Daily Report of-Structural Steel
Client: SAFEWAY STORES INC - PHIL JUTTELSTAD
Project: SAFEWAY STORE #1094 REMODEL - SPRINGFIELD cn Job #: S0805400.
Address: 1891 PIONEER PKWY E - SPRINGFIELD, OR Jurisdiction: SPRINGFIELD
cn representative L. WES'fPHAL, JR. OBOA 782
was on sit te _Sep. 10, 2008 to perform Special Inspection for:
Pennit COM2008-004711
,
DFS#(s)
SCOPE OF INSPECTION
I. Checked in with superintendent, client or shop rep.
Name: RANDY
Company' JAMES E JOHN
2. Inspection was "IBe" D Continuous GJ Periodic
3. Work performed: GJ In the field D At fab shop
4. If shop inspection do they have fabrication and QC
procedures? DYes D No GJ N/A
INSPECTION
. Yes NoN/A
I :'Reviewed.previuus inspection reports?
2. Verified steel materials are in compliance by reviewing
random samples of the mill test reports, steel JD
markings or other documentation.
3. Verified weld filler materials conform.
4.
x
x
x
Checked steel members to see they were fabricated and
erected in accordance with the workmanship and
tolerances required.
5. Checked welded studs and structural connections were
installed as required.
6. Verified high strength bolts and fasteners conform.
7. Verified the quality of welds produced by \velders,
welding operators, and tackers confoml.
8. Verified steel frame joint details for bracing, stiffening,
member locations, and application ofjoint details at each X
connection arc in compliance by random sampling.
x
xl
I I X
X I I
WELDER INFORMATION
Welders Name: MICHAEL LIVERMORE
Certification #: W05869 I C-2196
Yes No N/A
1. Verified the contractor's Welding Procedure
Specifications are in conformimcc with
A WS requirements.
2. Verified the essential variables outlined in the
Welding Procedure Specifications were
employed during execution of the work.
X
X
3. Verified the weldability of reinforcing steel
other than ASTM A706.
D See additional report page(s).
D Distribute attachments.
Po. Number: 108018
Location of steel inspection [to include grid lines, elevations
(floors) and drawing details):
INSPECTION OF STEEL FRAMING AND WELDING. METAL
DECKING AND CANOPY AT THE EAST END OF BUILDING.
WELDS WERE FCAW FOR STRUCTURAL STEEL AND E6011
FOR STEEL DECK FCAW WELD ELCTRODE WAS E71T-11/16
DIAMETER SELF SHEILDING FLUX CORED WIRE. WELDS
WERE ADEQUATE. NOTE: DECK BUTTON PUNCHING OF
SIDE SEAM LAPS ARE IN-PROGRESS AT THIS TIME.
REPORT SUMMARY
L Work inspected was: GJ Completed D In progress
2. Completed work inspected was in compliance with
GJ Approved plans and specifications D' Shop drawings
D RFI 0 Design change D Submittal D N/A
Document #(s) PLANS Dated:
3. Noncompliance item(s) were noted this date, details on
followingpage(s). DYes D No GJ N/A
4, Noncompliance item(s) were reinspected this date, details
on following pagers). DYes D No [i] N/A
D Conform D Remain in progress
Report(s) findings were discussed and left with
RANDY
of _ JAMES E JOHN
X
Based on the Code, approval is required from the Building Official before the
SPECIAL INSPECTED items noted above can be covered. Carlson Testino
has no authority to direct work of contractors or subcontractors. e
Page
nf_
Daily Report of Structural'Steel
.CTI Job #: S0805400,
Project: SAFEWAY STORE %1094 REMODEL - SPRINGFIELD
For: 09/10/2008
Notes:
In some cases more than one box may be checked for a given item on the front page.
OUT Teports pertain to the material tested/inspected only. Information contained herein is not to be Teproduced, except in
full, without pTior authorization from this office.
If there are any further questions regarding this matter, please do not hesitate to contact this office,
Respectfully submitted,
CARLSON TESTING, INC.
Reviewed By: Steven DuggeT
Review Date: 10/02/2008
LLW!LS
SAFEWAY STORES INC - PHIL JUTTELSTAD
TO: CITY OF SPRINGFIELD BUILDING DEPARTMENT
ASSOCIATED CONSULTANTS INC - MANOUCH YAGANEH
BENNER STANGE ASSOCIATES - JIM PARK
JAMES E JOHN CONSTRUCTION CO INC - KRIS SIMENSEN
FAXj503-657-6496
FAXj503-384-0459
FAXj503-670-0235
FAXj360-696-9723
;Carlson Testing, Inc.
Construction Inspections & Related Tests.
Geotechnical Consulting
Main Office
P.O. Box 23814
Tigard, Oregon 97281
.Phone (503) 684-3460
Fax (503) 684-0954
Salem Office
4060 Hudson Ave.. NE
Salem, Oregon 9730 I
Phone (503) 589-1252
Fax (503) 589-1309
"Bend Office
P.O. Box 7918
Bend, Oregon 97708
Phone (541) 330-9155
Fax (541) 330-9163
REPORT OF 3X3X6
GROUT
TEST SPECIMENS
Test Methods:. ASTM C31/Cl72/Cl92/C617/Cl064/C143
Date Molded: 08/19/2008
Permit #: COM2008-00471
Client: SAFEWAY STORES INC - PHIL JUTTELSTAD
Project: SAFE WAY STORE #1094 REMODEL - SPRINGFIELD
Address: 1891 PIONEER PKWY E - SPRINGFIELD, OR
Job Number: S0805400.
Jurisdiction: SPRINGFIELD
. Contractor: JAMES E JOHN CONSTRUCTION CO INC - KRIS SIMENSEN
Subcontractor:
Grout Supplier: X
Truck #:
Weather: CLOUDY
Cast By:
G. KEENE
Load #: l'
Test Time:' 8: 10 AM
Ticket#: 154217
Air Temp. at Sampling Time:' 62
Grout samples cast at the following location:
G.2 @ 2.4
. Total Grout Placement Location:
6,,'CMU WALL G.2 @ 2-3.2, (2) DOOR IN FILLS G @ 5.8 AND 3 @ B
Strength Requirement: 2000
Mix Number:
psi fg@ 28 Days Slump'
Grout Temp: ~ Cement Type:
8-10"
Admix/Amt: NO BATCH WEIGHTS
Register Number: 0006244
Max Agg: 3/4"
Cubic Yards:
Lab Location: SALEM
Set Test @ Date Test Total Area I Unit Tested
No. . Davs Rec'd Date Load PSI Bv
28 08/21/2008 09/16/2008 26110 3.20 I 8160 SRT
28 08/21/2008 09/16/2008 26210 3.20 I 8190 SRT
28 08/21/2008 09/16/2008 26385 3.20 I 8250 SRT
28 08/21/2008 09/16/2008 26890 3.25 I 8270 SRT
j
I
I
Average fg @ 28 days I 8220
D Distribute attachments. Please see reverse side for additional information.
Job Number: S0805400. Register Number: 0006244
Project: SAFEWAY STORE #1094 REMODEL - SPRINGFIELD
Date Molded: 08/19/2008
Asterisked C*) average unit PSI test results did not meet listed acceptance criteria.
".o.j
Remarks:
SAFEWAY STORES INC - .PHIL JUTTELSTAD
TO: CITY OF SPRINGFIELD BUILDING DEPARTMENT
ASSOCIATED CONSULTANTS INC - MANOUCH YAGANEH
BENNER STANGE ASSOCIATES - JIM PARK
JAMES E JOHN CONSTRUCTION CO INC - KRIS SIMENSEN
FAX/503-657-6496
FAX/503-384-0459
FAX/503-670-0235
FAX/360-696-9723
Project Manager: B. LEACH
Reviewed By: Reviewed On 09/22/2008
Our Teport pertains to the material tested only, The information contained in this report is provided subject to all terms an,
conditions of CTI's General Conditions in effect at the time this report is prepared. No party other than those to whom
CTI has distributed this report shall be entitled to use or Tely upon the information contained in this document
Carlson Testing, Inc.
Main Office
P.O. Box 23814
Tigard. Oregon 97281
Phone (503) 684-3460
Fax (503) 684-0954
Salem Office
4060 Hudson AYe., NE
Salem, Oregon 97301
Phone (503) 589-1252
Fax (503) 589-1309
Bend Office
P.O. Box 7918
Bend, Oregon 97708
Phone (541) 330-9155
Fax (541) 330-9163
. Daily Report .of Structural Steel
"Clieut: SAFEWAY STORES INC - PHIL JUTTELSTAD
Project: SAFEWAY STORE #1094 REMODEL - SPRINGFIELD cn Job #: S0805400.
Address: 1891 PIONEER PKWY E - SPRINGFIELD, OR Jurisdiction:. SPRINGFIELD
'CT! representative B. TATMAN OBOA 834
was on site this date Sep, 03, 2008 to perform Special Inspection for:
Pennit COM2 0 0 8 - 0 0 4 71
DFS #(s)
PO Number: 108018
SCOPE OF INSPECTION
Location of steel.inspection [to include grid lines, elevations
(floors) and drawing details]:
A.) eTI INSPECTION 3/16" FILLET WELDS ON 11 EACH)
HEADER AND (2 EACH) COLUMNS.
B.I CHECKED WELDS ON (2 EACH) WALL STIFFENERS FOR
NEW SUFFIT.
C. I INSPECTED PER DETAILS 9/51.2, 11/S1.2
J . Checked in with superintendent; client or shop rep.
: Name: TERRY
Company: MASS FAB
2. Inspection was "!BC" [i] Continuous D Periodic
3. Work performed: 0 In the field [i] At fab shop
MAS S FAB
. 4. If shop inspection do they have fabrication and QC
procedures? [i] Yes 0 No 0 N/A
D.I PARTS WELDED PER DETAILS AND MEET ACCEPTABLE
CRITERIA D1.1 TABLE 6.1
INSPECTION
Yes NoN/A
( 1. Reviewed previous inspection reports? . I , X
2. V erifiedsteel materials 'are in compliance by reviewing'
random samples orthe mill test reports, steel ID
markings or other documentation.
I' 3. Verified weld filler materials cOI1fonn.
4. Checked steel members to' see they were fabricated and
. erected in accordance with the workmanship and
tolerances required.
15. Checked welded studs and structural connections were
installed as required.
I 6. Verified high strengt.h bolts and fasteners confonn.
7. Verified the quality of welds produced by welders,
welding operators, and tackers conform.
8. Verified steel frame joint details for bracing, stiffening,
member locations, and application of joint details at each X
connection are in compliance by random sampling.
x
x
x
I X I I I
I I I X I
I X I I
REPORT SUMMARY
WELDER INFORMATION
I. Work inspected was: [i] Completed 0 In progress
2. Completed work inspected was in compliance with
[i] Approved plans and specifications 0 Shop drawings
o RFI 0 Design change 0 Submittal 0 NIA
Document #(s) S1. 2 Dated:
f
Verified the contractor's Welding Procedure
Specifications are in conformance with
A WS requirements.
2. Verified the essential variables outlined in the
Welding Procedure Speci(jcations ,were
employed during execution of the work.
X
3. Noncompliance item(s) were noted this date, details on
following pagels). 0 Yes 0 No [i] N/A
4. Noncompliance item(s) were reinspected this date, details
on following page(s). 0 Yes 0 No [i] N/A
D Conform D Remain in progress
Welders Name: ON FILE
Certification #:
Yes No N/A
X
Report(s) findings were discussed and left with
TERRY
of MASS FAB
13
Verified the weldability of reinforcing steel
other.than ASTM A 706.
X I Based on the Code, approval is required from the Building Official before the
SPECIAL IN~PECT~D items noted above can be covered. Carlson Testing
has no authonty to direct work of contractors or subcontractors. .
D Distribute attachments. Page of _
o See additional report pagels).
Daily Report of Structural Steel
en Job #: S0805400.
For: 09/0312008
Project: SAFEWAY' STORE #1094 REMODEL - SPRINGFIELD
Notes:
In some cases more than 'one box may be checked for a given item on the front page.
Our reports pertain to the material tested/inspected only, Information contained heTein is not to be reproduced, except in
full, without prior authorization from this office.
If there aTe any furtheT questions regaTding this matter, please do not hesitate to contact this office.
Respectfully submitted,
CARLSON TESTING, INC.
Reviewed By: Steven Dugger
Review Date: 09/22/2008
BT/KMF