HomeMy WebLinkAboutCorrespondence FLS 1/30/2007 Page 1 of 1 ,. REESOR David From: ,GORDON Gilbert Sent: Tuesday, January 30,2007 10:33 AM To: REESOR David Cc: GERARD Alan: FECHTEL,Melissa Subject: DRC2D07.DD003 BFD Investments iI- Site Plan Tentative DRC2007-00003 BFDlnvestments Address: Olympic and 35th Streets Existing Use: Vacant ' ,Proposal: Construct 4 warehouse buildings: McKenzie-Taylor Center Planner: Dave Reesor ' 'RECEIVED " -v~--Q7 SY:1JhbRAfN d ~ , ,'1) rzL (prY\~ , Fire Department Comments: Water Supply: OK. The proposed three hour fire wall separation between storage spaces in Building B creates three separate building spaces per 2004 OSSC and reduces required fire flow per 2004 Springfield Fire Code Ap~endix B to 1500 gpm, One hydrant onlyperAppendix C, ' .Access: OK, Fire apparatus access roads shall support an' 80,000 Ib.. imposed load per 2004 Springfield Fire Code 503.2,3 and ,SFC Appen~lix 0102,1, Provide PW locks,if gates are manual opening; provide a Knox keyed gate switch if gates are electric, 1; Landscaping: A 3 foot clear space shall be maintained around the circumference of fire hydrants (2004 SFC 508.5,5), ' . \,., i:. Gilbert R.Gordon Deputy Fire Marshal' Springfield Fire and Life Safety ,'" 225 Fifth Street ' , Springfield, Oregon 97477 , 541-726-2293 : aaordonra>cLsorinofield,or. us '/" " ,"., . .J,:~ . 'c' " ,," "". " " "I' !. ," . . ~ ' -. ~.. . '. , .:. ;; ". -,.' "':0 .': .,. t, .;" ,",. :,.." "," 1-, , ' ';; <: . i' .1'" ." . . . . .,," ','1 . . ~,:. , " ".' '. '. ','-' , , " . h' .. " ....' ", '. ~, ','. .' -'.' '.' 1/30/2007 " }"