 psi SACKS SUPPLIER Knife River
PRODUCT CODE 40K1UOZF CEMENT MAX SIZE AGG, 3/4"
ADDITIVES Adva; Eclipse; Fiber AIR CONTENT 5,3%
LOAD NO. ' 2 TICKET NO, 3160190 SLUMP 6"
CONCRETE TEMP 660 F YARDAGE 10,0 OF 30,0 TIME 12:00 PM
AIR TEMP 540 F WEATHER Overcast SPECIMEN STORAGE ASTM C31
POUR LOCATION Slab number 11,
Set 1
LOAD 2 SAMPLED From southwest corner.
AVERAGE
TEST AGE AREA WEIGHT TOTAL COMPRESSIVE STRENGTH TIME OF TYPE OF
DATE (DAYS) (IN.') (LBS) LOAD (LBSl STRENGTH (PSIl (PSll TEST FRACTURE"
11-17-08 7 12.43 8.4 55300 4450 9:15AM 5
12-08-08 28 12,50 8.4 75600 6050 3:15 PM 6
12-08-08 28 12,50 8,3 78100 6250 6150 3:20 PM 6
Hold
..1 - End Cones 2 - Cone/Split 3 - Columnar 4 - Diagonal 5 - Side (top and bottom) 6 - Side (top or bottom)
REMARKS: Mike Stickling (EWEB) and Jake Stucky (Wildish) was advised of on-site test results,
ReviewedBy:
fh.<;t;,~
Michael L. Meyer ~
Technical Manager
c:
EWEB- Mike Stickling (email)
EWEB- Wally McCullough (email)
OBEC- Pete Slocum (email)
Wildish Building Co,- KevinFitzjarrell (email)
Wildish Building Co,- Jake Stucky (email)
City of Springfield
Knife River
MLM:sc
This report and/or enclosed test data is the confidential property of the client to whom it is addressed and pertains to the specific
process and/or rnateriaLevaluated. As such, information contained herein shall not be reproduced in part or full and/or any part
thereof be disclosed without FEI Testing & Inspection, Inc:'s written authorization.
700 NoN Cornell Avenue' CavalfIS, Oregon 97330, phone (541) 757-4698, fax (541) 757-2991
29540 BAirportRoad' Eugene, Oregon 97402 'phone (541)684-J849 fax(541 )684.'3851
63050 Corporate Place, Suite 2 ' Bend, Oregon 97701 'phone (541) 382-4844 ,fax (541) 382-4846
{~fEI
11a.'II~(ti;.I~"'~l'I(II~U1!I
CLIENT
EWEB
500E, 4'h Ave,
Eugene, Oregon
DATE CAST
STRENGTH REQUIRED
STRENGTH PLACED
PRODUCT CODE
ADDITIVES
LOAD NO.
CONCRETE TEMP
AIR TEMP
POUR LOCATION
LOAD 1 SAMPLED
Geotechnical & Construction Services
Compressive Strength of Concrete
(ASTM C 39)
PROJECT
Hayden Bridge Water
Filtration Plant Expan~ion
Springfield, Oregon
DATE
PROJECT NO.
REPORT NO,
12-08-08
2087168
6105
B.P.NO.
2008-00225
DATE RECEIVED
SPECIMEN SIZE
SUPPLIER
MAX SIZE AGG,
AIR CONTENT
SLUMP
TIME
SPECIMEN STORAGE
11-11-08
4" x8"
Knife River
3/4"
4,7%
8"
1:30 PM
ASTM C31
11-10-08 CAST BY
4000 psi
4000 psi SACKS
40-SEy CEMENT
Super; Eclipse; Adva
1 TICKET NO.
70" F YARDAGE
560 F WEATHER
Wall number 25,
SET2
From first lift
A. Fenstermacher
AVERAGE
TEST AGE AREA WEIGHT TOTAL COMPRESSIVE STRENGTH TIME OF TYPE OF
DATE (DAYS) (IN,') (LBSl LOAD (LBSt STRENGTH (PSIl (PSIl TEST FRACTUREri
11-17-08 7 12.43 8,5 62500 5030 9:20 AM 5
12-08-08 28 12,50 8,5 79400 6350 3:25 PM 6
12-08-08 28 12,50 8,5 80100 6410 6380 3:30 PM 6
Hold
**1 - End Cones 2 - Cone/Split 3 - Columnar 4 - Diagonal 5 - Side (top and bottom) 6 - Side (top or bottom)
3160196
7,5 ,OF 15,0
Overcast
REMARKS: Mike Stickling (EWEB) and Jake Stucky (Wildish) was advised of on-site test results,
Reviewed By:
(J;,~.~
Michael L. M~'il
Technical Manager
c:
EWEB- Mike Stickling (email)
EWEB- Wally McCullough (email)
OBEC- Pete Slocum (email)
Wildish Building Co,- Kevin Fitzjarrell (email)
Wildish Building Co,- Jake Stucky (email)
City of Springfield
Knife River
MLM:sc
This report and/or enclosed test data is the confidential property of the client to whom it is addressed and pertains to the specific
process and/or material evaluated. A~ such, information contained hereifl sha!1 not be reproduced in part or full and/or any part
thereof b~ disclosed without FEI Testing & Inspection, lnc.'s written authorization:
7fil tfN Come<< Avenue' Cavanis, CfegGn 9733O' phone(541) 757-4698, fax (541) 757-2991'
29540 B AiIpcrt Road ' Eugene, CfegGn 97402 ' phone (541) 684,3849 ,fax (541) 684J851
63050 Corporate Place, Suite 2 ' Bend, Oregon 97701 ' phone (541) 382-4844 ' fax (541) 382-4846
~PPt
~rt
Page 1 of 1
11~"II'lrt;"III11':i~'IIIJt!.I~l.
Geotechnical & ConstrucliOn Servires
Daily Field Report
Client: EWEB Project: Hayden Bridge Water Filtration Date: 11-13-08
500E, 4'h Ave, Plant Expansion ' Project No.: 2087168
Eugene, Oregon Springfield, Oregon Report No:: E-21789
Inspector: A. Fenstermacher,
IDNo,: 5258882-49
ICC
Inspection of: Reinforcing Steel Weather: Showers Continuous Inspection: D
Contractor': Wildish Construction BPNo.: 2008-00225 Periodic Inspection: Ii]
Performed preliminary inspection on the reinforcing steel for slab numbers 13 and 15
and wall number 24, Reinforcing steel was checked for grade, size, laps, quantities,
locations', ties, clearance and supports, A final inspection will be performed prior to
concrete placement.
(/:"',
'::',;;'B-radY (Wildish) was asked to notify our office when additional services are needed,
To the best of our knowledge, the work inspected was in accordance with RFI #47
dated 10-28-08, plans dated 02/2008 and applicable workmanship provisions of the
I.B,C" except if noted above,
Reviewed By:
/h.'i.~
Michael L. M~er
Technical Manager
c.
EWEB- Mike Stickling (email)
EWEB- Wally McCullough (email)
OBEC- Pete Slocum (em ail)
Wildish Building Co,- Kevin Fitzjarrell (email)
Wildish Building Co,- Jake Stucky (email)
City of Springfield
MLM:sc
.. ...- . -.. .... -- - - ---
This report and/or enclosed test data is the confidential property of the client to Whom it is addressed and'pertains"to the specific
process and/or material evaluated. As such, information contained herein shall notbe reproduced in part or full and/of any part
thereof be disclosed without FEI Testing & Inspection, Inc.'s written authorization.
7fJJ NN Cornell Avenue,' Corvallis, 0Eg0n 97330, phone (541) 757-4698, fax (541) 757-2991
29540 BAirpalRoad 'Eugene, 0Eg0n 97402, phme (541)6B4-3a49 , fax (541) 684-J851
630fJJ Corporate Place, Suite 2, Bend, Oregon 97701, phone (541)382-4844' fax (541) 382-4846
./
&fEI
11:"'II~I,,;.yI~~'1:1~'IIII~IIIIH.
CLIENT
EWEB
500E, 4'h Ave,
Eugene. Oregon
DATE CAST
STRENGTH REQUIRED
STRENGTH PLACED
PRODUCT CODE
ADDITIVES
LOAD NO,
CONCRETE TEMP
AIR TEMP
POUR LOCATION
LOAD 1 SAMPLED
TEST
DATE
11-17-08
12-08-08
12-08-08
Hold
AGE
(DAYS)
7
28
28
Geotechnical & Construction Services
PROJECT
B.P.NO,
11-10-08 CAST BY
4000 psi
4000 psi SACKS
40-SE7 CEMENT
Super; Eclipse; Adva
1 TICKET NO.
70'F Y~RDAGE
56' F WEATHER
Wall number 25,
SET2
From first lift
AREA
(IN,')
12.43
WEIGHT
(LBS)
8,5
TOTAL
LOAD (LBS)
62500
**1 - End Cones 2 - Cone/Split
3 - Columnar
Compressive Strength of Concrete
(ASTM C 39)
Hayden Bridge Water
Filtration Plant Expansion
Springfield, Oregon
. 2008-00225
A, Fenstermacher
3160196
7,5 OF 15,0
Overcast
COM PRESSIVE
STRENGTH (PSI)
5030
I
I
I
DATE
PROJECT NO,
REPORT NO,
11-17-08
2087168
6105
DATE RECEIVED
SPECIMEN SIZE
SUPPLIER
MAX SIZE AGG,
AIR CONTENT
SLUMP
TIME
SPECIMEN STORAGE
AVERAGE
STRENGTH
(PSI)
TIME OF
TEST
9:20 AM
4 - Diagonal
5 - Side (top and bottom)
6 - Side (top or bottom)
REMARKS: Mike Stickling (EWEB) and Jake Stucky (Wildish) was advised of on-site test resuits,
Reviewed By:
{1~e~:~
T echn)cal M_an.?ger
,I
c:
EWEB- Mike Stickling (email)
EWEB- Wally McCullough (email)
OBEC- Pete Slocum (email) , .'
Wild ish Building Co,- Kevin Fitzjarrell (email)
Wildish Building Co,- Jake Stucky (em ail)
City of Springfield '
Knife River
MLM:sc ,
-'.
11-11-08
4" x 8"
Knife River
3/4"
4,7%
8"
1:30 PM
ASTM C31
TYPE OF
FRACTURE-
S I
I
I
I
RECEIVE!:)
NOV 2 1 Z008
This report and/or enclosed test data is the confidential property of the client to whom it is addressed and pertains to the specific
process and/or material evaluated. As such, information contained herein shall not be reproduced in part or full and/or any part
thereof be disclosed without.FEI Testing & Inspection, .'nc.'s Y,ffitten authorization.
7fIJ ~ Cornell Avalue ' ContaDis, Oregon 97330 ' phone (541) 757-4698 ,fax (541) 757-2991
29540 BAirport Rood ' Eugene, Oregon 97402 ' phone (541) 684'3849 'fax (541) ~1
63050 Corporate Place, Suite 2 ' Bend, Oregon 97701, phone (541) 382-484'1' fax (541) 382-4846
&ftl
Geotechnical & Consfruclion Servires
Compressive Strength of Concrete
(ASTM C 39) ,
11~'mlrt;.I~~'~~'IlIJ\llIIHIi
CLIENT
EWEB
500E, 4'h Ave,
Eugene,'Oregon
PROJECT
Hayden Bridge Water
Filtration Plant Expansion
Springfield, Oregon
DATE
PROJECT NO.
REPORT NO.
11-18-08
2087168
6072
B.P, NO.
2008-00225
DATE CAST
STRENGTH REQUIRED
STRENGTH PLACED
PRODUCT CODE
ADDITIVES
LOAD NO,
CONCRETE TEMP
AIR TEMP
POUR LOCATION
10-21-08 CAST BY J,Keller DATE RECEIVED
4000 psi SPECIMEN SIZE
4000 psi SACKS SUPPLIER
2440KIUOZF CEMENT MAX SIZE AGG,
Adva, Eclipse, Fiber AIR CONTENT
'4 (1" accepted) TICKET NO, 3159951 SLUMP
68" F YARDAGE 10,00 OF TIME
53" F WEATHER Clear SPECIMEN STORAGE
FootinglSlab 1 and 2 east wall and spread footing number 8 north wall.
10-22-08
4" x8"
Knife River
3/4"
5,0%
51/4"
12:10 PM
, ASTM C31
LOAD 1 SAMPLED
Near SE corner of foo~ng 1 slab #1,
AVERAGE
TEST AGE AREA WEIGHT TOTAL COMPRESSIVE STRENGTH TIME OF TYPE OF
DATE (DAYS) (IN,') (LBS\ LOAD (LBSI STRENGTH (PSJI (PSJI TEST FRACTURE"
10-28-08 7 12,56 8.4 53400 4250 I 12:45 PM 6
11-18-08 28 12,56 8.4 72500 5770, f 7:40 AM 5
11-18-08 28 12,56 8.4 75700 6030 5900 7:45 AM 1
Hold I
**1 - End Cones
2 - Cone/Split
3 - Columnar
4 - ,Diagonal
5 - Side (top and bottom)
6 - Side (top or bottom)
REMARKS: Mike Stickling (EWEB) was advised of on-site test results,
Reviewed By:
/l;xlL^ ~
Michael L, ~;yT
Technical Manager
c.
EWEB- Mike Stickling (email)
EWEB- Wally McCullough (emali)
OBEC- Pete Slocum (email)
WiJdish Building Co,- Kevin Fitzjarrell (email)
Wild ish Building Co,- Jake Stucky (email)
City of Springfield
Knife River
MLM:SC
This repOrt and/or enclosed test data is the confidential property of the client to whom itis addressed and pertains to the specific
process and/or material evaluated. As such, 'information contained herein shall not be reproduced in part or full and/or any part
thereof be disclosed without FEI Testing & Inspection, Ine.'s written authorization.
7fJJ r-NV CcmeIIAvenue' Cavallis, Oregon 97330, phone (541) 757-4698, fax(541) 757-2991
29540 BAirport Rood ' Eugene, Oregon 97402 ' phone (541) tJ84.J849 ,fax (541) 684;3851
63050 Corporate Place, Suite 2, Bend, Oregon 97701 'phone (541) 382-4844: fax (541) 382-4846
&fEJ
Page 1 of 2'
11~'lmrt;tll~'~~'IlII~.mw
Geotechnical & Conslruclion Servires
Daily Field Report
Client:
EWEB
500E, 4'h Ave,
Eugene, Oregon
Project:
Hayden Bridge Water Filtration
Plant Expansion
Springfield, Oregon
Date:
Project No.:
Report No.:
Inspector:
10 No.:
11-14-08
2087168
E-21790
A, Fenstermacher
5258882-49
ICC
Inspection of:, Reinforced Concrete
Contractor: Wildish Construction'
Weather: Fog
BpINo~: 2008-00225
4<
"
- Continuous Inspection: 0
'Periodic Inspection: 0
Performed final inspection on the reinforcing steel for slab numbers 13 and 15 and wall
number 24, A preliminary inspection was performed on 11-13-08 (reference FEI report
number E-21789),
Observed placement of 65 yards of Knife River 4000 psi concrete (mix 40K1 UOZF) into
slabs and 10,75 yards of Knife River 4000 psi concrete (mix 40-SE7) into wail.
Concrete was placed by pump and was mechanically consolidated, Performed field
tests on loads 1 and 2 of slab concrete for mix design compliance,
I Load 1
I Concrete temperature- 65F
I Air teme.erature- 54F
I Slump-7"
I Air content- 5,7%
Load 2
Concrete temperature- 65F
Air tem~erature- 47F
Slump- 5 1/2"
Air content- 4,8%
Also; cast one (1) set of four (4) 4" x 8" compressive strength cylinders from each mix,
I Set 1 (mix 40K1 UOZF)
I Concrete temperature- 68F
I Air temperature- 54F
I Slump-7"
I Air content- 4.4%
Set 2 (MIX 40-SE7)
Concrete temperature- 66F
Air temperature- 55F
Slump- 81/4"
Air content- 3,6%
,
f\t:.Cf/'VtD
NOV'J
'" 1 2008
This report and/or enclosed test data is the confidential property of the client to 'Nhom it is addressed and 'pertains to the specific
process and/or material evaluated. As such, information contained herein shall not be reproduced in part or full and/or any part
thereof be disclosed without FEI Testing & Inspection, Inc,'s written authorization. .
7m rm Cornell Avenue' Cavallis. Oregon 97330, phone (541) 757-4698, fax (541) 757-2991
29540 B Airport Road ' Eugene, Oregon 97402 ' phone (541 j 684-3849 ,fax (541) 684J851
63050 Corporate Place, Suite 2 ' Bend. Oregon 97701 'phone (541) 382-4844 ' fax (541) 382-4846
Hayden Bridge Water
Filtration Plant Expansion
Project No,: 2087168
, Report' No,: E-21790
Date: 11-14-08
Page 2 of 2
Jake Stucky (Wild ish) was advised of on-site test results and was asked to notify our
office when additional services are needed, '
To the best of our knowledge, the work inspected was in accordance with RFI #47
dated 10-28-08, plans dated 02/2008 and applicable workmanship provisions of the
I.B,C" except if noted above,
R;;;Jn~~~
Michael L. Meyer
Technical Manager
c:
EWEB- Mike Stickling (email)
EWEB- Wally McCullough (em ail)
OBEC- Pete Slocum (em ail)
Wildish Building Co,- Kevin Fitzjarrell (email)
Wildish Building Co,- Jake Stucky (email)
City of Springfield
MLM:sc
This report and/or enclosed test data is the confidential property of the client to whom it is addressed and pertains to the specific
process and/or material evaluated. As such, information contained herein shall not be reproduced in part or full and/or any part
thereof be disclosed without FEI Testing & In~pection, Inc.'s \Witten authorization.
750 NVV CanelIAvenue' Cavallis, Qegon 97330' phone (541) 757-4698 'fax(541) 757-2991
29540 BAirpat Road, Eugene, Qegon 97402, phcre (541) 684-3849 ,fax (541)684-3851
63050 Corporate Place, Suite 2 ' Bend, Oregon 97701 'phone (541) 382-4844 ' fax (541) 382-4846
~......~
~ttl
Page 1 of 1
11a.'llfl~;"I~~':i~'llIJI_
Geotechnical & Construction Services
Daily Field Report
Client: EWEB Project: Hayden Bridge Water Filtration Date: 11-18-08
500E, 4'h Ave, Plant Expansion Project No.: 2087168
Eugene,Oregon Springfield, Oregon Report No.: E-21825
Inspector: A. Fenstermacher
ID No.: 5258882-49
ICC
Inspection of: Reinforcing Steel Weather: Partly Cloudy Continuous Inspection: D
Contractor: Wi/dish Construction BP No.: 2008-00225 Periodic Inspection: Ii!
Performed preliminary inspection on the reinforcing steel for siab numbers 17 and 19
and wall numbers 23 and 29, Reinforcing steel was checked for grade, size, laps,
quantities, locations, ties, clearance and supports, A final inspection will be performed
prior to concrete placement.
Jake Stucky (Wi/dish) was asked to notify our office when additional services are'
needed,
To the best of our knowledge, the work 'in-progress was in accordance with RFI #47
dated 10-28-08, plans dated 02/2008 and applicable workmanship provisions of the
I.B,C" except jf noted above, '
Reviewed By:
A.'i./~
Michael L. M eJ,r .
T echnicai Manager
c:
EWEB- Mike Stickling (email)
EWEB' Wally McCullough (email)
OBEC- Pete Slocum (em ail)
Wi/dish Building Co,- Kevin Fitzjarrell (email)
Wildish Building Co,- Jake Stucky (email)
City of Springfield
MLM:sc
J
"This report and/or enclosed test data is the confidential property of the client to lNhom iUs addressed and pertains lathe specific
process and/or material evahJsted. As such, information contained herein shall not be reproduced in part or full and/or any part
thereof be di~closed without FEI Testing & Inspection, Inc.'s y.mtten authorization.
7fIJ N-N ComeIIAvenue' CorvaIILs, Oregon 97330, phone (541) 757-4698, fax (541) 757-2991
29540 BAirpatRoad' Eugene, Oregon 97402, phme (541) 684:J849 ,fax (541)684-3851
630fIJ Corporate Place, Suite 2 'Bend, Oregon 97701, phone (541) 382-4844 'fax(541) 382-4846
(~FEI
Geotechnia31 & Construc:lion SeIVices
, Compressive Strength of Concrete
(ASTM C 39),
1I:lo'mlrf;.lf~'~a'IIIJ~d1m"
CLIENT
EWEB
500E. 4'h Ave,
Eugene, Oregon
PROJECT
Hayden Bridge Water
Filtration Plant Expansion
Springfield, Oregon
DATE
PROJECT NO.
REPORT NO.
11-17-08
2087168
6104
B.P, NO.
2008-00225
DATE CAST 11-10.08 CAST BY A. Fenstermacher DATE RECEIVED 11-11-08
STRENGTH REQUIRED 4000 psi SPECIMEN SIZE 4" x 8"
STRENGTH PLACED 4000 psi SACKS SUPPLIER Knife River
PRODUCT CODE 40K1 UOZF CEMENT - MAX SIZE AGG, 3/4"
ADDITIVES Adva; Eclipse; Fiber AIR CONTENT 5,3%
LOAD NO. 2 TICKET NO, 3160190 SLUMP 6"
CONCRETE TEMP 66' F YARDAGE 10,0 OF 30,0 TIME 12:00 PM
AIR TEMP 54' F WEATHER Overcast SPECIMEN STORAGE ASTM C31
POUR LOCATION Slab number 11,
Set 1
LOAD 2 SAMPLED From southwest comer.
TEST
DATE
11-17-08
12-08-08
12-08-08
Hold
AGE
(DAYSl
7
28
28
AREA
(IN,')
12.43
WEIGHT
(LBS)
8.4
TOTAL
LOAD (LBSI
55300
COMPRESSIVE
STRENGTH (PSIl
4450
AVERAGE
STRENGTH
(PSIl
TIME OF
TEST
9:15AM
TYPE OF
FRACTURE"
5
"'*1 - End Cones
2 - Cone/Split
3 - Columnar
4 - Diagonal
5 - Side (top and bottom)
6 - Side (top or bottom)
REMARKS: Mike Stickling (EWEB) and Jake Stucky (Wildish) was advised of on-site test results,
Reviewed By:
::a:I~~
Technical Man,ager
c:
EWEB- Mike Sticklin9,(email)
EWEB- Wally McCullough (email)
OBEC- Pete Slocum (email)
Wildish Building Co,- Kevin Fitzjarrell (email)
Wildish Building Co,- Jake Stucky (email)
City of Springfield
Knife River
MLM:sc
This report and/or enclosed.test'data,is, the r.onfidential property of the client to whom it is addressed and pertains .to the specific
process and/or material evaluated. As such, information contained herein shall not be reproduced in part or full and/or any part
thereof be disclosed without FEI Testing & Inspection, Inc.'s written authorization.
7m NoN CanelIAvenue' Cavaffis, Oregon 97330, pha1e (541) 757-4698, fax (541) 757-2991
29540 BAirport Rood, Eugene, Oregon 97402' pha1e (541)684-3849' fax (541) 684-3851
630m Corporate Place, Suite 2 ' Bend, Oregon 97701 ' phone (541) 382-4844 ' fax (541) 382-4846
~ftl
Page 1 of 2
11~'llllC'l;"J~~'~:'IIII~'al~l.
Gbv,~ " ,leal & ConstrucIioo Services
Daily Field Report
Client: EWEB Project: Hayden Bridge Water Filtration Date: 10-27 & 28-08
500E. 4'h Ave, Plant Expansion Project No.: 2087168
Eugene, Oregon Springfield, Oregon Report No.: E-21647
Inspector: A, Fenstermacher
10 No.: 5258882-49
ICC
Inspection of: Reinforcing Steell
Reinforced Concrete Weather: Clear/Fog Continuous Inspection: 0
Contractor: Wildish BPNo.: 2008-00225 ' Periodic Inspection: ItJ
10-27-08: Performed inspection on the reinforcing steel for slab numbers 3, 4 ahd 5,
Reinforcing steel was checked for size, grade, laps, quantities, locations, ties,
clearance and supports, ,A final inspection will be performed prior to concrete
placement. '
10-28-08: Performed final inspection on the reinforcing steel for siab numbers 3, 4 and
5,
Observed the placement of 75 cu/yds, of Knife River 4000 psi concrete (mix
2440K1 UOZF) into areas noted above, Concrete was placed by pump and was
mechanically consolidated, Tested load 1 and 2 before placement to verify compliance
with mix design parameters,
I Load 1
I Concrete temperature- 66F
I Air temperature- 48F
I Slump- 5 1/2"
I Air content- 4.4%
Load 2
Concrete temperature- 68F
Air temperature- 48F
Slump- 41/2"
Air content- 4,0%
This report and/or enclosed test data is the confidential'property of the client to whom it is addressed and pertains to the specific
process and/or material evaluated. J As such, information contained herein shall not be reproduced in part or full and/or any part
thereof be disclosed without, FEI Testing & Inspection, Inc,'s 'Mitten authorization.
700 rwv Canell Avenue' CorvaI~, Qegx197330' phone (541) 757-4698, fax (541) 757-2991
29540 BAirportRoad 'Eugene, Qegx197402' phone (541) 684-J849 ,fax (541)684,3851
63050 Corporate Place, Suite 2. Bend, Oregon 97701 'phone (541) 382-4844, fax (541) 382-4846
'-
Hayden Bridge
Water Filtration
Springfield, Oregon
Project No.: 2087168
Report No.: E21647
10-27 & 28-08
Page iof 2
Cast one (1) set of four (4) 4" x 8" concrete test .cylinders from load 7. Notified Mike
Stickling (EWEB) and Jake (Wildish) of on-site results. Concrete temperature- 68F; air
temperature- 53F; slump- 61/2"; air content- 5.0%.
Contractor was asked to notify our office when additional services are needed.
To the best of our knowledge, the work inspected was in accordance with plans dated
02/2008 and applicable workmanship provisions of the I.B.C., except if noted above.
Reviewed By:
/lJ.'?(.~
Michael L. yer
Technical nager.
c:
EWEB- Mike Stickling (email)
EWEB- Wally McCullough (email)
OBEC- Pete Slocum (email)
Wildish Building Co.- Kevin Fitzjarrell (em ail)
Wildish Building Co.- Jake Stucky (em ail)
City of Springfield
/
MLM:sc
This report and/or enclosed test data is the confidential property of the client to whom it is addressed and pertains to the specific
process and/or material evaluated. As such, information contained herein shall not be reproduced in part or full and/or any part
thereof be disclosed without FEl Testing & Inspection, Inc,'s Written authorization.
'-"--""~!y.'-' -~""'.'~...-~,~"'9" --..-- - --....,........,.~. '""7' ...,.,.,.~.",- ....,~~---,. --
7fIJ NW CaneII Avenue' CavaIis, Oregm 97330' phone (541) 757-4698, fax (541) 757-2991
29540 BAirport Road . Eugene, Oregm 97402 . phone (541) ~ . fax (541) 684J851
63050 Corporate Place, Suite 2 . Bend, Oregon 97701 . phone (541) 382-4844 . fax (541) 382-4846
~fEt
'1;"IIIII'I;.II\.'~I'lllhl.l~l_
CLIENT
EWEB
500E. 4th Ave.
Eugene, Oregon
DATE CAST
STRENGTH REQUIRED
STRENGTH PLACED
PRODUCT CODE
ADDITIVES
LOAD NO.
CONCRETE TEMP
AIR TEMP
POUR LOCATION
LOAD 1 SAMPLED
TEST
DATE
10-28-08
11-18-08
11-18-08
Hold
AGE
(DAYS)
7
28
28
Geotechnical & Construclion Servires
Compressive Strength of Concrete
(ASTM C 39) .
PROJECT
DATE
PROJECT NO.
REPORT NO.
10-28-08
2087168
.6072
Hayden Bridge Water
Filtration Plant Expansion
Springfield, Orego~
B.P. NO.
2008-00225
10-21-08 CAST BY J. Keller DATE RECEIVED
4000 psi SPECIMEN SIZE
4000 psi SACKS SUPPLIER
2440KIUOZF CEMENT MAX SIZE AGG.
Adva, Eclipse, Fiber AIR CONTENT
4 (1" accepted) TICKET NO. 3159951 SLUMP
680 F YARDAGE 10.00 OF TIME
530 F WEATHER Clear SPECIMEN STORAGE.
Footing/Slab 1 and 2 east wall and spread footing .number 8 north wall.
Near SE corner of footing 1 slab #1. .
AREA
(IN.')
12.56
WEIGHT
(LBSl
8.4
TOTAL
LOAD (LBSl
53400
COMPRESSIVE
STRENGTH (PSIl
4250
AVERAGE
STRENGTH
(PSIl
TIME OF
TEST
12:45 PM
I
10-22-08
4" x8"
Knife River
3/4"
5.0%
51/4"
12:10 PM
ASTM C31
TYPE OF
FRACTURE~
6
**1 - End Cones. 2 - Cone/Split
3 - Columnar
4 - Diagonal
5 - Side (top and bottom)
6 - Side (topor bottom)
REMARKS: Mike Stickling (EWEB) was advised of on-site test results.
Reviewed By'
/h.~.~-
Michael L. ';eyetl'"
Technical Manager
c:
EWEB- Mike Stickling (email)
EWEB- Wally McCullough (em ail)
OBEC- Pete Slocum (em'ail)
Wildish Building Co.- Kevin Fitzjarrell (email)
Wildish Building Co.- Jake Stucky (emall)
City of Springfield .
'Knife River
MLM:
This report and/or enclosed test data is the confidential property of the client to lNhom it ;s addressed and pertains to the speCific
process and/or material evaluated. As such, information contained herein shall not be reproduced in part or full and/or any part
thereof be disclosed.without,FE! Testing & Inspection, lnc.'s written autho~zatjon..
7!'IJ NW CaneIIAvenue' CavaJIs, 0eg:Jn 97330, phone (541) 757-4698, fax (541) 757-2991
29540 B Airport Road . Eugene, Qegon 97402, phone (541) 684-3849 . fax (541) 684J851
63050 Corporate Place. Sulle 2 . Bend, Oregon 97701 . phone (541) 382-4844 . fax (541) 382-4846
{4Ftl
Geotechnical & ConsIn.K:fun Services
11~'II~ler:"lf~'~~'II'III.lue!l
CLIENT
PROJECT
EWEB
500E. 4th Ave.
Eugene, Oregon
B.P. NO.
DATE CAST
STRENGTH REQUIRED
STRENGTH PLACED
PRODUCT CODE
ADDITIVES
LOAD NO.
CONCRETE TEMP
AIR TEMP
POUR LOCATION
10-28-08 CAST BY
4000 psi
4000 psi . SACKS.
2440KIUOZF CEMENT
ADVA, Eclipse, Fiber
7 TICKET NO.
680F YARDAGE
530 F WEATHER
Slab numbers 3, 4 and 5.
LOAD 7 SAMPLED
From slab 5, northeast comer.
TEST
DATE
11-04-08
11-25-08
11-25-08
Hold
AREA
(IN')
12.50
TOTAL
LOAD (LBS)
57800
AGE
(DAYS)
7
28
28
WEIGHT
(LBSl
8.4
"1 ~ End Cones 2 - Cone/Split
3.;.;. Columnar
REMARKS: Jake (Wildish) was advised of on-site test results.
Reviewed By:
;11.7(. ~
Michael L. ~ey{;l
Technical Manager
c:
EWEB- Mike Stickling (emaii)
EWEB- Wally McCullough (email)
OBEC- Pete Slocum (email)
Wildish Building Co.- Kevin Fitzjarrell (emaii)
Wildish Building Co.- Jake Stucky (email)
City of Springfield
Knife River
MLM:sc
Compressive Strength of Concrete
(ASTM C 39)
Hayden Bridge Water
Filtration Plant Expansion
Springfield, Oregon
2008-00225
A. Fenstermacher
3160042
10.0 OF 75.0
Fog
COMPRESSIVE
STRENGTH (PSn
4620
DATE
PROJECT NO.
REPORT NO.
DATE RECEIVED
SPECIMEN SIZE
SUPPL!ER
. MAX SIZE AGG.
AIR CONTENT
SLUMP
TIME
SPECIMEN STORAGE
AVERAGE
STRENGTH
(PSn
TIME OF
TEST
3:30 PM
I
I
11-04-08
2087168
6092
10-29-08
4" x 8"
Knife River
3/4"
5.0%
6 1/2"
11:00AM
ASTM C31
TYPE OF
FRACTURE-
5 I
I
I
I
4 - Diagonal
5 - Side (top and bottom)
6 - Side (top or bottom)
RECEIVEr.'
NDV.O 6 7nnR
This report and/or enclosed test data is the confidential property of the client to ~om itis addressed and pertains to the specific
process and/6rmaterial evaluated. As such, information contained herein shal! not be ~eprodL:ced in,part odulLand/or any parL
thereof be disclosed without FEI Testing & Inspection, -Inc.'s Written authorization.
7fIJ NW ComeIIAvenue' CorvaIfIS, Qegon 97330. phone (541) 757-4698. fax (541) 757-2991
29540 B Airport Road . Eugene, 0e<;p197402 . phone(541)61J4.J849 . fax (541) 684J851
63050 Corporate Place, Suite 2 . Bend, Oregon97701 'phone (541) 382-4844 . fax (541) 382-4846
~..=~~
~,,_l
Page 1 of 2
11~'mlCi;"ll..'~~'IIII1'_
ec-..k:; ,,1ical & ConslJuc:fun Services'
Daily Field Report
Client: EWEB Project: Hayden Bridge Water Filtration Date: 11-03 & 04-08
,
500E. 4th Ave. Plant Expansion Project No.: 2087168
Eugene, Oregon Springfield, Oregon Report No.: E21713
Inspector: A. Fenstermacher
ID No.: 5258882-49
ICC
Inspection of: Epoxy/Reinforcing Steel &
Reinforced Concrete Weather: Showers Continuous Inspection: 0
Contractor: Wildish Construction Co. BPNo.: 2008-00225 Periodic Inspection: iii
11-03-08: Performed continuous inspection during the installation of ten (10) 3/4" x 28"
horizontal and vertical stainless steel all thread anchors into existing buttress at the
southeast corner of contact basin for new wall tie-in. Prior to installation, the predrilled
holes were cleaned using compressed air and a brush. Verified minimum embedment
of 7". Anchors were secured with Epcon A7 (ICC-ES ESR- 2351, expiration date
11/2009). .
11-04-08: Performed inspection on the reinforcing steel for slab numbers g and 10.
Reinforcing steel was checked for size, grade, laps, quantities, locations, ties,
clearance and supports. .
Observed the placement of 60 cu/yds. of Knife River 4000 psi concrete (mix
40K1 UOZF) into areas noted above. Concrete was placed by pump and mechanically
consolidated. Test load 1 and 2 for compliance with mix design.
I Load 1
I Concrete temperature- 64F
I Air temperature- 41 F
I Slump- 61/2"
LAir content- 6.3%
Load 2
Concrete temperature- 62F
Air tem~erature- 50F
Slum p- 5 3/4" ,
, Air content~ 5.0%
This report and/or enclosed test data is the confidential property of the client to whom it is addressed and pertains to the specific
process and/or material evalu"ated. As such,' information" contained herein shall not'tie reproduced in parra; fulf and/Of any part
thereof be disclosed without FEI Testing & Inspection, lnc:'s written authorization. .
750 NW Cornell Avenue' Corvallis, 0regx197330' phone (541) 757-4698, fax (541) 757-2991
29540 B Airport Road, Eugene, 0regx197402 . phone (541)6843849 . fax (541) 684-3851
63050 Corporate Place, Suite 2 . Bend, Oregon 97701 . phone (541) 382-4844 . fax (541) 382-4846
Hayden Bridge Water
Filtration Plant Expansion
Project No.: 2087168
Report No.: E-21713
'11-03 & 04-08
Page 2 of 2
Cast .one (1) set of four (4) 4" x 8" concrete test cylinders from load 6. Notified Jake
Stucky (Wildish) of on-site results. Concrete temperature!' 66F; air temperature- 50F;
slump- 5 1/2"; air content- 4.0%
Mr. Stucky was asked to notify our office when additional services are needed.
To the best of our knowledge, the work inspected was in accordance with pians dated
02/2008 and applicable workmanship provisions ofthe I.B.C., except if noted above.
R~~e~y: .
Michael L. ~
Technical ~:~aer
c:
EWEB- Mike Stickling (email)
EWEB- Wally McCullough (email)
OBEC- Pete Slocum (emaii)
Wildish Building CO.- Kevin Fitzjarrell (email)
Wildish Building CO.- Jake Stucky (email) .
City of Springfield
MLM:sc
This report and/or enclosed test data is the confidentialPFoper!Yof the client to. wh.o!TI it is addressed and pertains to the specific
process and/or material"evaluatea. -As such, information. contained herein shall not be" reproduced in part or full'and/or any part
thereof be disclosed without FEI Testing & Inspection, Inc.'s written authorization. .
7fIJ NW CanelIAvenue' OlrvaIlis, Oregm 97330 'phone(541) 751-4698' fax (541) 757-2991
29540 B Airport Road . Eugene, Oregm 97402 . phone (541) 664J849 . fax (541) 684J851
63050 Corporate Place, Suite 2 . Bend, Oregon 97701 . phone (541 i 382-4844 . fax (541 ) 382-4846
~fEJ
1I~"I>'lrt:tll~m'III11.llllJl Geotechnical & Construcfun Servires
Page 1 of 1
Field Density Test Results - ASTM D 2922
Client: EWEB
500 E. 4th Ave.
Eugene, Oregon 97440
Project: Hayden Bridge Water Filtration
Plant Expansion.
Springfield, Oregor
Date:
Project No.:
Report No.:
B.P. No,:
1 0-30-08
2087168
E-21686
2008-00225
\.
MOISTURE/DENSITY DATA: ASTM 0698 - Maximum Dry Density of 129.5 pcf, at 11.0% moisture, is from our sample
no. 1934 dated 08-15-08 for 3/4"-0 (Wildish).
.n-=;;
Test Approximate Location
No.
I 1 J Near center slab #10
Approx.
Elev.
FG
Wet
Density
(pcfl
134.1
. Percent
Moisture
3.5
Dry Density
(pcfl
129.6
Percent.
Compaction
100.0
Compaction
Requirement
95.0 I
Test performed at finished grade of base rock under thickened area of contact basin slab..
Note: Base rock thickness appears to be less than 4" in other areas of siab. Conventional procedures will not provide
consistent or reliable test results on thin lifts of materials.
Remarks: Jake Stucky (Wildish) was advised of test results.
Reviewed By:
A.<-j{.~
Michael L. Me#
Technical Manager
c:
EWEB-Mike Sticking (em ail)
EWEB- Wally McCullough (email)
OBEC- Pete Slocum (email)
Wildish Building Co.- Kevin Fitzjarrell (em ail)
Wildish Building Co.- Jake Stucky (email)
City of Springfield
MLM:sc
Tlus report and/or enclosed test data'is the coil1idential property of the client to whom it is addressed and pertains to thespecilic process'andlor"mitterialevaluated. As such, infonnation
contained herein, shatlnot be reproduced in part of fun and/or any part thereof be disclosed without FE' Testing & Inspection, Inc. 's written authorization.
750NW OlnellAvcrrue. Corvallis, Oregon 97330. phone(541) 757-4ffJ8. fux (541) 757-ml
29540 B Airpat RoOO' Eugene, Oregon 97402 . Jfure(54!)684-3849' fux (541)684-3851
63050 COl1JOrate Place, Suite 2 . Bend, Oregon 97701' phone (541) 38,2-4844 . fax (541) 382-4846
~ftl
Page 1 of 1
11~'lI!lrt;41~..'~~'llll~_
Gcv~ ,,1ica1 & Construction Services
Daily Field Report
Client:
EWEB
500E. 4th Ave.
Eugene, Oregon
Project:
Hayden Bridge Water Filtration
Plant Expansion
Springfield, Oregon
Date:
Project No.:
Report No.:
Inspector:
10 No.:
11-06-08
2087168
E-21726
A. Fenstermacher
5258882-49
ICC
Inspection of: Reinforcing Steei
Contractor: Wildish Construction
Weather: Showers
BP N<?: 2008-00225
Continuous Inspection: 0
" Periodic Inspection: Ii!
Performed preliminary inspection on the reinforcing steel for wall number 25.
Reinforcing steel was checked for size, grade, laps, quantities, locations, ties,
.clearance 'and supports.. A final inspection will be performed prior to concrete
placement.
Contractor was asked to notify our office when additional services are needed.
To the best of our knowledge, the work in-progress was in accordance with RFI #47
dated 10-28-08, plans dated 02/2008 and applicable workmanship provisions of the
I.B.C., except if noted above.
Reviewed By:
jJJ.'i.~
Michael L. Meye?J
Technical Manager
c:
EWEB- Mike Stickling (email)
EWEB- Wally McCullough (email)
OBEC" Pete Slocum (email)
Wiidish Building Co.- Kevin Fitzjarreli (email)
Wildlsh Building Co.- Jake Stucky (email)
City of Springfield
This report and/or enclosed test data is the confidential property of the client to whom it ;s addressed and pertains to the specific
process and/or material evaluated. As such, information.contained herein shall not be reproduced in part or full and/or any part
thereof be disclosed without FEI Testing & Inspection, Inco's written authorization.
~wm.
tMW 011J 700gQ
RECEIVED
NOV 1 0 zooa
MLM:sc
7fIJ NW CaneII Avenue. Cavallis, Oegon 97330, phone (541) 757-4698, fax (541) 757-2991
29540 B Airport Reed . Eugene, Oegon 97402 . phone (541) 684J849 . fax (541) 684J851
63050 Corporate Place, Suite 2 . Bend, Oregon 97701 . phone (541) 382-4844 . fax (541) 382-4846
~ftj
lI~'""":.t"mllllt'."t" .Geotechnical & Construction SeNices
Page10f1'
Report of Inspection Services
Weldina/Hi~h-Str:enath Boltina
Client: EWEB
500E. 4th Ave.
Eugene, Oregon
Project:
Hayden Bridge Water
Filtration Plant Expansion
Springfield, Oregon
Date:.
Project No.:
Report No.:
Inspector:
ID No.:
Inspection of:
Fabricator or Erector:
Contractor:
Welding
Knife River
Wildish Construction Co.
.
Shop: ,~
Weather:
BPNo.: .
.11-07-08
2087168
E-21749
C. Walpole
01040131
AWS CWI
Field: 0
Inside
2008-00225
Performed visual inspection on forty-eight (48) fabricated structural steel embeds P101. DBA's were
checked for 360" flash and by ring/bend test.
Fabricator was asked to notify our office when additional services are needed.
To the best of our knowledge, the work checked is in conforman~e with shop drawings dated 10-30-08
and applicable AWS 01.1 code, except if noted above.
RC:;;;1tlc
Michael L. Meyer ~
Technical Manager
c:
EWEB- Mike Stickling (email)
EWEB- Wally McCullough (email)
OBEC- Pete Slocum (email)
Wildish Building Co.- Kevin Fitzjarrell (em ail)
Wildish Building Co.- Jake Stucky (em ail)
City of Springfield
RtCt/t;
NO/l tl)
10 ![J(JO
;"test data is the confidential property of the cli~nt to whom iUs addressed and pertains "to the,specific
.:tluated. As such, information contained herein s.hall not be reproduced in part or fulland/or any part
.ereof be disclosed without FEI Testing & Inspection, Inc.'s Written authorization.
/
_//comeIlAvenue. Corvallis, Oregon 97330, phone (541) 757-4698. fax (541) 757-2991
,AD B Airport Road, Eugene, Oregon 97402 . phone (541) 6~9 . fax (541) 684-3851
/.;0 Corporate Piace, Suile 2 . Bend, Oregon 97701 . phone (541) 382-4844 . fax (541) 382-4846
~fE}
Page 1 of 1
11;"'IINrt;'liII~"'~="lllu.m,
Geoted1nica1 & Construction Servia3s
Daily Field Report
Client: EWEB Project: Hayden Bridge Water Filtration Date: 11-07-08
500E. 4th Ave. Plant Expansion Project No.: 2087168
Eugene, Oregon Springfield, Oregon Report No.: E-21750
Inspector: A. Fenstermacher
10 No.: 5258882-49
ICC
Inspection of: Reinforcing Steel Weather: Showers Continuous Inspection: 0
Contractor: Wildish Construction Co. BPNo.: 2008-00225 Periodic Inspection: Ii'!
Performed preliminary inspection on the reinforcing steel for slab #11. Reinforcing
steel was checked for size, grade, laps, quantities, locations, ties, clearance and
supports. A final inspection will be preformed prior to concrete placement.
To the best of our knowledge, the work inspected was in accordance with plans dated
02/2008 and applicable workmanship provisions of the I.B.C., except if n.oted above.
R~j .
Michael L..Meyer k
Technical Manager
-----...,
c:
EWEB- Mike Stickling (em ail)
EWEB- Wally McCuilough (email)
OBEC- Pete Slocum (em ail)
Wild ish Building Co.- Kevin Fitzjarrell (email)
Wildish Buildin9 Co.- Jake Stucky (em ail)
City of Springfield
MLM:sc
This report and/or enclosed test data is the confidential property of the client to whom it is addressed and pertains to the specific
process andlor material evaluated. As such, infonnation contained herein shall not ~e reproduced in part or full and/or any part
. thereof be disclosed without FEI Testing & Inspection, Inc.'s written authorization.
. 7fIJ rm CaneII Avenue' CavalfIS, Oegon 97330, phone (541) 757-4698 . fax (541) 757-2991
29540 BAirportRoad. Eugene, Oregm 97402, phone (541)684-3849' fax (541 )684J851
63050 Corporate Place, Suite 2 . Bend, Oregon 97701 . phone (541) 382-4844 . fax (541) 382-4846
~..p.
~rt~
Page 1 of 1,
1I:lro'II~'lrt;4im~';j;'Il'J~.ltltl
Geoted1nical & Cons1ruclion Servires
Daily Field Report
Client: EWEB Project: Hayden Bridge Water Filtration Date: 11-25"08
500E. 4th Ave. Plant Expansion Project No.: 2087168
Eugene, Oregon Springfield, Oregon Report No.: E-21882
Inspector: A. Fenstermacher
ID No.: 525882-49
ICC
'.
Inspection of: Reinforcing Steel Weather: Overcast Continuous Inspection: 0
Contractor: Wildish Construction BPNo.: 2008-00225 Periodic Inspection: 0
Performed preliminary inspection on the reinforcing steei for wall numbers 22 and 27.
Reinforcing steel was checked for size, grade, laps, quantities, locations, ties,
ciearance and supports. A final inspection wiil be performed prior to concrete
placement.
',,"\;h.'i'. .
r .' Jake, Stucky (Wild ish) was asked to notify our office when additional services are
needed.
To the best of our knowledge, the work in-progress was in accordance with plans dated
02/2008 and applicable workmanship provisions of the I.B.C., except if noted above.
Reviewed By:
1l~~~
Technical Manager
c:
EWEB- Mike Stickling (em ail)
EWEB- Wally McCullough (em ail)
OBEC- Pete Slocum (email)
Wildish Building Co.". Kevin Fitzjarrell (emaii)
Wildish Building CO.- Jake Stucky (em ail)
City of Springfield
"'. ,
l"
.,
MLM:sc
RECE\\JEO
IlE\:. ~ ~ 100~
This report and/or enclosed test data is the confidential property of the client to whom it is addressed and pertains to the specific
process and/or material evaluated. As such, information contained herein shall not be reproduced in part or futl andfor any part
thereof be disclosed without FEI Testing & Inspection, Inc.'s written authorization.
750 NW CaneII Avenue. CavaI~s, Oregon 97330, phone (541) 7574698. fax (541) 757-2991
.29540 BAirportRoad . Eugene, Oregon 97402, phone (541)684:3849' fax (541 )684.Ja51
63050 Corporate Place, Su~e2' Bend, Oregon 97701. phone (541) 382-4844. fax (541) 382-4846
~",p~
~yrtl
'1~'mlrt;"I~~'~;'IIII1I.m.
CLIENT
EWEB
500E. 4th Ave.
Eugene, Oregon
DATE CAST
STRENGTH REQUIRED
STRENGTH PLACED
PRODUCT CODE
ADDITIVES
LOAD NO.
CONCRETE TEMP
AIR TEMP
POUR LOCATION
LOAD 7 SAMPLED
Cc.v~',,1icill & Construclion Servioos
Compressive Strength of Concrete
(ASTM C 39)
PROJECT
DATE
PROJECT NO.
REPORT NO.
11-25-08
2087168
6092
Hayden Bridge Water
Filtration Plant Expansion
Springfield, Oregon
B.P. NO.
2008-00225
10-28-08 CASt BY
4000 psi
4000 psi SACKS
2440KIUOZF CEMENT
ADVA, Eclipse, Fiber
7 . TICKET:NO.
68"F YARDAGE
53" F WEATHER
Slab numbers 3, 4 and 5.
DATE RECEIVED
SPECIMEN SIZE
SUPPLIER
MAX SIZE AGG.
AIR CONTENT
SLUMP
TIME
SPECIMEN STORAGE
10-29-08
4" x8"
Knife River
3/4"
5.0%
61/2"
11:00AM
ASTM C31
A. Fenstermacher
3160042
10.0 OF 75.0
Fog
From ~Iab 5, northeast corner.
AVERAGE
TEST AGE AREA WEIGHT TOTAL COMPRESSIVE STRENGTH TIME OF TYPE OF
DATE (DAYS) (IN.') (LBSI LOAD (LBSI STREN'GTH (PSI) (PSI) TEST FRACTURE"
11-04-08 7 12.50 8.4 57800 4620 3:30PM 5 I
11-25-08 28 12.56 8.4 72000 5730 8:10AM 5 I
11-25-08 28 12.56 8.4 75000 5970 5850 8:15AM 5 I
Hold I
"*1 - End Cones 2 - Cone/Split 3 - Columnar 4 - Diagonal 5 - Sid,e (top and bottom) 6 - Side (top orbqttom)
REMARKS: Jake (Wildish) was advised of on-site test results.
Reviewed' By:
!!L~'/:o
Technical Manager
c:
EWEB- Mike Stickling (email).
EWEB- Wally McCullough (email)
OBEC- Pete Slocum (email)
Wildish Building Co.- Kevin Fitzjarrell (email)
Wildish Building Co.- Jake Stucky (email)
City of Springfield
Knife River
MLM:sc
This report and/or enclosed test data is the confidential property of the client to Whom it is addressed and pertains 'to the specific
process and/or material evaluated. As such, information contained herein shall not be reproduced in part or full and/or any part
thereof be disclosed without FEl Testing & Inspection, Inc:'s written authorization.
7fIJ NW CanellAvenue' ConIaIJis, Oregm 97330, phone (541) 757-4698. fax (541) 757-2991
29540 BAirportRoad' Eugene, Oregm 97402, phone (541)684-J849' fax (541) 684J851
63050 Corporate Place, Suite 2 . Bend, Oregon 97701 . phone (541) 382-4844 . fax (541) 3824846
SfEt
GeotEchnical & Construction Servires
Compressive Strength of Concrete
(ASTM C 39) .
11a.'II~lrt;.IN.'~I'IIII~III~l.
CLIENT
EWEB
500E. 4th Ave.
Eugene, Oregon
PROJECT
Hayden Bridge Water
Filtration Plant Expansion.
Springfieid, Oregon
DATE
PROJECT NO.
~EPORT NO.
11-26-08
2087168
6118
B.P. NO.
2008-00225
DATE CAST 11-19-08 CAST BY A. Fenstermacher DATE RECEIVED 11-20-08
STRENGTH REQUIRED 4000 psi SPECIMEN SIZE 4" x 8"
STRENGTH PLACED 4000 psi SACKS SUPPLIER Knife River
PRODUCT CODE 40K1UOZF CEMENT MAX SIZE AGG. 3/4"
ADDITIVES Adva, Eclipse, Fiber AIR CONTENT 4.9%
LOAD NO. 6 TICKET NO. 3160320 SLUMP 61/2"
CONCRETE TEMP 69" F YARDAGE 10.0 OF 65.0 TIME 12:10 PM
AIR TEMP 60" F WEATHER Overcast SPECIMEN STORAGE ASTM C31
POUR l;.OCATlON Slab numbers 19 and 17.
Set 1
LOAD 6 SAMPLED From southwest comer of slab 19.
TEST
DATE
11-26-08
12-17-08
12-17-08
Hold
AGE
(DAYSl
7
28
28
AREA
(IN').
12.56
WEIGHT
(LBSl
8.3
TOTAL
LOAD (LBSI
51700
COMPRESSIVE
STRENGTH (PSI)
4120
AVERAGE
STRENGTH
(PSI)
.TIME OF
TEST
8:00 AM
TYPE OF
FRACTURE-
5 I
I
I
J
H1_ End_Cones
2- COile~Split
3 ~ Columnar
4 - Diagonal
5 - Side (top and bottom)
6 - Side (top or bottom)
REMARKS: Jake Stucky (Wildish) was advised of on-site test results.
Reviewed By:
A.'ilfwv--
Michael L~ ~r
Technical Manager
c:
EWEB- Mike Stickling (email)
EWEB- Wally McCullough (em ail)
OBEC- Pete Slocum (email)
Wildish Building Co.- Kevin Fitzjarrell (email)
Wildish Building Co.- Jake Stucky (email)
City of Springfield
Knife River
MLM'sc
Thisreportandlor enclosed test data is the confidential property of the client to whom it is addressed and pertains to the specific
process and/or material evaluated. As such, information contained herein shall not be reproduced in part or full and/or any part
thereofbedisclosed without FEl Testing & Inspection, loco's 'Mitten authorization.
7"'IJ NW Cornell Avenue . Cavallis, Qeg:ln 97330 . phone (541) 757-4698 . fax (541) 757-2991
29540 BAirport Road, Eugene, Qeg:ln 97402. phone (541 )664'3849' fax (541)684J851
63050 Corporate Place. Suite 2 . Bend, Oregong7701 . phone (541) 382-4844 . fax (541) 382-4846
~fE'
11~"fllrt;"I~Iio'~i'IIIJ~_
CLIENT
EWEB
500E. 4th Ave.
Eugene, Oregon
DATE CAST
STRENGTH REQUIRED
STRENGTH PLACED
PRODUCT CODE
ADDITIVES
LOAD NO.
CONCRETE TEMP
AIR TEMP
POUR LOCATION
LOAD.4 SAMPLED
TEST
DATE
11-26-08
12-17-08
12-17-08
Hold
AGE
(DAYS)
7
28
28
*""1 - End Cones
Geotechnical & ConslrucOCin Servia3s
PROJECT
B.P. NO.
11-19-08
4000 psi
4000 psi
40-SE7
CAST BY
SACKS
CEMENT
Compressive Strength of Concrete
(ASTM C 39)
Hayden Bridge Water
Filtration Plant Expansion
Springfield, Oregon
DATE
PROJECT NO.
REPORT NO.
11-26-08
2087168
6119
Super, Eclipse
4 TICKET NO.
72" F YARDAGE
55" F WEATHER
Wall numbers 23 and 29.
Set 2
From 4th lift in walls.
AREA
(IN.')
12.56
TOTAL
LOAD (LBS)
56000
2008-00225
A. Fenstermacher
DATE RECEIVED
SPECIMEN SIZE
SUPPLIER
MAX SIZE AGG.
AIR CONTENT
SLUMP
TIME
SPECIMEN STORAGE
WEIGHT
(LBS)
8.5
2 - Cone/SP.Ut
3 - Columnar
3160336
10.0 OF 48.0
Overcast
COMPRESSIVE
STRENGTH (PSIl
4460
AVERAGE
STRENGTH
(PSI)
TIME OF
TEST
7:55 AM
11-20-08
4" x8"
Knife River
3/4"
4.2%
6"
4:00 PM
ASTM C31
TYPE OF
FRACTURE"
5
4 - Diagona!
5 - Side (top and bottom)
6 - Side (top or bottom)
REMARKS: Jake Stucky (Wildish) was advised of on-site test results.
Reviewed By:
/l1,~~
Michael L. Me~
Technical Manager
c:
EWEB- Mike Stickling (email)
EWEB- Wally McCullough (smail)
OBEC- Pete Slocum (email)
Wildish Building Co.- Kevin Fitzjarrell (email)
Wildish Building Co.- Jake Stucky (email)
City of Springfield
Knife River
MLM:sc
This report and/or enclosed test data is the confidential property of the client to whom it is addressed and, pertains to the specific
process and/or material evaluated. As such, information contained herein shall not be reproduced in part or full and/or any part
thereof be disclosed'without FEI Testing & Inspection, Inc.'s Written authorization.
750 NW ComeIIAvenue' Cavalis, Oregm 97330. phone (541) 757-4698, fax (541) 757-2991
29540 BAirportRoad . Eugene, O"egon 97402, phone (541)664J849' fax(541)684J851
63050 Corporate Place, Suite 2 . Bend, Oregon 97701 . phone (541)382-4844' fax (541) 382-4846