Loading...
HomeMy WebLinkAboutComments FLS 6/13/2006 c . Page 1 of 1 L1MBIRD Andrew From: GORDON Gilbert Sent: Tuesday, June 13, 20068:57 AM To: L1MBIRD Andrew Cc: GERARD Alan; FECHTEL Melissa Subject: Partition Tentative SUB2006-00033 Duane Knights Partition Tentative SUB2006-00033 Duane Knights Address: Garden and Laurel Avenues Existing Use: Vacant Proposal: Create a 3-lot partition Planner: Andy Limbird Fire Depart[11ent Comments: Water Supply: OK. Proposed hydrant shown on Plan Sheet 2 of 4. Access: OK. The fire apparatus access road extension from Garden Avenue shall have an unobstructed width of not less than 20 feet and a minimum clear height of not less than 13 feet 6 inches per 2004 Springfield Fire Code 503.2.1. No parking is allowed on both sides of the fire apparatus access' road. ' "No Parking-Fire Lane" signage shall be posted on both sides of the fire apparatus access road per SFC 503.3 and SFC Appendix D103.6. . Gilbert R. Gordon Deputy Fire Marshal Springfield Fire'and Life Safety 225 Fifth Street . Springfield, Oregon 97477 541-726-2293 aaordon@cLsDrinafield.or.us , ., I '. 6/13/2006