Inspection of: Masonry
Contractor: Chambers Construction
Weather: Clear/ 630 ~
BP No.: ; Cm..,2007-01851"
RECEIVE[
OCT 2 0 7nnq
Page 1 of 1
Daily Field Report
Date:
Project No.:
Report No.:
Inspector:
ID No.:
10-13-08
2087024
E-21516
M, Meyer
0877905-84
ICC
Continuous Inspection: 0
Periodic Inspection: 0
Performed inspection on the reinforcing steel in the top two (2) courses of the
generator enclosure walls, Rebar was checked for size, grade, lap, quantity, spacing
and clearances, where applicable, Vertical bars are in place and anchored from
previous pour and horizontal bond beam steel in top course has been installed, Mike
Helms (Hap's Masonry) stated grout placement is scheduled for later this afternoon,
Mr. Helms was asked to notify our office when additional services are needed,
To the best of our knowledge, the work inspected was in accordance with RFI #144
dated 08-26-08 and applicable workmanship provisions of the I.B,C" except if noted
above,
Reviewed-By:
(fJ.'-i.~-
Michael L Meltr
Technical Manager
c:
Chambers Construction - Dave Bakke (email)
Chambers Construction - John Shay (email)
Coughlin, Porter Lundeen - Bobbi Fisher (email)
Eric Hall Architects - Ted Corbin (em ail)
City of Springfield
MLM:sc
This report and/or enclosed test data is the confidential property of the client to whom it is addressed and pertains to the specific
process and/or material evaluated. As such, information contained herein shall not be reproduced in part or full and/or any part
thereof be disclosed without FEI Testing & Inspection. Inc.'s written authorization.
7fJJ NoN ComeII Avenue' Corvallis, Oregon 97330 ' phone (541) 757-4698 ,fax (541) 757-2991
29540 B Airport Road ' Eugene, Oregon 97402 ' phone (541) 684-3849 ,fax (541) 684-3851
63050 Corporate Place, Suite 2 ' Bend, Oregon 97701 ' phone (541) 382-4844 ' fax (541) 382-4846
RECEIVED
OCT 2 0 70nB
Sf;)
1I~'I"lrt;."'lmUl",II"," Geotechnical & Construction SeNices
Page 1 of 1
Report of Inspection Services
Welding/High-Strength Bolting
Client: Mr, Joe Hawes
Hawes Investments, LLC
2892 Crescent Avenue
Eugene, Oregon 97402
Project:
International Way Development
Package A
400 International Way
Springfieid, Oregon
Date:
Project No.:
Report No.:
Inspector:
ID No.:
Inspection of:
Fabricator or Erector:
Contractor:
Welding re-inspection
West Side Iron
Chambers Construction
Shop: 0
Weather:
BPNo.:
1 0-09-08
2087024
E-21475
C, Walpole
5114210-85
ICC
Field: 0
Overcast
COM2007-01851
Arrived on-site to perform re-inspection on the lower truss connection at line C,3/1 that was noted in FEI
report E-20813 dated 08-05-08, Fit up was re-worked to make the connection using fillet welds per plans,
Welds were checked for size, length, profile and location, While on-site witnessed truss bracing being
installed by a certified welder using FCAW process, Welding was not completed during the time of
inspection,
John Shay (Chambers Construction) was asked to notify our office when additional services are needed,
To the best of our knowledge, the work in-progress is in conformance with structural drawings and
applicable AWS D1, 1 code, except if noted above,
Reviewed By:
Ih.'i,~
Michael L. Meyer
Technical Manager
c:
Chambers Construction - Dave Bakke (emaH)
Chambers Construction - John Shay (email)
Coughlin, Porter Lundeen - Bobbi Fisher (em ail)
Eric Hall Architects - Ted Corbin (em ail)
City of Springfield
MLM:sc
This report andlor enclosed test data is the confidential property of the-client to whom it is addressed and pertains to the specific
process -and/or material evaluated. As such, information contained herein shall not be-reproduced in part or full and/or any part
thereof be disclosed'without FEI'Testing & Inspection, Inc.'s written aut~orjzation.
7f:IJ NW Comell Avenue' Corvallis, Oregon 97330, phone (541) 757-4698, fax (541) 757-2991
29540 B Airport Road 'Eugene, Oregon 97402, phone (541) 684-3849 'fax(541)684-3S51
63050 Corporate Place, Suite 2 ' Bend, Oregon 97701 ' phone (541) 382-4844 ' fax (541) 382-4846
{!)f;J
r.:-:r~:\'ED
I' QO?OOB
Page 1 of 1
Gov~ Ulical & Construction SeNices
Daily Field Report
.1~'lImt:<!II/~'~:.IIII/.III.
Client:
Mr, Joe Hawes Project:
Hawes Investments, LLC
2892 Crescent Avenue
Eugene, Oregon 97402
Date:
Project No.:
Report No.:
Inspector:
ID No.:
International Way Development
Package A
400 International Way
Springfield, Oregon
10-10-08
2087024
E-21494
M, Meyer
0877905-84
ICC
Inspection of: Masonry, , ' ,
Contractor: Chambers Construction
,Weather:. OV,ercast "
BP No.: . COM2007-01851
;~~ .
Continuous Inspection: 0
Periodic Inspection: 0
10-09-08: Performed inspection on the reinforcing steel in the 8" CMU generator
enclosure walls (ftg, to 4'), Rebar was checked for size, grade, lap, quantity, spacing
and clearance, where applicable, Cells were relatively clean and free of excess mortar
projections, Observed placement of 2,5 yards of Knife River 7,Osk grout. Grout was
placed by pump and was mechanically consolidated, Grout slump- 9" +; grout
temperature- 65F; air temperature- 54F, Walls were grouted solid, Three (3)
compressive strength prisms were also grouted during today's pour, Mike Helms
(Jones Masonry) scheduled the next site visit for tomorrow morning,
10-10-08: Inspected rebar in second lift of enclosure walls (4' to 8') and observed
placement of 2,5 yards of Knife River 7,0 grout by pump, Grout slump- 8" +; grout
temperature- 61 F; air temperature- 44F,
Mr. Helms was asked to notify our office when additional services are needed,
To the best of our knowledge, the work inspected was in accordance with RFI #144
dated 08-26-08 and applicable workmanship provisions of the LB,C" except if noted
above,
Reviewed By:
(JJ ~.Ilo---
Michael L Meyer '
Technical Manager
c: Chambers Construction - Dave Bakke (email)
Chambers Construction - John Shay (email)
Coughlin, Porter Lundeen - Bobbi Fisher (email)
Eric Hall Architects - Ted Corbin (email)
City of Springfield
'-." .'-; ", ... .
MLM:sc
This report and/or enclosed test data is the confidential property of the client to whom it is addressed and pertains to the specific
process and/or material evaluated. As such, information contained herein shall not be reproduced in part or full and/or any part
thereof be disclosed without FEI Testing & Inspection, Inc.'s written authorization.
. I 'I .. ..... .
, 750 NoN ComeIIAvenue' CavaIIis, Oregon 97330 'phone(541) 757-4698, fax (541) 757-2991
29540 BAirportRoad' Eugene, Oregon 97402, phone (541) 684-3849 'fax(541)684-3851
63050 Corporate Place, Suite 2 'Bend, Oregon 97701, phone (541) 382-4844, fax (541) 382-4846
(j~t)P"'1
''ill' tr
--
1I:Irl'II~lrt;<lII~~'lfUI1IJIII~ld
RECEIVE!:;
OCT 2 0 Z008
Compressive Strength of Concrete
(ASTM C 39)
Geotechnical & Construction SeNices
PROJECT
DATE
PROJECT NO,
REPORT NO.
Mr. Joe Hawes
Hawes Investments, LLC
2892 Crescent Avenue
EUgene, Ore90n 97402
International Way Development
Package A
400 International Way
Springfield, Ore90n
COM2007-01851
CLIENT
DATE CAST
STRENGTH REQUIRED
STRENGTH PLACED
PRODUCT CODE
ADDITIVES
LOAD NO,
CONCRETE TEMP
AIR TEMP
POUR LOCATION
TEST
DATE
10-15-08
11-05-08
11-05-08
Hold
AGE
(DAYS)
7
28
28
**1 - End Cones
B.P,NO.
10-08-08
4000 psi
4500 psi
314568
CAST BY
A, Fenstermacher
DATE RECEIVED
SPECIMEN SIZE
SUPPLIER
MAX SIZE AGG,
AIR CONTENT
SLUMP
TIME
SPECIMEN STORAGE
SACKS
CEMENT
1 TICKET NO.
740F YARDAGE
660 F WEATHER
Riparian overlook wall.
60008440
7,5 OF 7,5'
Overcast
AREA
(IN')
12,56
WEIGHT
(LBSl
8,5
TOTAL
LOAD (LBSl
57400
COMPRESSIVE
STRENGTH (Psn
4570
AVERAGE
STRENGTH
(Psn
TIME OF
TEST
8:25 AM
10-15-08
2087024
6054
10_09-08
4" x8"
ESG
314"
5 314"
1:30 PM
ASTM C31
TYPE OF
FRACTURE-
6
2 - Cone/Split
3 - Columnar
4 - Diagonal
5 - Side (top and bottom)
6 - Side (top or bottom)
REMARKS: John (Chambers Construction) was advised of on-site test results,
Reviewed By:
fJJ .'-i.~
Michael L Meye9'
Technical Manager
c: Chambers Construction - Dave Bakke (email)
Chambers Construction - John Shay (em ail)
Coughlin, Porter Lundeen - Bobbi Fisher (email),
Eric Hall Architects - Ted Corbin (email)
EUgene Sand and Gravel '
City of Springfield
MLM:sc
This report and/or enclosed test data is the confidential property of the client to whom it is addressed and pertains to the specific
process and/or material evaluated. As such, information contained herein shall not be reproduced in part or full and/or any part
thereof be.disclosed without FEI Testing & Inspection, Inc.'s written authorization.
750 NoN cOmeil Avenue' Corvalis, Oregon 97330, phone (541) 757-4698, fax (541) 757-2991
29540 B Airpat Road ' Eugene, Oregm 97402 ' phone (541) 684-3849 ,fax (541) 684-3851
63050 Corporate Place, Suite 2 ' Bend, Oregon 97701 'phone (541) 382-4844 ' fax (541) 382-4846
(~FEI
RECEIVED
OCT 2 0 200B Compressive Strength of Concrete
Geotechnical & Construction.SeNices (ASTM C 39) .
11~'mlrf;'I~~'~atUlliU1J
PROJECT
DATE
PROJECT NO,
REPORT NO.
Mr, Joe Hawes
Hawes Investments, LLC
2892 Crescent Avenue
EUgene, Ore9on 97402
Intemational Way Development
Package A
400 Internationai Way
Sprin9field, Oregon
COM2007-01851
CLIENT
DATE CAST
STRENGTH REQUIRED
STRENGTH PLACED
PRODUCT CODE
ADDITIVES
LOAD NO,
CONCRETE TEMP
AIR TEMP
POUR LOCATION
TEST
DATE
10-08-08 I
10-29-08 I
10-29-08 I
Hold I
AGE
(DAYS)
7
28
28
**1 - End Cones
B.P,NO,
10-01-08
3000 psi
3500 psi
313568
CAST BY
DATE RECEIVED
SPECIMEN SIZE
SUPPLIER
MAX SIZE AGG,
AIR CONTENT
SLUMP
TIME
SPECIMEN STORAGE
M, Meyer
SACKS
CEMENT
1 TICKET NO. 58005229
74" F YARDAGE 6,5 OF
71" F WEATHER Overcast
Continuous footing for riparian overlook wall.
6,5
AREA
(IN,')
12,50
WEIGHT
(LBSl
8.7
TOTAL
LOAD (LBSl
46600
COMPRESSIVE
STRENGTH (PSn
3730
AVERAGE
STRENGTH
(PSn
TIME OF
TEST
9:05 AM
10-08-08
2087024
6043
10-02-08
4" x 8"
ESG
3/4"
4"
1:15 PM
ASTM C31
TYPE OF
FRACTURE-
2
2 - Cone/Split
"3 - Columnar
5 - Side (top and bottom)
6 - Side (topor bottom)
4 - Diagonal
REMARKS: Dave Krull (Chambers Construction) was advised of on-site test results:
Reviewed By:
f/J.';(.~.
Michael L, Me~
Technical Manager
c: Chambers Construction - Dave Bakke (email)
Chambers Construction - John Shay (email)
COU9hlin, Porter Lundeen - Bobbi Fisher (email)
Eric Hall Architects _ Ted Corbin (email)
Eugene Sand and Gravel
City of Springfield
MLM:sc
This report and/or enclosed test data is the confidential property of the client to whom it is addressed and pertains to the specific
process and/or material evaluated. As such, information contained herein shall not be reproduced in part or full and/or any part
thereof be disclosed without FEI Testing & Inspection, lnc.'s written authorization.
700 NoN Camel Avenue' CotvaIlis, Oregon 97330, pi1one(541) 757-4698, fax(541) 757-2991
29540 BAirport Road' Eugene, Oregon 97402, phone (541 )684-3849' fax (541 )684-3851
. 63050 Corporate Place, Suite 2 ' Bend, Oregon 97701 'phone (541) 382-4844 ' fax (541) 382-4846
RECEIVE[
OCT 2 0 7001
Page 1 of 1
~ftJ
Geotechnical & Construction SeNices
Daily Field Report .
11:"IJNct;4m.'~~all'I~JIlli!I
Client: Mr. Joe Hawes Project: International Way Development Date: - 10-14-08
Hawes Investments, LLC Package A Project No.: 2087024
2892 Crescent Avenue 400 International Way Report No,: E-21523
Eugene, Oregon 97402 Springfield, Oregon Inspector: M, Meyer
ID No.: 0877905-88
ICC
Inspection of: Reinforced Concrete Weather: Clear Continuous Inspection: 0
Contractor: Chambers Construction BPNo.: COM2007-01851 Periodic Inspection: 0
Performed inspection on reinforcing steel in continuous planter box wall footings on
south, side of building, Rebar was checked for size, grade, lap, spacing, quantity,
supports, ties and clearances, where applicable,
Observed placement of 15,0 yds, of Eugene Sand and Gravel 4500 psi concrete- 3000
psi required (Mix 31468), Concrete was placed directly, from truck and was
mechanically consolidated, Cast four (4) 4" x 8" compressive strength cylinders from
load 1 and performed field tests as follows: slump- 3"; concrete temperature- 72F; air
temperature- 66F, Dave Krull (Chambers Construction) was advised and was asked
to notify our office when additional services are needed,
To the best o(our knowledge, the work inspected was in accordance with email from
AOR dated 10-07-08 and applicable workmanship provisions of the I.B,C" except if
noted above,
Reviewed By:
j7J. ';?(. ~
Michael L Meyg{
'Technical Manager
c:
Chambers Construction - Dave Bakke (email)
Chambers Construction - John Shay (email)
Coughlin, Porter Lundeen - Bobbi Fisher (em ail)
Eric Hall Architects - Ted Corbin (email)
City of Springfield" ,!",';-:"', .~",~', , "..;c , "';'0"
". . ~~ .Ij _."..
. ~.; j ,
,-,",,,
MLM:sc,--- -- _'
This report and/or enclosed test data is the confidential property of the client to whom-it is addressed and pertains to the specific
process and/or material evaluated. As such, information contained herein shall notbe reproduced in part or full and/or any part
thereof be disclosed without FEI Testing & Inspection, Inc.'s written authorization.
. 7'3J NoN ComeIIAvenue' Corvallis, Oregon 97330, phone (541) 757-4698 'fax(541)757-2991
, -' 29540 B Airport Road ' Eugene, Oregon 97402 ' phone (541) 684-3849 ' fax (541) 138<k3851
63050 Corporate Place, Suite 2 ' Bend, Oregon 97701 ' phone (541) 382-4844 ' fax (541) 382-4846 .
~ftJ
RECEIVED
OCT 2 0 ZOOB
Page 1 of 1
1Ia,,'II~lf'i;.I~.'~lIl!ll~_
Geotechnici31 & Construction SeNices
Daily Field Report .
Client: Mr. Joe Hawes Project: Internationai Way Development Date: 1 0-08-08
Hawes Investments, LLC Package A Project No.: 2087024
2892 Crescent Avenue 400 International Way Report No.: E-21460
Eugene, Oregon 97402 Springfield, Oregon Inspector: A, Fenstermacher
ID No.: 525882-49
ICC
Inspection of: Reinforced Concrete Weather: Overcast .' Continuous Inspection: 0
Contractor: Chambers Construction BP No.: COM2007 -01851 Periodic Inspection: 0
Performed inspection on the reinforcing steel for riparian overlook wall. Reinforcing
steel was checked for size, grade, laps, quantities, locations, ties, clearance and
supports,
Observed the placement of 7,5 cu/yds, of Eugene Sand and Gravel 4500 psi concrete
(Mix 314568) into areas noted above, Concrete was placed directly from truck and was
mechanically consolidated, Cast one (1) set of four (4) 4" x 8" concrete test cylinders,
Notified John (Chambers) of on-site results, Concrete temperature- 74F; air
temperature- 66F; slump- 5 3/4",
John was asked to notify our office when additional services 'are needed,
To the best of our knowledge, the work inspected was in accordance with drawing L 1
dated 05-16-08, EOR email dated 09-10-08 and applicable workmanship provisions of
the I.B,C" except if noted above,
Reviewed By:
/h.'-i,~
Michael L M~yerr:J -
Technical Manager
c: Chambers Construction - Dave Bakke (em ail)
Chambers Construction - John Shay (email)
Coughlin, Porter Lundeen - Bobbi Fisher (em ail)
Eric Hall Architects - Ted Corbin (email)
City of Springfield
MLM:sc
This report and/or enclosed test data is the confidential property of the client to whom iUs addressed and pertains to the specific
process and/or material evaluated. As such, information contained herein shall not be reproduced in part or full and/or any part
thereof be disclosed without FEl Testing & Inspection, lnc,'s written authorization.
7f:IJ NoN ComeIIAvenue' CavaUis, Oregon 97330' phone (541) 757-4698' fax (541) 757-2991
29540 BAirportRoad' Eugene, Oregon 97402 'phone(541)684-3849 'fax(541)684-3851
63050 Corporate Place, Suite 2 'Bend, Oregon 97701 __ phone (541)382-4844' fax (541) 382-4846
, '
~ftl
RECEIVED
OCl 2 0 7U08
Page 1 of 1
11:"lm~;'wI~..'~~.IIII~_
G.:..,.,M ",ical & Construclion SeNices
Daily Field Report .
Client: Mr, Joe Hawes Project: International Way Development Date: 1 0-08-08
Hawes Investments, LLC Package A Project No.: 2087024
2892 Crescent Avenue 400 Interna'tional Way Report No.: E-21471
Eugene, Oregon 97402 Springfield, Oregon Inspector: M, Meyer
ID No,: 0877905
ICC
Inspection of: Ceiling Grid Weather: Inside Continuous Inspection: 0
Contractor: Chambers Construction BPNo.: COM2007-01851 Periodic Inspection: 0
Performed inspection on the completed drop-ceiling grid installation in third floor room
numbers 320, 322, thru 325, 330 thru 340 and 364 thru 377, The 'T suspension
system for the Armstrong 2' x 2' and 2' x 4' tiles was anchored to 7/8" wall molding
along two (2) adjoining walls with pop-rivets, BERC 2 perimeter clips were installed on
the opposite walls at each 'T intersection, Support wires are anchored to roof support
members and/or roof deck, and to perimeter walls within 8" .of wall face, Seismic struts
using 1" conduit encircling a support wire attached to roof and ceiling grids were
installed at:!: 12'feet on center.
John Shay (Chambers Construction) was asked to notify our office when additional
services are needed,
To the best of our knowledge, the work inspected was in accordance with approved
submittal package from Haas Contracting, Inc, dated 06-30-08, package C addendum
1 prints dated 06-18-08 and applicable workmanship provisions of the I.B,C" except if
noted above,
Reviewed By:
fL~~
Technical Manager
c: Chambers Construction - Dave Bakke (em ail)
Chambers Construction - John Shay (em ail)
Coughlin, Porter Lundeen - Bobbi Fisher (email)
. Eric Hall Architects - Ted Corbin (em ail)
City of Springfield
MLM:sc
This report and/or enclosed test data is the confidential property ofJhe client to whom it is addressed and pertains to the specific'
process and/or material evaluated. As such, information contained herein shall nalbe reproduced in part or full and/or any part
thereof be disclosed without FEI Testing & Inspection, Inc.'s written authorization.
7ffJ NoN cOrnell Avenue' Corvat~, Oregon 97330' phone (541) 757-4698, fax (541) 757-2991
29540 B Airport Road ' Eugene, Oregon 97402, phone (541) 684-3849' fax (541)684-3851
63050 Corporate Place, Suite 2 'Bend, Oregon 97701 'phone (541)382-4844.' fax (541) 382-4846
~pr.
,,"7rt~
RECEIVED
OCT 2 0 100B Compressive Strength of Concrete
<k~,,;cal&ConstruclionSeNices (ASTM C 39)
11;r.'IlNrf;"h\t.'~~llllmU1!l
CLIENT
PROJECT
DATE
PROJECT NO,
REPORT NO,
Mr. Joe Hawes
Hawes Investments, LLC'
2892 Crescent Avenue
Eugene, Oregon 97402
International Way Development
Package A
400 International Way
Springfield, Oregon
COM2007-01851
B,P, NO.
DATE CAST
STRENGTH REQUIRED
STRENGTH PLACED
PRODUCT CODE
ADDITIVES
LOAD NO.
CONCRETE TEMP
AIR TEMP
POUR LOCATION
09-30-08
4000 psi
4500 psi
314568
CAST BY
A, Fenstermacher
SACKS
CEMENT
1 TICKET NO, 60008180
7r F YARDAGE 10.25 OF 25,0
68" F WEATHER Clear
HVAC pad at east side and generator slab at north side,.
LOAD 1 SAMPLED
From 1" lift in generator slab,
TEST
DATE
10-06-08
10-28-08
10-28-08
Hold
AGE
(DAYS)
6
28
28
AREA
(IN.')
12,56
WEIGHT
(LBSl
8,6
TOTAL
LOAD (LBS)
45200
COMPRESSIVE
STRENGTH (PSI)
3600
DATE RECEIVED
SPECIMEN SIZE
SUPPLIER
MAX SIZE AGG,
AIR CONTENT
SLUMP
TIME
SPECIMEN STORAGE
AVERAGE
STRENGTH
(PSI)
TIME OF
TEST
2:00 PM
10-06-08
2087024
6038
10-01-08
4"x8"
ESG
3/4"
53/4"
1:20 PM
ASTM C31
TYPE OF
FRACTURE"
6
**1 - End Cones
2 - Cone/Split
3 - Columnar
4 - Diagonal
5 - Side (top and bottom)
6 - Side (top or bottom)
REMARKS: John (Chambers) was advised of on-site test results,
6 day break requested by Dave Krull (Chambers),
Reviewed By:
/'7.-i~
Michael L M r
Technical Ma ager
c: Chambers Construction - Dave Bakke (email)
Chambers Construction - John ,Shay (email)
Cou9hlin, Porter Lundeen - Bobbi Fisher (email)
Eric Hall Architects - red Corbin (email)
Eugene Sand and Gravel
City of Springfield
MLM:sc
This report and/or enclose_d test data is the confidential property of the client to whom it is addressed and pertains to the specific
process and/or material evaluated. As such, information contained herein shall notbe reproduced in part or full and/or any part
. - thereof be disclosed without FEI Testing & Inspection" Inc.'s written authorization. .
750 NoN Cornell Avenue' CoIvaIlis, Oregon 97330, phone (541 ) 757-4698, fax (541) 757-2991
29540 B Airport Road 'Eugene, Oregon 97402 'phone(541)684-3849' fax (541) 684-3851
63050 Corpcrate Place, Suite 2 ' Bend, Oregon 97701 'phone (541) 382-4844 . fax (541) 382-4846
~rP~j
_J
11~'IIII..:.",'mlllll~1Jl!I Geotechnical & Construc!ion Services
Page 1 of 1
Report of Inspection Services
Welding/High-Strength Bolting
Client: Mr. Joe Hawes
Hawes Investments, LLC
2892 Crescent Avenue
Eugene, Oregon 97402
Project:
International Way Development
Package A
400 International Way
Springfield, Oregon
Date:
Project No,:
Report No.:
Inspector:
ID.No.:
10-08-08
2087024
E-21449
C, Walpole
5114210-85
ICC
Field: 0
Clear
COM2007-01851
Inspection of:
Fabricator or Erector:
Contractor:
Welding Re-Inspection
West Side Iron
Chambers Construction
Shop: 0
Weather:
BPNo.:
Arrived on-site on 09-30-08 to perform re-inspection of the items noted in FEI report E-21312 dated 09-24-
08, All items were completed and/or repaired, except the shear tabs that were backwards at line A,8/3
which has not been repaired and the bolted connections along line 3 with four (4) bolts in lieu of five (5) is
awaiting engineer's approval. John Shay (Chambers) was notified of the above conditions.
To the best of our knowledge, the work checked is in conformance with structural drawings dated 01-29-
08, AISC manual and applicable AWS D1, 1 code, except as noted above,
Reviewed By:
'\ /IJ,<-;(~
Michael L Meyer
Technical Manager
c:
Chambers Construction - Dave Bakke (email)
Chambers Construction - John Shay (email)
Coughlin, Porter Lundeen - Bobbi Fisher (email)
Eric Hall Architects - Ted Corbin (email) ,
City of Springfield
MLM:sc
This report and/or enclosed test data is the confidential propertyof the client to lNhom itls addressed and pertains to the specific
process and/or material evaluated. As such, information contained herein shall not be reproduced in part or full and/or any part
, thereof be disclosed without FEI Testing '& Inspection, Inc. 's wr!t!en authorization.
750 NoN ComellAvenue' Corvallis, Oregon 97330, phone (541) 757-4698, fax (541) 757-2991
29540 BAirport Road' Eugene, Oregon 97402, phone (541)684-3849' fax (541)684-3851
63050 Corpcrate Place, Suite 2 ' Bend, Oregon 97701 ' phone (541) 382-4844 ' fax (541) 382-4846
A~..... ~
~rtl
11:..'mlri;"I~\Il'~~'lIm.I~LII
~~ " ,ical & Construction SeNices
Compressive Strength of Masonry Prisms
ASTM C 1314
CLIENT
Mr. Joe Hawes
Hawes Investments, LLC
2892 Crescent Avenue
EUgene, Ore90n 97'402
PROJECT Intemational Way Development
Package A ,
400 International Way
Sprin9field, Oregon
BP NO. COM2007-01851
DATE
PROJECT NO,
REPORT NO,
10-16-08
2087024
6055
DATE CONSTRUCTED
DATE GROUTED
SOLID XX
DESIGN (F'M)
SPECIMEN STORAGE
LOCATION
10-08-08
10-09-08
HOLLOW
1500
ASTM C1314
8" CMU generator enclosure walls (slab to 4'),
FEI REP,
M, Meyer
DATE RECEIVED
PRISM I.D.
TIME
WEATHERfTEMP.
10-10-08
8"x8"x16" Ground Face
1:15 PM
Partly Cloudy/54"
MORTAR: PSIITYPE 1800 GROUT: PSI 2000
SAND 5- 5 9allon buckets AGG, SIZE 3/8"
CEMENT 1,0 sk, CEMENT 7,0
LIME 0,5 sk, ADDITIVE
OTHER Dry block additive SLUMP 9" +
TEMP. TEMP. 65"
SOURCE/I.D, Job mix SOURCE/I,D. KR/247KG3ROOO
TICKET NO. 3224058
SPEciMEN SPECIMEN SPECIMEN NET CROSS- COMPRESSIVE AVERAGE
TEST AGE HEIGHT LENGTH WIDTH SECTIONAL TOTAL STRENGTH STRENGTH
DATE (DAYS) (IN,) (IN,) (IN,) AREA (IN.') LOAD (LBS) (PSI) (PSI)
10-16-08 7 15,75 7,625 8,5 84,81 154700 2390
11-06-08 28
11-06-08 28
REMARKS: Mike Helms (Jones Masonry) was advised of on-site test results,
Reviewed By
/7/ . ';(, tl7"L;.~
Michael L. Meyer(!
Technical Manager
c:
Chambers Construction - Dave Bakke (email)
Chambers Construction - John Shay (email)
Coughlin, Porter Lundeen - Bobbi Fisher (email)
Eric Hall Architects - Ted Corbin (email)
City of Springfield
MLM:sc
This report and/or enclosed test data is the confidential property of the client to whom it is addressed and pertains to the specific
process and/or material evaluated. As such, information contained herein shall not be reproduced in part or full and/or any part
thereof be disclosed without FEI Testing & Inspection, loco's written authorization.
7ffJ NoN CaneIIAvenue' CorvaITIS, Oregon 97330, phone (541) 757-4698, fax (541) 757-2991
29540 BAirport Road, Eugene, Oregon 97402 'phone(541)684-3849' fax (541) 684-3851
63Of:IJ Corporate Place, Suite 2, Bend, Oregon 97701 'phone(541) 382-4844' fax (541) 382-4846
RECEIVED
~ftl
arp'T ? 11 7rfr1D
age' 0 eil
m~'IIHrI;'I~.'~:'lllli*h'Ilii11
. Geotechnit;:al & ConStruction SeNices
Daily Field Report
Performed inspection on the completed drop-ceiling grid installation in third floor room
numbers 305, 306, 309, 310, 350, 351, 353 and 357 (except at patio door/window);
second floor room numbers 206, 218 (except at window), 219, 222 to line 6 (except at
window near line 8), 234 (except at window), 235, 236, 250, 281, 282 and 284 (except
at window), The ''T'' suspension system for-the Armstrong 2' x 2' and 2' x 4' tiles was
anchored to 7/8" wall molding along two (2).adjoining walls with pop-rivets, BERC 2
perimeter clips were installed on the opposite walls at each "r intersection, Support
'wires are anchored to roof support members and/or roof deck, and to perimeter walls
within 8" of wall face, Seismic struts using 1" conduit encircling a support wire attached
to roof and ceiling grids were installed at':!: 12 feet on center, Advised by Brett Stutz
(Chambers Construction) that seismic joints are not required in large rooms,
Rod Carothers (Chambers Construction) was asked to notify our office when additionai
services are needed,
To 'the 'best of our knowledge, the work inspected was in accordance with approved
submittal package from .Haas Contracting, Inc, dated 06-30-08, package C addendum
1 prints dated 06-18-08 and applicable workmanship provisions of the 1.B,C" except if
noted above,
Reviewed By:
A . '-;(. fJ ,/J"--'
Michael L. Me~r
Technical Manager
c: Chambers Construction - Dave Bakke (email)
Chambers Construction.c-,John Shay (em ail)
Coughlin, Porter Lundeen - Bobbi Fisher (email)
Eric Hall Architects - Ted Corbin (em ail)
City of Springfield
MLM:sc
This report and/or enclosed test data is the confidential property of the client to whom.it is addressed and pertains to the specific
process and/or material evaluated. As such: information contained herein shall not be reproduced in part or full and/or any part
thereof be disclosed without FEI Testing & Inspection, Inc;'s written authorization.
7fJJ NoN ComeII Avenue , Corvallis, Oregon 97330 'phone(541)757-4698' fax(541) 757-2991 '
29540 BAirport Road, Eugene, Oregon 97402' phone (541)684-3849 ,fax (541 )684-3851
63050 Corporate Place, Surte 2 ' Bend, Oregon 97701 'phone (541) 382-4844 ' fax (541) 382-4846