September 17, 2008
S0805400.CTI '
Permit No. COM2008-00471
FIELD INSPECTION REPORT
DATES COVERED: September 16th, 2008
c <g - <-(1'(
PROJECT: Safeway Store #1094 Remodel - Springfield
ADDRESS: 1891 Pioneer Pkwy E - Springfield, OR
INSPECTOR: R. Lee OBOA #619
09/16/08: As requested by Engineer of Record Manouch Yaganeh, CTI representative is
reporting this additional information in regards to inspection performed August 29th, 2008:
By request of the EOR the Contractor removed (2) shell facing (6" CMU) from each of
the (3) walls in question (Bottle Room wall infills at B/3 & G/6.4). A total of (12) cells
were checked for consolidation. (1) cell was not consolidated at infill G/6.4(rocks only),
CTI is still requiring Engineer's written approval for this condition.
Our reports pertain to the material tested/inspected only. Information contained herein is not to
be reproduced, except in full, without prior authorization from this office.
If there are any further. questions ,regarding ,this.matter, .please do not. hesitate. to.contact this
office. .. ...... . .:'. ':"'" ",...... :. ':. .... " 'u '.
Respectfully submitted,
CARLSON TESTING, INC.
.~Q?
Project Manager
RLlls
cc:
Safeway Stores Inc - Phil Juttelstad
City Of Springfield Building Department
Associated Consultants Inc - Manouch Yaganeh
Benner Stange Associates - Jim Park
James E JohnConstCY,cti9.n C.q,.lnp~.Kr,i?$im.~nsen . '.
Fax: 503-657-6496
" "
Fax: 503-384-0459
Fax: 503-670-0235
Fax:.360-696,9723..""". . '"
~.. ,..." ~ .... ,-, .~. -'- 7' .., . -"" J ".'f'-' "'~ ' . "
. " -c',> !' I
, . 'I' ,-'"
. :t}: .. ._
Carlson Testing, Inc.
_ Main Office
P.O. Box 23814
Tigard, Oregon 97281
Phone (503) 684-3460
Fax (503) 684-0954
Salem Office
4060 Hudson Ave.. NE
Salem, Oregon 9730 I
Phone (503) 589-1252
Fax (503) 589'1309
Bend Office
P.O. Box 7918
Bend, Oregon 97708
Phone (541)330-9155
Fax (541) 330-9163
Daily Report of Proprietary-Anchors
Client: SAFEWAY STORES INC - PHIL JUTTELSTAD
Project: SAFEWAY STORE #1094 REMODEL - SPRINGFIELD CTI Job #: S0805400.
Address: 1891 PIONEER PKWY E - SPRINGFIELD, OR Jurisdiction: SPRINGF'T~iJD
cn representative R. LEE
was on site this date Sep. 05, 2008 to perform Special Inspection for:
Permit COM2 0 0 8 - 0 0 4 71
DFS #(s)
'SCOPE-OF INSPECTION
1. Checked.in with superintendent or client representative.
Name: RANDY
Company: JAMES E JOHN
2. Inspection was "IBC" [i] Continu~us
PROPRIETARY ANCHORS
1. Reviewed previous inspection reports?
2. Reviewed evaluation report?
Verified-following itcmsmeet'manufacturer's'
published installation instructions.
I
I
I
I
I
_I
I 9. Verified hole cleaning method.
110. Verified adhesive application.
'111. Verified edge distance.
112. Verified spacing.
/13 .. Verified installation torque.
3. Verified minimum embedment depth of the
anchors.
4.Verified installation of the anchors.
5. Verified anchor diameter.
6. Verified steel grade.
7. Verified hole diameter.
8. Verified type of drill bit used.
Evaluation report number & date:
ESR #4945
12/1/98
Name of product being in'stalled
o Periodic
Yes NoN/A
I ~ I I I
x
X
xl
x I I
I X I I
I X I I
I X I I
I x I I
I X I I
I X 1 i
I I Ix
HILTl HIT RE 500
Batch Number 3103384
Expiration Date .Q.2I? 0 0 q
'PO Number: 108018
Location of proprietary anchors inspected [to include,grid
. lines, elevations (floors) and drawing details):
SECOND FLOOR C.3. 5/8" THREADED BOLTS FOR LTT 20
R _ ~ /4" 'T'HRRAnF'.n ROT,TS FOR rnNNRr'l"TnN nF' HSS ::l
1/2" x 3 1/2" X 1/4" TO rONCRP/f'R WAT,T.
REPORT SUMMARY
1. Work inspected was: GJ Completed .0 In progress
2. Completed work inspected was in compliance with
'0 Approved plans and specifications o Shop drawings
GJ RFI '0 Design change 0 Submittal 0 N/A
Document#(s) #10
Dated: 8 14 lOR
3. Noncompliance item(s) Were noted this date, details on
followingpage(s). 0 Yes' 0 No' GJ N/A
4. Noncompliance item(s) were reinspected this date, details
on following page(s). .0 Yes 0 No GJ N/A
D Conform D Remain in progress
Report(s) findings were discussed and left with
RANDY
of JAMES E JOHN
Based on the Code, approval is required from the Building Official before the SPECIAL INSPECTED items noted above can
be covered. Carlson Testing has no authority.to direct work of contractors or subcontractors.
o See additional report page(s).
o Distribute attachments.
Page ~of_
.Daily'Report of'ProprietaryAnchors
CTIJob #: S0805400.
.For: 09/05/2008
'Project: SAFEWAY STORE. #1094 REMODEL - SPRINGFIELD
Notes:
.j
-.........
In some cases more than one box may be checked for a given item on the front page.
Our reports pertain to the material tested/inspected only.' Information contained herein is not to be reproduced, except in
. full, without prior authorization from this office.
. Ifthere.are.any further questions regarding this matter, please do not hesitate to contact this office.
Respectfully submitted,
CARLSON TESTING, INC.
Reviewed By: Steven Dugger
Review Date: 09/15/2008
RL/KMF
SAFEWAY STORES INC - PHIL JUTTELSTAD
TO, CITY OF SPRINGFIELD BUILDING DEPARTMENT
ASSOCIATED CONSULTANTS INC - MANOUCH YAGANEH
BENNER STANGE ASSOCIATES - JIM PARK
JAMES E JOHN CONSTRUCTION CO INC - KRIS SIMENSEN
FAX/503-657-6496
FAX/503-384-0459
FAXj503-670-0235
FAXj360-696-9723
Carlson Testing, Inc.
Main Office
P.O. Box 23814
Tigard, Oregon 97281
Phone (503) 684-3460
. Fax (503) 684-0954
Salem Office
4060 Hudson Ave.. NE
. Salem, Oregon 97301
Phone (503) 589-1252
Fax (503) 589-1309
Bend Office
P.O. Box 7918
Bend. Oregon 97708
Phone(541) 330-9155
Fax (541) 330-9163
Daily Report of Proprietary Anchors
Client: SAFEWAY STORES INC - PHIL JUTTELSTAD
Project: 'SAFEWAY STORE #1094 REMDDEL' - SPRINGFIELD
Address: 1891 .PIONEER PKWY E - SPRINGFIELD. OR
B. PARRISH OBOA 771
Sep. 08, 2008
. CTl representative
.. was on site this date
Permit COM2008-o'0471
. Jurisdiction:
CTI Job #: S0805400.
SPRINGFIELD
to perfonn'Special Inspection for:
DFS #(s)
'SCOPEOFINSPECTlON
] . Checked in with superintendent or client representative.
Name: RANDY
Company: JAMES E JOHN
2. Inspection was "ISe" W Continuous
o Periodic
PROPRIETARY ANCHORS
Yes NoN/A
I. Reviewed previous inspection reports?
.2. Reviewed evaluation report?
I: I I
Verified following items meet manufacturer~s
pub~ished installation instructions.
3. Verified minimum embedment depth of the
anchors.
4.Verified installation of the anchors.
5. Verified anchor diameter.
6. Verified steel grade.
7. Verified hole diameter.
8. Verified type of drill bit used.
9. Verified hole cleaning method.
10. Verified adhesive application.
I 1. Verified edge distance.
12. Verified spacing.
13 . Verified installation torque.
x
X
X
X
X
X
X
x
X
X
Evaluation report number & date:
ESR 2322
Name of product being installed
HILTI RE 500 SD
Batch Number 070508 L3
Expiration Date 5/09
PO Number: 108018
Location of proprietary anchors inspected [to include grid
lines, elevations (floors) and drawing details):
121 3/4" X 12" ALL THREAD EMBEDED AT 4 1/2" INTO
CONCRETE WALLS AT STORR FRONT. 4X 4' TURF S'T'RRT,
WITH BRACKETS. r:OUJMNS. r:RN'T'FRS ARE' AT 7" ANn
EDGE DISTANCE - 9". ALL WORK CONFORM TO REPORT
INFORMATION AND RF'T ~1n 1'0 THR RRS'T' OF MY
KNOWLEDGE
I
j
REPORT SUMMARY
1. Work inspected was: W Completed '0 In progress.
2. Completed work inspected was in compliance with
o Approv'ed plans and specifications.. 0 Shop drawings
W RFI 0 Design cbange 0 Submittal 0 N/A
Document #(s) #10
Dated: R /4/8
x
3. Noncompliance item(s) were noted this date, details on
followingpage(s). 0 Yes 0 No' GJ N/A
4. Noncompliance item(s) were reinspected this date, details
on following page(s). 0 Yes 0 No GJ N/A
D Conform 0 Remai~ in progress
Report(s) findings were discussed and left witb
RANDY
of JAMES E JOHN
Based on the Code, approval is required ITom the Building Official before. the SPECIAL INSPECTED items noted above can'
be covered. Carlson Testing has no authority to direct work of contractors or subcontractors. .
. D See additional report page(s).
o Distribute attachments.
Page _of _
Daily Report'of-Proprietary Anchors
'CTI Job #: S0805400.
'For: 09/0812008
Project:
SAFEWAY STORE #1094 REMODEL - SPRINGFIELD
Notes:
.'
h" ..
-"0
In some cases more than one box may be checked for a given item on the front page.
Our reports pertain to the material tested/inspected only. Information contained herein is not to be reproduced, except ir
full, without prior authorization from this office.
If there are any further questions regarding this matter, please do not hesitate to contact this office.
Respectfully submitted,
CARLSON TESTING, lNC.
Reviewed By: Steven Dugger
Review Date: 09/15/2008 .
BP/KMF
SAFEWAY STORES INC - PHIL JUTTELSTAD
TO: CITY OF SPRINGFIELD BUILDING DEPARTMENT
ASSOCIATED CONSULTANTS INC - MANOUCH YAGANEH
BENNER STANGE ASSOCIATES - JIM PARK
JAMES E JOHN CONSTRUCTION CO INC - KRIS SIMENSEN
FAX/503-657-6496
FAX/503-384-0459
FAX/503-670-0235
FAX/360-696-9723
'Carlson'festing, Inc.
Main Office
P.O. Box 23814
Tigard, Oregon 97281
Phone (503) 684-3460
Fax (503) 684-0954
Salem Office
4060 Hudson Ave.. NE
Salem, Oregon 9730 I
Phone (503) 589-1252
Fax (503) 589-1309
Bend Office
P.O. Box 7918
Bend; Oregon 97708
Phone (541) 330-9155
Fax (541) 330-9163
Daily Report of Proprietary Anchors
. Client: SAFEWAY STORES INC - PHIL JUTTELSTAD
Project: SAFEWAY STORE #1094 REMODEL - SPRINGFIELD
Address: 1891 PIONEER PKWY E - SPRINGFIELD, OR Jurisdiction:
CTI representative B'. PARRI SH OBOA 771
was on site this date Sep. 08, 2008 to perform Special Inspection for:
Permit COM2 0 0 8 - 0 0 4 71
DFS #(s)
SCOPE OF INSPECTION
1. Checked in with superintendent or client representative.
Name: RANDY
Company: JAMES E JOHN
2. Inspection was l1IBCrl [i] Continuous
D. Periodic
PROPRIETARY ANCHORS
Yes NoN/A
'.~Il. Reviewed previous inspection reports?
2. Reviewed evaluation report?
I ~ I II
Verified follo~ing items meet manufacturer's
published installatIOn instructIOns.
I 3. Verified minimum embedment depth of the
anchors. x
I 4.Verified installation of the anchors. X
5. Verified anchor diameter. x
I 6..Yerified steel grade. x
I, 7: Verified hole diameter. I x
I 8. Verified type of drill bit used. I X I
I 9. Verified hole cleaning method. I x I I
110. Verified adhesive application. I I x'l
111. Verified edge distance. Ix I I
112. Verified spacing. I x I I
13. Verified installation torque. I I xl
, Evaluation report number & date:
ESR 2322
Name of product being installed
HILTI RE 500 SO
Batch Number 22 0 5 L3
Expiration Date 5/09
CTIJob#: S0805400.
SPRINGFIELD
PO Number: 108018
Location of proprietary anchors inspected [to include grid
lines, elevations (floors) and drawing details]:
141 5/8" x 12" ANCHORS EMBEDMENT AT 10" INTO CMU
. AT BOTTLE RETURN FOR COLUMN' MOlJN'1'TNr: _ AT,T, HOU",S
ARE CLEAN AND DRY. EDGE DISTANCF'. - 1 1/')"
. CENTERED AT 3". THIS CONFORMS TO ENGINEERED
DRAWINGS BUT NOT MANUFACTURERS F'.Dr:F'. D~S'T'ANrF'.
REQUIREMENTS. ALL WORK CONFORMS '1'0 'T'HF'. RF'.S'T' OP
MY KNOWLEDGE
.REPORT SUMMARY
I. Work inspected was: GJ Completed '0 In progress
2. Completed work inspeCted was in compliance with
GJ Approved plans and specifications 0 Shop drawings
o RFI' 0 Design change .0 Submittal 0 N/A
Document #( s) S 1. 2 #9
Dated: 3/31/08
3. Noncompliance item(s) were noted this date, details on
followingpage(s). 0 Yes 0 No GJ N/A
4. Noncompliance item(s) were reinspected this date, details
on following page(s). 0 Yes 0 No GJ N/A
D Conform D Remain in progress
Report(s) findings were discussed and left with
.RANDY
of JAMES E JOHN
. Based on the Code, approval is required from the Building Official before the SPECIAL INSPECTED items noted above can
be covered. Carlson Testing has no authority to direct work of contractors or subcontractors.
o See additional report page(s).
D Distribute attachments.
. Page _of_
Daily Report of Proprietary Anchors
'CTI Job.#: S0805400.
'For: 09/08/2008
'Project:
SAfEWAY STORE #1094 REMODEL - SPRINGFIELD
Notes:
'.:..
In some cases more than one box may be checked for a given item on the front page.
Our reports pertain to the material tested/inspected only. Information contained herein is not to be reproduced, except in
full, without prior authorization from this office.
If there are any further questions regarding this matter, please do not hesitate to contact this office.
Respectfully submitted,
CARLSON TESTING, INC.
Reviewed By: Steven Dugger
Review Date: 09/I 5/2008
BP/KMF
SAFEWAY STORES INC - PHIL JU77ELS7AD
TO, CITY OF SPRINGFIELD BUILDING DEPARTMENT
ASSOCIATED CONSULTANTS INC - MANOUCH YAGANEH
BENNER STANGE ASSOCIATES - JIM PARK
JAMES E JOHN CONSTRUCTION CO INC - KRIS SIMENSEN
FAX/503-657-6496
FAX/503-384-0459
FAX/503-670-0235
FAX/360-696-9723
,Carlson 'resting, Inc.
Main Office
P.O. Box 23814
Tigard, Oregon 97281
Phone (503) 684-3460
Fax (503) 684-0954 .
Salem Office
4060 Hudson Ave.. NE
Salem, Oregon 97301
Phone (503) 589-1252
Fax (503) 589-1309
Bend Office
P.O. Box 7918
Bend, Oregon 97708
Phone (541) 330-9155
. Fax (541) 330-9163
Daily Report 'of Proprietary Anchors
Client: SAFEWAY STORES INC - PHIL JUTTELSTAD
Project: SAFEWAY STORE #1094 REMODEL - SPRINGFIELD
Add~ess: 1891 PIONEER PKWY E - SPRINGFIELD, OR Jurisdiction:
CTl representative R. LEE
was on site this date Sep. 09, 2008 to.perform Special Inspection for:
Permit COM2 008 -00 4 71
DFS #(s)
SCOPE OF INSPECTION
1. Checked in with s.uperintendent or client representative.
Name: RANDY
Company: JAMES E JOHN
2)n'spection was "IBC" W Continuous
. D Periodic
PROPRIETARY ANCHORS
Yes NoN/A
"I. Reviewed previous inspection-reports?
2. Reviewed evaluation report?
I ~'I I
Verified following items meet manufacturer's
published installation instructions.
I 3. Verified minimum embedment depth of the
anchors.
I 4.Verified installation of the anchors.
I 5. Verified anchor diameter.
./' .6. Verified steel grade.
7. Verified hole diameter.
'1 8. Verified type of drill bit used.
I 9. Verified hole cleaning method.
/10. Verified adhesive application.
1.1. Verified edge distance.
112. Verified spacing.
113. Verified installation torque.
x
X
X
X
X
X
X
X
X
X
CTI Job #: S0805400.
SPRINGFIELD
PO Number: 108018
Location of proprietary anchors inspected [to include grid
lines, elevations (floors) and drawing details):
OBSERVED PLACEMENT OF 5/8" THREADED BOLTS FOR
3"X :i" X 1/1 ri" -nNr;T,RR FOR ROOF' SUPPOR'T' (RO'T''T'T,F',
ROOM) ON RAST"SIDE or STORE
DETAIL 11.12 PAGE Sl.2
REPORT SUMMARY
I 1. Work inspected was: GJ Completed 0 In progress
r 2. Completed work inspected was in compliance with
I [Xl Approved plans and specifications 0 Shop drawings
I 0 ~I 0 Design change 0 Submittal 0 N/A
I
I
I
I
Document #(s) AA.12
Dated: 8/4/8
3. Noncompliance item(s) were noted this date, details on
following page(s). 0 Yes 0 No GJ
N/A
I
i
Ix
4. Noncompliance item(s) were reinspected this date, details
on following page(s). 0 Yes 0 NoGJ N/A
D Conform D Remain in progress
Evaluation report number & date: Report(s) findings were discussed and left with
ESR 2322 JANDY
11/1/07 o[-.JAMES E JOHN
Name of product being installed HILTI RE 500 SO
Batch Number 3103384
Expiration Date 5/09
Based on the Code, approval is required ITOm the Building'Official before the SPECIAL INSPECTED items noted above can
be covered. Carlson Testing has no authority to direct work of contractors or subcontractors.
D See additional report page(s).
o Distribute attachments.
Page _of _
Daily ,Report 'of Proprietary Anchors
-cn Job #: S0805400.
'For: 09/09/2008
. . -
Project: SAFEWAY STORE #1094 REMODEL - SPRINGFIELD
Notes:' .
In some cases more than one box may be checked for a given item on the front page.
Our reports .pertain to the material tested/inspected only. Information contained herein is not to be reproduced, except in
full, without prior authorization' from this office.
If there are any further questions regarding this matter, please do not hesitate to contact this office.
Respectfully submitted,
CARLSON TESTING, INC.
Reviewed By: Steven Dugger
Review Date: 09/1512008
RL/KMF