HomeMy WebLinkAboutPermit Field Test & Inspection Report 2008-12-10
.d"3=i. Information
I....:::." U 0 !l.7bBuild On
~In.""'... . C'. .,...., """, . 1I.,~",.;, ,I'"
Client:
Address:
;L?~
0~~'1
COMPRESSION REPORT
Springfield School District
525 Mill Street
Springfield, OR 97477
Project No.: 722-80173-119
Proj. Name: Thurston Elementary School
Date:
B.P. No.:
P.O. No.:
Cast By:
Location:
7345 Thurston Road
Springfield, Oregon
Placement Data:
Wail pour. between grid 5 and 6 on line L
Materi'al: 'Concrete
Field Test Data
Slump"(in.): ASTM C143 5"
Max. Aggr. Size: 3/4"
Air Content: ASTM C231
Air Temperature (F): 500
Material Temp. (F): ASTM C1064 62"
Max Temp (F):
IMin Temp (F):
Specimen Size: 4x8
Unit Weight (pcl): ASTM CI3B
Time Cast: 10:20 AM Curing Conditions:
Additives:
Results Reported'To: Contractor
Location Sampled At:
Center 2' from bottom
Oat. Cast: 11/11/08
Tick~t No.: IMlx No.:
3224898 40N1S200 .
_I 1....."'-
De~i9n Strength (osil:
Cylinder No.
08-3548
08-3549
08-3550
08'-3551
Test Date
11118/2008
12/9/2008
12/9/2008
Hold
koad:
Total:
Supplier:
Knife River
Yardage
Date Rec'd:
Weather:
1
6.5
11/12/08
Overcast
reouired 4.000
Compressive Strength Data ASTM C39
olaced 4.000
Age (days)
Field Cure
(days)
Lab Cure Diameter or Cross Sect. Area Cylinder WT. Camp. Strength
Dimensions Max. Load (Ibs.) Fracture Type ..
(days) (inches) (s.i.) (Ibs.) (pSi)
6 3.99 12.51 8.6 55,980 4,470 2
27 3.99 12.51 8.6 79,345 6,340 3
27 3.99 12.51 8.6 79,020 6,320 3
7
28
28
H
H
3 - Column.ar 4 ~ Diagonal w no cracking at ends
~. 1 -'Cone (bolh ends)' 2 - ConeNerifca(Cracks-(oneend)
Remarks:
c:
"
SPRINGFIELD OFFICE
1040 - A Shelley Street
Springfield, Oregon 97477
(541)746-9649. (541)746-7163 fax
December 10, 2008 CCB#176269
P0272-334-0809
Verlyn Bearden
f
ASTM
Test Time
Capping Metryod
:l C617'-tJ3
112:32 PM X
j11:49AM. X
111:53 AM I X
I I
C1231ctJ3
5 - Side frac ures'.(at 'top of bottom) 6 - Top'fractures (same as #5 but end of cylinder is pointed)
Respectfully Submitted,
R;SSiOUO~S Industries. Inc.
Ray~ Alipertj
Project Manager
T.HIS REPORT IS PROVIDED FOR THE INFORMA nON OF THE CLIENT ONL Y. THE REPRODUCTION OF THIS REPORT BY ANY METHOD; AND ITS TRANSMITTAL TO A THIRD PARTY BY ANY MEANS EXCEPT IN FULL, IS
PROHIBITED WITHOUT THE WRITTEN
PERMISSION OF PROFESSIONAL SERVICE INDUSTRIES.
KPFF - ugo.cosla@kpff.com
Hyland Construction - markb@jhconst.com
Milstead & Associates - angus@milstead.us
Mahlum - rberndt@mahlum.com
Robertson/Sherwood & Architects - dguadagni@robertsonsherwood.com
Springfieid School District - jsaracen@sps.lane.edu
Yolanda Bird - yolanda.bird@sps.lane.edu
City of Springfield
l..~;l Information
,.,~. .To Build On
Engineering . Consulting. Testing
DAILY FIELD REPORT
Date Performed:
Client:
November 26, 2008
Springfield School District
525 Mill Street
Springfield, OR 97477
Report Number:
722-80173-135
Project Name:
Thurston Elementary School
7345 Thurston Road
Springfield, Oregon
Project Location:
Building Permit No.: COM2008-00437
Type of Inspection: Epoxy
P.O. No.:
Weather:
P0272-334-0809
Overcast
Field Observations and Comments
Performed continuous inspection during the installation of #4 (floors) and #5 (walls) epoxied rebar doweis in the
following locations: Building #1 Kitchen and Music Rooms. Floor between kitchen and music room #4 rebar (19 east and
2 west). North wall of music room #5 rebar (2 center and 11 west). East wall of music room #5 rebar (14). East wall of
kitchen #5 rebar (10 north and 8 south). Floor between kitchen and commons area #4 rebar (4 east and 2 west). South
wall of commons area #5 rebar (30). Prior to installation the predrilled holes were cleaned using a nyion brush and
compressed air. Verified minimum embedment depth of 5 inches. The above listed epoxy anchors were installed using
Hilti Hit-Re 500-SD epoxy with ICC #2322' expiration: 9/2009. The epoxy anchors were installed in accordance
approved job-site plans and manufacturer's directions. Contractor was asked to notify our office when additional
services are needed. To the best of our knowledge, the work inspected above was in accordance with the building
department approved design drawings, specifications and applicable workmanship of the International Building Codes.
Inspector: Devon Hovis
CCB #176269
If you have any questions regarding this report, please feel free to contact us at 541-746-9649.
Respectfully Submitted,
'<:'J~~ Industries, Inc.
Raymond Aliperti
Project Manager
c: KPFF - ugo.costa@kpff.com
Hyland Construction - markb@jhconst.com
Miistead & Associates - angus@milstead.us
Mahlum - rberndt@mahlum.com
Robertson/Sherwood & Architects - dguadagni@robertsonsherwood,com
Springfield School District - jsaracen@sps.iane.edu
Yolanda Bird - yolanda.bird@sps.lane.edu
City of Springfield
THIS REPORT IS PROVIDED FOR THE INFORMATION OF THE CLIENT ONL Y. THE REPRODUCTION OF THIS REPORT, BY ANY METHOD, AND ITS TRANSMITTAL TO A THIRD
PARTY, BY ANY MEANS, EXCEPT IN FULL, WITHOUT THE WRITTEN PERMISSION OF PROFESSIONAL SERVICE INDUSTRIES, IS PROHIBITED.
Professional Service Industries, Inc.. 1040-A Shelley Street. Springfield, OR 97477. Phone 541f746-9649. Fax 541f746-7163
l..~ ., lrifonnation
"..,. .To Build On
Engineering. Consulring . Testing
DAILY FIELD REPORT
Date Performed:
December 8, 2008
Springfield School District-
525 Mill Street
Springfield, OR 97477
Report Number:
722-80173-148
Client:
Project Name:
Thurston Elementary School
7345 Thurston Road
Springfield, Oregon:
Project Location:
Contractor:
Fabricator:
Type of Inspection:
John Hyland
P.O. No:
Shop/ Field:
Weather:
P0272-334-0809
Field
Cloudy
Welding
Field Observations and Comments
Performed periodic visual inspection of the following items: Preliminary visual inspection of 2nd fioor deck welds and'
nelson studs at gridlines A to 0 from 5 to 8. At this time, nelson studs are completed and in accordance with project
plans. Weldments were inspected for size, length, profile and locations. To the best of our knowledge, the work
inspected is in conformance with the approved drawings, specifications and applicable AWS 01.1 and AWS 01.3 codes.
The Contractor was asked to notify our office when additional services are needed.
Inspector: Raymond Aliperti, Certification #1017075-86
eBB #176269
If you have any questions regarding this report, please feel free to contact us at 541-746-9649.
Respectfully Submitted,
Professional Service Industries, Inc.
~d~li~
Project Manager
c: KPFF - ugo.costa@kpff.com
Hyland Construction - markb@jhconst.com
Milstead.& Associates - angus@miistead.us
Mahlum - rberndt@mahlum.com
Robertson/Sherwood & Architects - dguadagni@robertsonsherwood.com
Springfield School District - jsaracen@sps.lane.edu
Yolanda Bird - yolanda.bird@sps.iane.edu
City of Springfield
THIS REPORT /s PROVIDED FOR THE INFORMATION OF THE CLIENT ONL Y. THE REPRODUCTION OF THIS REPORT, BY ANY METHOD, AND ITS TRANSMITTAL TO A THIRD
PARTY, BY ANY MEANS, EXCEPT IN FULL:W/THOUT THE WRITTEN PERMISSION OF PROFESSIONAL SERVICE INDUSTRIES, IS PROHIBITED.
Professional Service Industries, Inc.. 1Q40-A Shelley 'Street. Springfield, OR 97477 . Phone 541/746-9649 . Fax 541/746-7163
l...~;lInfonnation
",~. .To Build On
Engineering . Consulting . Testing
DAuL Y FiELD REPORT
Date Performed:
December 9, 2008
Springfield School District
525 Mill Street
Springfield, OR 97477
Report Number:
722-80173-149
Client:
Project Name:
Thurston Elementary School.
7345 Thurston Road
Springfield, Oregon
Project Location:
P.O. No.:
Type of Structure:
Type of Inspection:
P0272-334-0809
Permit No.:
Weather:
COM2008-00437
Clear
Reinforced Concrete
Field Observations and Comments
Performed visual inspection of reinforcing steel at the following locations: stage wall reinforcing at gridline E to E.l at 2 to
5 and curb reinforcing at gridline D tot D.3 at 2.5, D.5 to Eat 2.5, D to D.3 at 5.5 and D.5 to Eat 55 prior to piacement of
concrete also placed concrete at column pour backs at gridline D.2 at 5, D.4 at 5 and D.6 at 5. Reinforcing steel was
checked for grade, size, placement and clearances where appiicable. Reinforcing steel was secured using tie wire and
supported on piastic chairs. Reinforcing steel was placed in accordance with the latest revisions dated 5/1/08.
Performed visual inspection during placement of concrete in the iocations listed above. Concrete was placed by boom
pump and mechanically consolidated. Cast one (1) set of our four (4) (4x8) concrete test cylinders. Additional
Comments: Also placed concrete at the column pour backs at gridline C at 4, B at 6, B at 7, C at 6 and Cat 7.
Contractor was asked to notify our office when additional services are needed. To the best of our knowledge, the work
inspected above was in accordance with the building department approved design drawings, specifications and
appiicable workmanship provisions of the International Building Codes.
Tvoe of Material Set #1
Supplier Knife River
Mix# 40NI15200
Slump 41/4"
Air Content 1.7%
Ambient Temperature 51"
Material Temperature 62"
Time Placed 11 :45 AM
Design Strength (psi) 4,000
Number of Samples 4
Total Yardage Placed 10 3/4
Inspector: Glenn Meeks Jr, ICC #5071538-49
CCB# 176269
If you have any questions regarding this report, please feei free to contact us at 541-746-9649.
Respectfully Submitted,
P~~T\l~O)fstries, Inc.
Raymond V. Alipertj .
Project Manager
cc: KPFF - ugo.costa@kpff.com
Hyland Construction - markb@jhconst.com
Miistead & Associates - angus@milstead.us
Mahlum - rberndt@mahlum.com
Robertson/Sherwood & Architects - dguadagni@robertsonsherwood.com
Springfield School District - jsaracen@sps.lane.edu
Yolanda Bird - yoianda.bird@sps.laneedu
City of Springfield
THIS REPORT IS PROVIDED FOR THE INFORM/.. nON OF THE CLIENT ONL Y. THE REPRODUCTION OF THIS REPORT, BY ANY METHOD, AND ITS TRANSMITTAL TO A THIRD
PARTY, BY:ANY MEAN/i, t:XI..;!:::t-'! I/"II-ULL. WII HUUI I Ht:. WKII I t:.N r'cKM/:;':;'IUN VI- I-'KUrt:~;;'JUIW-\l ::>t:/"'rVI"c: If~UV;;' /r-\tt:::>, I,) r--rlvnIO/1 CI..I.
ProfeSSional Service .lndustnes, Inc.. 1040-A Shelley Street. Springfield, OR 97477 . Phone 5411746-9649 . Fax 5411746.7163
l~~;lInformation
,.,~. .To Build On
Engineering. Consulting . Testing .
0.1\ - l\31
DAILY FIELD REPORT
Date Performed:
Client:
December 9, 2008
Springfield School District
525 Mill Street
Springfield, OR 97477
Report Number:
722-80173-150
Project Name:
Thurston Elementary School
7345 Thurston Road/
Springfield, Oregon
Project Location:
Contractor:
Fabricator:
Type of Inspection:
John Hyiand
Axis Crane
Welding
P.O. No:
Shop/ Field:
Weather:
P0272-334-0809
Field
Inside
Field Observations and Comments
Performed periodic visual inspection of the following items: preliminary visual inspection on 1;;," long seam weids for
2nd floor decking from gridlines A to 0 between 5 and 8. Final inspection of seam weids to be performed prior to
piacement of concrete. Weldments were inspected for size, length, profile and locations. To the best of our knowiedge,
the work inspected is in conformance with the approved drawings, specifications and appiicabie AWS 01.1 and AWS
01.3 codes. The Contractor was asked to notify our office when additional services are needed.
Inspector: Raymond Aliperti, Certification #1017075-86
CBB #176269
If you have any questions regarding this report, please feel free to contact us at 541-746-9649.
Respectfully Submitted,
p'{)essi~~ar~ervice Industries, Inc.
R~i~
Project Manager
c: KPFF - ugo.costa@kpff.com
Hyland Construction - markb@jhconst.com
Milstead & Associates - angus@milstead.us
Mahlum - rberndt@mahlum,com
Robertson/Sherwood & Architects - dguadagni@robertsonsherwood.com
Springfieid School District - jsaracen@sps.lane.edu
Yolanda Bird - yolanda.bird@sps.lane.edu
City of Springfield
THIS REPORT IS PROVIDED FOR THE INFORMA TION OF THE CLIENT ONL Y. THE REPRODUCTION OF THIS REPORT, BY ANY METHOD, AND ITS TRANSMITTAL TO A THIRD
PARTY, BY ANY MEANS, EXCEPT IN FULL, WITHOUT THE WRITTEN PERMISSION OF PROFESSIONAL SERVICE INDUSTRIES, IS PROHIBITED.
Professional Service Industries, Inc. -1040-A Shelley Street. Springfield, OR 97477 ..Phone 541f746-9649. Fax 541f746-7163
l..~ ;ZInformation
II"'. .10 Build On
Engineering . Consulting . ~sting
DAiLY FIELD REPORT
Date Performed: December 4, 2008 Report Number: 722-80173-146
Client: Springfield School District Project Name: Thurston Elementary School
525 Mill Street \
Springfield, OR 97477 Project Location: 7345 Thurston Road
Springfield, Oregon
P.O. No.: P0272-334-0809 Permit No.: COM2008-00437
Type of Structure: Weather: Clear
Type of Inspection: Reinforced Concrete
Field Observations and Comments
Performed visual inspection of reinforcing steel at the following iocations: trash enciosure footing reinforcing prior to
placement of concrete. Reinforcing steel was checked for grade, size, placement and clearances where. appiicable.
Reinforcing steel was secured using tie wire and supported on concrete dobie blocks. Reinforcing steel was placed in
accordance with the latest revisions dated 5/1/08 (15/55;02, S106). Performed visual inspection during placement of
concrete in the locations iisted above. Concrete was placed by mixer chutes and mechanically consolidated. Cast one
(1) set of our four (4) (4x8) concrete test cylinders. Concrete was asked to notify our office when additional services are
needed.
Tvop. of Mahuial
Supplier
Mix#
Slump
Air Content
Ambient Temperature
Material Temperature
Time Placed
Design Strength (psi)
Number of Samples
Total Yardaqe Placed
Inspector: Glenn Meeks Jr, ICC #5071538-49
CCB# 176269
Set #1
Knife River
40NI15200
41/4"
1.7%
51'
62'
11:45AM
4,000
4
103/4
If you have any questions regarding this report, please feel free to contact us at 541-746-9649.
Respectfully Submitted,
p~nj-~ Industries, Inc
Raymond V. Aliperti
Project Manager
cc: KPFF - ugo.costa@kpff.com
Hyiand Construction - markb@jhconst.com
Milstead & Associates - angus@milstead.us
Mahlum - rberndt@mahlum.com
Robertson/Sherwood & Architects - dguadagni@robertsonsherwood.com
Springfield School District - jsaracen@sps.lane.edu
Yolanda Bird - yoianda.bird@sps.iane.edu
City of Springfield
THIS REPORT is PROVIDED FOR THE INFORMATION OF THE CLIENT aNL Y. THE REPRODUCTION OF THIS REPORT, BY ANY METHOD, AND ITS TRANSMITTAL TO A THIRD
PARTY, BY ANY MEANS, EXCEPT IN FULL, WITHOUT THE WRITTEN PERMISSION o,~ PRO,r:ESSIONAL SERVICE INDUSTRIES. IS PROHIBITED
Professional Servic~ Industries, Inc. .1040-A Shelley Street. Springfield, OR 97477- Phone 541/746-9649. Fax 541/746.7163
l rta ~ ;ZInjormation
",~. .10 Build On
Engineering . Consulting. Testing
DAILY FIELD REPORT
Date Performed:
December 3, 2008
Springfield School District
525 Mill Street
Springfield, OR 97477
Report Number:
Client:
Project Name:
Project Location:
Contractor:
Fabricator:
Type of Inspection:
John Hyland
P.O. No:
Shopl Field:
Weather:
Welding
722-80173-145
Thurston Eiementary School
7345 Thurston Road.
Springfield, Oregon
P0272-334-0809
Field
Cloudy
Field Observations and Comments
Performed periodic visual inspection of the following items: single pass weids and steel studs for 2nd floor deck gridline
A to D from 5 to 8 and single pass welds and steel studs for roof deck gridline C to D from 5 to 6. Weldments were
inspected for size, length, profile and iocations. To the best of our knowledge, the work inspected is in conformance
with the approved drawings, specifications and applicable AWS D1.1 codes. The Contractor was asked to notify our
office when additional services are needed.
Inspector: Raymond Aliperti, Certification #1017075-86
CBB #176269
If you have any questions regarding this report, please feel free to contact us at 541-746-9649.
Respectfully Submitted,
p~:J~ra1fndustries, Inc.
Raymond Alipertl
Project Manager
c: KPFF - ugo.costa@kpff.com
Hyland Construction - markb@jhconst.com
Milstead & Associates - angus@milstead.us
Mahlum - rberndt@mahlum.com
Robertson/Sherwood & Architects - dguadagni@robertsonsherwood.com
Springfield School District - jsaracen@sps.lane.edu
Yolanda Bird - yolanda.bird@sps.lahe.edu
City of Springfield
THIS REPORT IS PROVIDED FOR THE INFORMATION OF THE CLIENT ONL Y. THE REPRODUCTION OF THIS REPORT, BY ANY METHOD, AND ITS TRANSMITTAL TO A THIRD
PARTY, BY ANY MEANS, EXCEPT IN FULL, WITHOUT THE WRITTEN PERMISSION OF PROFESSIONAL SERVICE INDUSTFiIES. IS PROHIBITED.
Professional Service Industries, Inc. - 1040-A Shelley Street. Springfie,ld, OR 97477. Phone 541n46-9649. Fax 541/746.7163
l...~;lInfonnation
,.,~. .To Build On
Engineering . Consulting. Testing
DAIL YFIELD REPORT
Date Performed:
Client:
December 2, 2008
Report Number:
722-80173-144
Springiield School District
525 Mill Street
Springfield, OR 97477
Project Name:
Thurston Elementary School
7345 Thurston Road
Springfield, Oregon
Project Location:
Contractor:
Fabricator:
Type of Inspection:
John Hyland
Axis Crane
Welding
P.O. No:
Shop! Field:
Weather:
P0272-334-0809
Field
Cloudy
Field Obse'rvations and Comments
Performed periodic visual inspection of the following items: Single and muitj pass fillet weldments for clip to embed,
beam to clip, beam to column and angie to embed at panel connections for 2nd fioor elevation and roof elevation at
gridiines E to H from 5 to 8 with the following exceptions: gridiine 5 from E to H at roof elevation for beam to clip not
welded. Weldments were inspected for size, length, profile and iocations. To the best of our knowledge, the work
inspected is in conformance with the approved drawinq~, specifications and applicable AWS Dl.l codes.
Inspector: Chris McDonald, Certification #5298238-52
CBB #176269
If you have any questions regarding this report, please feel free to contact us at 541-746-9649.
Respectfully Submitted,
p{t:JnV Service Industries, Inc.
Raymond AIiP~
Project Manager
c: KPFF - ugo.costa@kpff.com
Hyland Construction - markb@jhconst.com
Milstead & Associates - angus@milstead.us
Mahlum - rberndt@mahlum.com
Robertson/Sherwood & Architects - dguadagni@robertsonsherwood.com
Springfield School District - jsaracen@sps.lane.edu
Yolanda Bird - yolanda.bird@sps.iane.edu
City of Springfield
-----
THIS REPORT IS PROVIDED FOR THE INFDRMA TION OF THE CLIENT ONL Y. THE REPRODUCTION OF THIS REPORT. BY ANY METHOD, AND ITS TRANSMITTAL TO A THIRD
PARTY, BY ANY MEANS, EXCEPT IN FULL, WITHOUT THE WRITTEN PERMISSION OF PROFESSIONAL SERVICE INDUSTRIES, IS PROHIBITED.
Professional Service Industries, Inc. . 1 040-A Shelley Street. Springfield, OR 97477 . Phone 5411746-9649 . Fax 541!7 46-7163
l...~;lInfonnation
",~. .To Build On
Engineering . Consulting . Testing
DAILY FIELD REPORT
Date Performed: December 2, 2008 Report Number: 722-80173-143
Client: Springfield School District Project Name: Thurston Elementary School
525 Mill Street
Springfield, OR 97477 Project Location: 7345 Thurston Road
Springfield, Oregon
Building Permit No.: COM2008-00437 P.O. No.: P0272-334-0809
Type of Inspection: Epoxy Weather: Cloudy
Field Observations and Comments
Performed continuous inspection during the instaliation of 0/," all thread epoxied anchor bolts in the following locations:
(4) at gridline H.1 to H.7 enclusive at 4.8, (4) at grid line H.1 to H.7 enclusive'at 6.2 and (8) at H.1 to H.7 enclusive at 5..3
for the column footings. Verified holes to be 7/8" diameter x 9)1,' in depth. Prior to installation the predrilled holes were
cleaned using a nylon brush and compressed air. Verified minimum embedment depth of 9 inches. The above listed
epoxy anchors were installed using Hilti Hit RE500 SD epoxy with ICC #241382. The epoxy anchors were installed in
accordance with latest revisions dated RFI 030 dated 7/10/08. Contractor was asked to notify our office when additional
services are needed. To the best of our knowledge, the work inspected above was in accordance with the building
department approved design drawings, specifications and applicable workmanship of the Internationai Building Codes.
Inspector: Glenn Meeks Jr, ICC #5071538-49
CCB #176269
If you have any questions regarding this report, please feel free to contact us at 541-746-9649.
Respectfully Submitted,
Professional Service Industries, Inc.
&~d~e~
Project Manager
c: KPFF - ugo.costa@kpff.com
Hyland Construction - markb@jhconst.cOln
Milstead & Associates - angus@milstead.us
Mahlum - rberndt@mahlum.com
Robertson/Sherwood & Architects - dguadagni@robertsonsherwood.com
Springfield School District - jsaracen@sps.lane.edu
Yolanda Bird - yolanda.bird@sps.lane.edu
City of Springfield
THIS REPORT IS PROVIDED FOR THE INFORMATION OF THE CLIENT ONL Y. THE REPRODUCTION OF THIS REPORT, BY ANY METHOD, AND ITS TRANSMITTAL TO A THIRD
PARTY, BY ANY MEANS. EXCEPT IN FULL, WITHOUT THE WRITTEN PERMISSION OF PROFESSIONAL SERVICE INDUSTRIES, /$ PROHIBITED
Professional Se~ice Industries, Inc.. 1040-A Shelley Street. Springfield, OR 97477. Pho~e 541(746-9649. Fax 541(746-7163
l~~;lInformation
",~. .To Build On
Engineering . Consulting . Testing
DAILY FIELD REPORT
Date Performed: December 5, 2008 Report.Number: 722-80173-147
Client: Springfield School District Project Name: Thurston Elementary School
525 Mill Street
Springfield, OR 97477 Project Location: 7345 Thurston Road
Springfield, Oregon
Building Permit No.: COM2008-00437 P.O. No.: P0272-334-0809
Type of Inspection: Epoxy Weather: Overcast
Field Observations and Comments
Performed continuous inspection during the installation of (138) #5 epoxied rebar doweis in the following locations: stage
wall at gym fioor on line E between 2 and 5. Prior to installation the predriiled holes were cleaned using a nylon brush
and compressed air. Verified minimum embedment depth of 3 0/. inches. The above listed epoxy anchors were instailed
using Hiiti Hit RE500 SD. The epoxy anchors were installed in accordance with latest revisions dated RFI 157 dated
12/4/08 and approved job-site pians. Contractor was asked to notify our office when additional services are needed. To
the best of our knowiedge, the work inspected above was in accordance with the building department approved design
drawings, specifications and applicable workmanship of the International Building Codes.
Inspector: Steve Wilder, ICC #0876915-88
CCB #176269
If you have any questions regarding this report, please feel free to contact us at 541-746-9649.
Respectfully Submitted,
Professional Service Industries, Inc.
R~d~l~
Project Manager
c: KPFF - ugo.costa@kpff.com
Hyland Construction - markb@jhconst.com
Miistead & Associates - angus@milstead.us
Mahlum - rberndt@mahlum.com
Robertson/Sherwood & Architects - dguadagni@robertsonsherwood.com
Springfield Schooi District - jsaracen@sps.lane.edu
Yolanda Bird - yolanda.bird@sps.iane.edu
City of Springfield
THIS REPORT IS PROVIDED FOR THE INFORMATION OF THE CLIENT ONL Y. THE REPRODUCTION OF THIS REPORT, BY ANY METHOD, AND ITS TRANSMITTAL TO A THIRD
r-/-lnJ r, 0 r MI. r w."',..".". CA....",' .", I \.ILL, H'" '.....vl ,.. Ie. '"'' ~--,-~" . ZYi:" .33'0:: 0,- ,-,-.:'.,-~:,:.'r;;;'''!.. '[['1' "~[ "'J?b'b'TQ'fia '~ O"'iQU'O>ITCI"'
Professional Service Industrie,s, Inc.. 1040-A Shelley Street. Springfield, OR 97477. Phone 541/746-9649. Fax 541f746-7163
Ip~ilfo1ifJi;::;:~n
~'"".
Client:
Address:
,,', ,I. I.~ . CottD:auItIng . 1'IJsIfng
Springfield School District
525 Mili Street
Springfield, OR 97477
COMPRESSION REPORT
Project No.: 722-80173-152
Proj. Name: Thurston E)ementary School
Location:'. 7345 ThurstonRoad
.. - Springfield, Oregon
,Placement Data: Material: 'Concrete
Stage wall gridline E to E.1 at 2 to 5 + curbs at grid line 0 to 0.3 at 2.5, 0.5 to E at 2.5, 0 to
D.3at 5.5 and 0.5 to E at 5.5
ILocation Sampled At:
Stage wall E to E.1 at 2 to 5 and curb 0 to 0.3 at 2.5 + 0.5 to E
at 2.5
Date Cast:
Ticket No.:
3225524
12/09/08
IMi:0~o;~200
Dale Ree'd: 12/10/08
Weather:
Clear
Design Strength (psi):
Cylinder No.
08-3835
08-3836
08-3837
08-3838
required 4:000
Test Date
Field Cure
Age, (days) _",- (days)
Lab Cure
(days)
Yardage
Slump (in.): ASTM C143
Max. Aggr. Size:
Air Content: ASTM .C231
Air Temperature (F):
Material Temp. (F): ASTM C1064
Max Temp (F):
Min Temo fF):
Specimen Size:
12/16/2008
1/6/2008
1/6/2008
Hold
7
28
28
H
6
27
27
H
load:
1
Unit Weight (pel): ASTM C138
Time Cast: 9:00 AM
Additives:
"Results Reported To:
Total: 103/4/15
Supplier:
Knife River
Compressive Strength Data ASTM C39
placed 4,000
Diameter or
Dimensions,
(inches)
Cross Sect. Area
(s.i.)
Cylinder WT.
(Ibs.)
Compo Strength
Max. Load (I~s.) "(psi) Fracture Type *_'
C1231-03
4.00
12.57
8.5
52,615
SPRINGFIELD OFFICE
1040 - A Shelley Street
Springfield, Oregon 97477
(541)746-9649 - (541)746-7163 fax
December 18,2008 CCB#176269
Date:
B.P. No.:
P.O. No.:
Cast By:
P0272-334-0809
Glenn Meeks Jr
Field Test Data
51/4"
3/4"
33'
56'
4x8
Curing Conditions:
ASTM
Contractor
.~
Test Time
Capping Method
C617-03
4,190
3
9:58 AM
x
5 - Side Irac:ures (al lop 01 JIOm) 6 -Top fractures (same as #5bul end o/eyhn"deris poirl'ed)
Respectfully Submitted,
Q:~ssD~ nri~ Industries, fnc.
Ray:A:d AliPJ
Project Manager
Remarks:
c: .
** 1 -Cone {belh--ends} 2 - ConeNertical Cra~ks (one end) 3 - Columnar 4-- Diagomil w no cracking at ends
Sel#2
KPFF - ugo.costa@kpff.com
Hyland Construction - markb@jhconst.com
Milstead & Associates - angus@miistead.us
Mahlum - rberndl@mahlum.com
Robertson/Sherwood & Architects - dguadagni@robertsonsherwood.com
Springfield School District - jsaracen@sps.lane.edu
Yolanda Bird - yolanda.bird@sps.lane.edu
City of Springfield
THIS REPORT IS PROVIDED FOR THE INFORMA nON OF THE CUENTONL Y. THE REPRODUCTION OF THIS REPORT BY ANY METHOD, AND ITS TRANSMITTAL TO A THIRD PARTY BY ANY MEANS EXCEPT IN FULL. IS PROHIBITED
WITHOUT THE WRITTEN
PERMISSION OF PROFESSIONAL SERVICE INDUSTRIES
l ft ~;., Information
f"4!...'~!'lTo Build On
fl!!ngIneerlng . c-.uHIng . n..tIng
Client:
Address:
Springfield School District
525 Mill Street
Springfield, OR 97477
SPRINGFIELD OFFICE
COMPRESSION REPORT
1040 - A Shelley Street
Springfield, Oregon 97477
(541)746-9649 - (541)746-7163 fax
December 18, 2008 CCB#176269
Project No.: 722-80173-137
Proj. Name: Thurston Elementary School
-- -----..
Location: .J345Thurston Road"
Springfield, Oregon,
Date:
B.P. No.:
P.O. No.:
Cast By:
P0272-334-0809
Michael Wright
Plac-e-menlDa'ta: --. -., .-.. - . Material: 'Co'ncr'e-te-.
Inside perimeter of slab from gridlines 5 to 8 at gridiines A to D and E to H
Field Test Data
38'
3/4"
Location Sampled At:
Al gridline F - 5
Date Cast: 11/19/08
Ticket No.: [MiX No.:
3160305 40N15200
Design Strength (psi):
Cylinder No.
08-3707
08-3708
08-3709
08-3710
Test Date
11/26/2008
12/17/2008
12/17/2008
Hold
Date Rec'd: 11/20108
Weather:
Overcast
required 4.000
Age (days)
Field Cure
(days)
Lab Cure
(days)
Yardage
7
70
15Iump(in.}:ASTM C143'
Max. Aggr. Size:
,Air Content: ASTM C231
.Air Temperature (F):
'Material Temp. (F): ASTM G1064
Max Temp (F):
.Min Temp (F):
Specimen Size:
IUnit Weight (pct): ASTM C138
Time Cast: 8:20 AM
IIdditives:-- WRDNHot H20
Results Reported To:' Todd with John Hyland Construction
7
28
28
H
6
27
27
H
52"
79"
74"
54"
4x8
Load:
Total:
-----
Supplier:
Knife River
Curing Conditions:
1 .day F,e. remainge, ASTM
Compressive Strength Data ASTM C39
placed 4,000
Diameter or Cross Sect. Area Cylinder WT. Compo Strength Capping Method
Dimensions Max. Load (Ibs.) Fracture Type*' Test Time
(inches) (s.!.) (Ibs.) (psi)
C617"OJ C12J1-0J
3.99 12.51 8.6 51,820 4,140 3 1:39 PM X
4.01 12.63 8.6 72,160 5,710 3 9:57 AM X
------
4.00 12.57 8.6 71,990 5,730 3 10:02 AM X
Remarks:
c:
*~ 1--~' Cone (bOlh- eiidsi 2 - -CclneNertica"] Cracks'(one end)" 3 - C6iumnar" '4 - "Diagonai w no cracking at ends
5 - S-ide frac:ures (at top of be Jom) 6 - Top 'fractures (same as,#5 but end of cylinder is pointed)
Respectfully Submitted,
~:~essl(j~Vices Industries. Inc.
'~nd AIiPer
Project Manager
Set #2
KPFF - ugo.costa@kpff.com
Hyland Construction - markb@jhconst.com
Milstead & Associates - angus@milstead.us
Mahlum - rberndi@mahlum.com
Robertson/Sherwood & Architects - dguadagni@robertsonsherwood.com
Springfield School District - jsaracen@sps.lane.edu
Yolanda Bird - yolanda.bird@sps.lane.edu
City of Springfield
THIS REPORT IS PRqVIDED FOR THE Ifl/FORMAT/ON OF THE CLlENTONL Y, THE REPRODUCTION OF THIS REPORT BY ANY METHOD, AND ITS TRANSMITTAL TO A THIRD PARTY BY ANY MEANS EXCEPT IN FULL. IS
PROHIBITED WITNOUT THEWRITTEN
PERMissiON OF PROFESSIONAL SERVICE INDUSTRIES
In.ifi:# _'I Information
I.~-::~,=~ 1.70 Build On
II/i!ngII1teeri . eo.-IItIng . 7MfIng
Client:
Address:
SPRINGFIELD OFFICE
COMPRESSION REPORT
1040 - A Shelley Street
Springfield, Oregon 97477
(541)746-9649 -(541)746-7163 fax
December 18, 2008 CCB#176269
Springfield School District
525 Mill Street
Springfield, OR 97477
Project No.: 722-80173-138
Proj. Name: Thurston Elementary School
Location: 7-345 Thurston Bpad
Springfield, 'Oregon
Date:
B.P. No.:
P.O. No.:
Cast By:
P0272-334-0809
Michael Wright
koad:
Field Test Data
.Slump (in.): ASTM C143 5"
Max. Aggr. Size: 3/4"
A.ir Content: ASTM C231
Air Temperature (F): 4 r
,Material Temp. (F): ASTM Cl064 78"
.Max Temp (F): 74"
Min Temo 1Ft: 54'
-------
,Specimen Size: 4x8
Unit Weight (pcl): ASTMC138
Time Cast: 8:20 AM Curing Conditions: 1 day F:C. remainder, ASTM
Additives: WRDNHot H20
Results Reported To: Todd with John Hyland
Placement Data: r~raterial:' Concrete
Inside perimeter of slab from gridlines 5 to 8 at grid lines A to D and E to H
Location Sampled At:
At gridlines D to 6
Dale Cast: 11/19/08
Ticket No.: IMiX No.:
3225096 2440N15200
Design Strength (psi):
Cylinder No.
08-3703
08-3704
08-3705
08~3706
Test Date
11/26/2008
12/17/2008
12/17/2008
Hoid
Yardage
2
20
Dale Rec'd: 11/20108
Weather:
Total:
Supplier:
Knife River
Fogqv
..,
reauired 4,000
Compressive Strength Data ASTM C39
olaced 4,000
Age (days)
Field Cure
(days)
Lab Cure Diameter or Cross Sect. Area Cylinder WT. Compo Strength Capping Method
Dimensions Max. Load (Ibs.) Fracture Type *. Test Time
(days) (inches) (s.i.) (Ibs.) (psi)
C617.03 Ct231-03,
6 3.99 12.51 8.6 60,180 4,810 3 1:43PM X
27 4.00 12.57 8.6 75,500 6,010 3 10:05 AM X
27 4.00 12.57 8.6 75,760 6,030 3 10:09 AM X
7
28
28
H
H
h1 :'Cone (both -ends) - -2 - Cone/Vert"ical Cracks (one end)
Remarks:
c:
3 - Columnar
4 ~ Ofagonal wIno cracking at ends
5 M Side fractures (at top of bc,tom) 6 - Top fractures (same as #5 but end of cylinder is pointed)
Respectfully Submitted,
~OfesSiOV (!J1Vices Industries. Inc.
Ra~d AliPerP
Project Manager
I<PFF - ugo.costa@kpff.com
Hyland Construction - markb@jhconst.com
Milstead & Associates - angus@miistead.us
Mahlum - rberndt@mahlum.com
Robertson/Sherwood & Architects - dguadagni@robertsonsherwood.com
Springfield School District - jsaracen@sps.lane.edu .
Yolanda Bird - yolanda.bird@sps.lane.edu
City of Springfield
THIS REPORT is PROViDED FOR THE INFORMA nON OF THE CLIENT ONL Y. THE REPRODUCTION OF THIS REPORT BY ANY METHOD, AND ITS TRANSMITTAL TO A THIRD PARTY BYANY MEANS EXCEPT IN FULL,IS PROHIBITED
WI7IIOUT THE W~lTTEN
PERMISSION OF PR-OFESSIONAL SERVicE INDUSTRIES.
l~~dio~;::;:~n
Jl!!nglneerlng . ~ . .........,
Client:
Address:
Springfield School District
525 Mill Street
Springfield, OR 97477
Placement Data:
Trash enclosure footings
Location Sampled At:
Same as above
Oa(e Cast: 12/04/08
Ticket No.: IMIX No
3160490 40N1'~200
. Design Strength (psi):
Cylinder No.
08-3814
08-3815
08-3816
08-3817
"Test Date
12/11/2008
1/1/2008
1/1/2008
Hold
COMPRESSION REPORT
Project No.: 722-80173-142
Proj. Name: Thurston Elementary School
Location: .'7349 ThurstonJl,oad
. Springfieid, Oregon
Material: Concrete
Date Rec'd: 12/05/08
Weather:
Clear
required 4,000
Age (days)
Field Cure
(days)
Lab Cure
(days)
7
28
28
H
6
27
27
.H
j -"Columnar
u f -' Cone-(both ends) ;2 - ConeNertical Cracks (one end)
Remarks:
c:
Yardage
'sfump (in.): ASTM C143
'Max. Aggr. Size:
Air Content: ASTM C231
.Air Temperature (F):
Material Temp. (F): ASTM C1061
Max Temp (F):
Min Temp (F):
Specimen Size:
UnitWeight (pef): ASTM C138
Time Cast: 11 :45 AM
Additives:
Results Reported To:
Load:
Total:
Supplier:
Knife Rive-r
1
103/4/103/4
Compressive Strength Data ASTM C39
placed 4,000
SPRINGFIELD OFFICE
1040 - A Shelley Street
Springfield, Oregon 97477
(541)746-9649 - (541)746-7163 fax
December 16, 2008 CCB#176269
Date:
B.P. No.:
P.O. No.:
Cast By:
P0272-334-0809
Glenn Meeks
Field Test Data
41/4"
3/4"
1.7%
51"
62'
4x8
Curing Conditions:
ASTM
Contractor
.-
Diameter or Cross Sect. Area Cylinder WT. Compo Strength F t T *' Capping Method
Dimensions (s.L) (Ibs.) Max. Load (lbs.) (psi) rac ure ype Test Time
(inches) C617;OJ C1231-03
4.00 12.57 8.4 54,585 4,340 3 9:22 AM X
4 - 'Diagonal w no. cracking at ends 's - Side rrar~:ures (at lop 01 bottom)
I\PFF - ugo.costa@kpff.com
Hyland Construction - markb@jhconst.com
Milstead & Associates - angus@milstead.us
Mahlum - rberndt@mahlum.com
Robertson/Sherwood & Architects - dguadagni@robertsonsherwood.com
Springfield School District - jsaracen@sps.lane.edu
Yolanda Bird - yolanda.bird@sps.lane.edu
City of Springfield
- ,
6 - Top Fractures (same as #5"but end of cylirl(ler is pointed)
Respectfully Submitted,
71;:;iO,1 {f~;zjndllSlries. Inc.
Raymond Aliperti
Project Manager
THIS REPORT IS PROVIDED FOR THE INFORMATlqN .oF THE CLlENrONL Y. THE REPRODUCTION OF THIS REPORT BY ANY METHOD, AND ITS TRANSMITTAL TO A THIRD PARTY BY ANY MEANS EXCEPT IN FULL IS PROHIBITED
WITHOUT THE WRITTEN.
- - PERMISSION OF PROFESSIONAL SERVICE INDUSTRIES.
l ft~.l'. Information
~:_,=~ .7bBuildOn
II!nfIlneerlng . ~ . 1IMrUIIg
Client:
Address:
Springfield School District
525 Mill Street
Springfield, OR 97477
.Placement Data:
Administration room section #3, pour back strips
'Location Sampled At:
Wests ide of room #3
Date Cast: 11/12/08
Ticket No.: I Mix No.:
3224925 2440N15200
Design Strength (psi):
Cylinder No.
Test Date
08-38584 11/19/2008
08-358512/10/2008
08-3586 12/10/2008
08-3587 Hold
COMPRESSION REPORT
Project No.: 722-80173c120
Proj. Name: Thurston Elementary School
Location: --7345Thurston.Road,
~. . Springfield, Oregon
-Material": Concrete-
Date Rec'd:
Weather:
11/13108
Overcast
required 4,000
Age (d~ys)
Field Cure
(days)
Lab Cure
(days)
.7
28
28
H
Yardage
9
10
BSlump '(in.): AS-TM C143'
DMax. Aggr. Size:
Air Content: ASTM C231
~Air Temperature {F}:
IMaterial Temp. (F): ASTM C1064
,
:Max Temp (F):
,Min Terno CFl:
Specimen Size:
.Unit Weight (pet): ASTM C138
Time Cast: 10:00 AM
Additives:
Results Repartee To:
Load:
Total:
Supplier:
Knife River
SPRINGFIELD OFFICE
1040 - A Shelley Street
Springfield, Oregon 97477
(541)746-9649 - (541)746-7163 fax
December 11, 2008 CCB#176269
Date:
B.P. No.:
P.O. No.:
Cast By:
P0272-334-0809
Pete Furlong
Field Test Data
51/2"
3/4"
620
66"
4x8
Curing Conditions:
ASTM
Contractor
Compressive Strength Data ASTM C39
olaced 4,000
-,
Diameter or Cross Sect. Area Cylinder WT. Compo Strength Capping Method
Dimensions Max. Load (Ibs.) Fracture Type ... Test Time
(inches) (5.1.) (Ibs.) (psi)
C617cOJ C1231-03
4.00 12.57 8.6 62,080 4,940 3 10:49 AM X
4.00 12.57 8.6 87,235 6,940 2 3:33 PM X
4.00 12.57 8.6 85,340 6,790 3 3:38 PM X
6
27
27
H
3 ~ coiumnar" 4 - Diagonal w no cracking at e"nds "5 - Side trac ures (at top of bottom)
- - ,
.:. 1 ~ Cone (both-ends) 2 - ConeNerficci'] Crac.;{s (one end)
Remarks:
c:
KPFF - ugo.costa@kpff.com
Hyland Construction - markb@jhconst.com
Milstead & Associates - angus@milstead.us
Mahlum - rberndt@mahlum.com
Robertson/Sherwood & Architects - dguadagni@robertsonsherwood.com
Springfield Schooi District - jsaracen@sps.lane.edu
Yolanda Bird - yolanda.bird@sps.lane.edu
City of Springfield
6' - Top fractures (same as #5 but end of cylinder is pointed)
Respectfully Submitted,
K;SsV(jft~ices Industries, Inc.
Rayind Aliperti
Project Manager
, THIS REPORT IS PROVIDE[) F:OR THE INFORMA nON OF THE CLIENT ONL Y. THE REPRODUCTION OF THIS REPORT BY ANYMETHOD, AND ITS TRANSMITTAL TO A THIRD PARTY ~y ANY,MEANS EXCEPT IN FULL, IS
PROHIB/{ED WITHOUT THE WRITTEN
PERMISSION OF PROFESSIONAL SERVICE "JDUSTRIES. .