Daily Field Report
Client:
Mr. Wally McCollough
EWEB
, 500 E. 4th Ave.
Eugene, Oregon
Project:
Hayden Bridge Water Filtration
Plant Expansion
Springfield, Oregon
Date:
Project No.:
Report No.:
Inspector:
ID No.:
08-25 & 26-08
2087168
E-20992
A. Fenstermacher
5258882-49
Inspection of: Epoxy Dowels
Contractor: Wildish
Weather: ;Clear .
BP No.: lCOM2008.,00225 . )
Continuous Inspection: 0
Periodic Inspection: 0
08-25-08: Performed continuous inspection during the installation of seventeen (17)
#10 x 7' to 11' vertical rebar dowels into bedrock for north four (4) buttresses along east
side. Prior to installation, the predrilled holes were, cleaned with water and a vacuum.
Dowels were secured with Epcon A7 (ICC-ES ESR- 6582, expiration date 11-07-09).
Verified minimum embedment of 2'.
08-26-08: Performed continuous inspection during the installation of eight (8) #10 x 11'
vertical dowels into south two (2) buttresses and ten (10) #4 x 24" horizontal dowels
into existing southeast buttress. Prior to installation, the predrilled holes were cleaned
with water and a vacuum. Verified minimum embedment of 2' for #10 bars and 6" for
#4 bars. Dowels were secured with Epcon A7 (ICC-ES ESR- 6582 expiration date 11-
07-09).
Jake (Wildish) was asked to notify our office when additional services are needed.
To the best of our knowledge, the work inspected was in accordance with plans dated
02/2008 and applicable workmanship provisions of the I.B.C., except if noted above.
Reviewed By:
/h.'1;.~
Michael L. -M,f,Jr
Technical Manager
c: EWEB- Mike Stickling (em ail)
EWEB- Wally ~cCullough (em ail)
OBEC- Pete Slocum (em ail)
Wildish Building Co.- Kevin Fitzjarrell (email)
Wildish Building Co.- Jake Stucky (em ail)
City of Springfield
MLM:sc
This report andfor enclosed test data is the confidential property of the client to whom it is addressed and pertains to the specific
process and/or material evaluated. As'such, infonnation contained herein shall not be reproduced in part orfull.and/or any part
thereof be disclosed without FEI Testing & Inspection, Inc.'s written authorization,
7ffJ NN ComeII Avenue' Corvalis, Qegon S7330' phone (541) 757-4698, fax (541) 757-2991
29540 BAirport Road, Eugene, Qegon 97402, phone (541)684J849 . fax (541 )684'3851
630ffJ'Corporate Place, Suite 2 . Bend, O.regon 97701 . phone (541) 382-4844 . fax (541) 382-4846
i:.., .,.' .,- .::~
'~.....
~~r!:l.
1I.""'ll".""mlllJ'.til. Gvu~', d &Construcli:ln Servioes
Page 1 of 1
Field Density Test Results - ASTM D 2922 .
Client: EWEB
500 E. 4th Ave.
Eugene, Oregon 97440
Project: Hayden Bridge Water Filtration
Plant Expansion
Springfield, Oregon
Date:
Project No;:
Report No.:
B.P. No.:
08-15-08
2087168
E-20914
MOISTURE/DENSITY DATA: ASTM 0698 - Maximum Dry Density of 129.5 pcf, at 11% moisture, is from our sample no.
1934 dated 08-15-08 for Wildish 3/4"-0 crushed gravel.
-_.~"-- - ..- -- .-
Wet
Test Approximate Location Approx. Density Percent Dry Density Percent Compaction
No. Elev. (pct) Moisture (pct) Compaction Requirement
1 Near south end FG 141.2 5.3 134.1 100+ 95.0
2 Near center FG 134.2 5.9 126.7 98.0 95.0
3 Near north end FG 132.8 6.3 125.0 97.0 95.0
-- .-
Tests performed at finished grade of base rock under east wall contact basin footing.
Remarks: Mike Stickling (EWEB) was advised of test results.
Reviewed By:
/h. ~~---
Michael L. Me#~
Technical Manager
c: EWEB- Mike Stickling (email)
EWEB- Wally McCullough (email)
OBEC- Pete Slocum (email)
Wildish Building Co.- Kevin Fitzjarrell (email)
Wildish Building CO.- Jake Stucky (email)
City of Springfield
Attachment: Moisture/density curve
MLM:sc
This report andJor enclosed test data is the confidential property of the client to whom it i<,; addressed and pertains to the specific process and/or material evaluated. As, such, information
contained herein shall not be reproduced in part offull andlor any part tbereofbe disclosed without FEI Testing & Inspection, Inc.'s written authorization.
70iJ NW CcmellA.mue' Comillis, Oregoo 97330, (kne (54 I ) 757-4fE8 . fux(541) 757-2991
29540BAitportRood' Eugene, Oregon 97402 'jirne(54!)6ll4-'3849 'fux(541)6ll4-'3851
. 63050 Corporate Place, Suite 2 . Bend, Oregon 97701' phone (541) 3824844 . fax (541)3824846
L~ .:..
131
MOISTURE-DENSITY RELATIONSHIP TEST
.1
12f
"'-.......
. ~ "
j "
'0 1271
a.
~
'in
c:
Q)
'tJ
c=-
o
I
I
(
I
I
J
I
,
,
/
.I
I
I
J
'\"
....
12C
122
I
1211
5
"
11
Water content, %
13
15
17
Test specification:. ASTM D 698-00a Method C Standard
Elev/
Depth
Classification
USCS AASHTO
Nat. .
Moist.
Sp.G.
II
PI
%>
%<
3/4 in.
NO.200
TEST RESULTS
Maximum dry density = 129.5 pef
Optimum moisture = 11 %
Project No. 2087168 Client: EWEB
Project: Hayden Bridg~ Filtration
MATERIAL DESCRIPTION
3/4" - 0 crushed gravel
Date: 8-15-08
. Source: Wildish Sand & Gravel Sample No.: 1934
MOISTURE-DENSITY RELATIONSHIP TEST
I FEI TESTING AND INSPECTION, INC. I
Remarks:
I Sample was obtained by FEI representative
I from stockpile on- site on 8-15-08.
Figure No.
l{!si..~t~7!:~~
Engineering. Consuiiing . Testing
DAILY FIELD REPORT
Date performed:
Client:
July 29, ?008
Accts Payable
EWES,
,
PO Box ,10148
Eugene,i.OR 97440
Report Number:
722-80118-14
Project Name:
Hayden Bridge
Project Location:
Eugene, Oregon
B.P. No.:
Type of Inspection:
Reinforced Concrete
P.O. No.:
Weather:
027280 .
Overcast
Field Observations and Comments
Specific placement locations: saddles under back wash section line. Casl one (1) set of four (4) (4x8) concrete test
cylinders. Contractor was asked tonolify our office when additional services are needed. To the best of our 'knowledge,
the work inspected above is in accordance with. the building department approved design drawings, specifications and
applicable workmanship provisions ofthe International Building Codes.
. lyoe of Materi:ll ~
Supplier Knife River
Mix # 2400NE7100
~ump ~
Air Cont~nt 3.5%
AmbienfTemperature 62.60
MateriafTemperature 78.40
Time Placed 12:15 PM
Design Strength (psi) 4,000
Number !ill Samples 4
Total Yardage Placed 3
Inspector: Pete Furlong
CCB #176269
. I
If you have any questions regarding this report, please feel free to contact us at 541-746-9649.
Respectfully Su
~~~
'Davld Smith
Branch Manager
us/rleS, Inc.
c: EWEB - wally.mccullough@eweb.eugene.or.us
City of Springfield - rcastile@cLspringfield.or.us
OSEC . pgs@obec.com
r
THIS REPORT IS PROVIDED FOR THE INFD~T10N OFTHE"CUENT DNL Y. THe REPRODUCTION OF THIS REPORT. BY ANY METHOD, AND ITS TRANSMITTAL TO Ii THIRD
PARTY, BY ANYMEANS. EXCEF-T IN FI.A..L, wrrHOUTTHE WRITTEN PERMISSION OF PROFESSIONAL SERVICE INDUSTRIES, IS PROHIBITED.
Professional Service Industries, Inc. .104D-A She/Jey Street. Springfleld"OR 97477. Phone 541n46.9649 . Fax 541/746-7163
l rA j:;ZIrI!onnation
. ~~,. .To Build On
Engineering. Consuning. .. Testing
DAILY FIELD REPORT
Date Performed: July 8, 2008 Report Number: 722-80118-13
Client: .Aects Payable, Project.i'Jame: Hayden Bridge
EWEB "
PO Box ,,1 0148 Project Location:
Eugene,:OR 97440 Eugene, Oregon
B.P, No.: P.O. No.: 027280
Type of Inspection: Rebar Locate Weather: Clear
Field Observations and Comments
As requested.a PSI represen:ative was on-site at EWEB's Hayden Bridge Water Treatment facility to locate rebar a1
- south back wash pump for discharge piping wall bracket. To the best of bur knowledge,the' work inspected above was
in accordance with 1he building department approved design drawings, specificalions and applicable workmanship
provisions of 1he International Buildinq Code's.
Inspector: Pete Furlong
CCB#176269
If you have any questions regaraingthis report, please feel free to contact us at 541-746:9649.
Respectiully Submitted,
i)~~:et-\1!stries, Inc.
David Smith
Branch Manager
\.
. J " ,,0"
c: EWES: wally:meeuIlDugh@eweb.eugene.or.us
City of Springfieid - rcastiie@cLspringfield.or.us
OBEe . pgs@obec.eom .
THIS REPORT IS PROVIDED FOR THE INFORMATION OF THE CUENT ONLY. THl! REPRODUCTION OF THIS REPORT, (3Y ANYMETHOD, AND fTS TRANSMITTAL ro A THIRD
PARTY. BY ANY MEANS, EXCEPT IN FUll., WiTHOUT THE WRITTEN PERMISSION OF_ PROFESSIONAL SERVICE INDUSTRIES, is PROHIBITED.
, .
Professional Service In:pusmes, Ir;c.. 1040.A Shelley Street. Springfield, OR 974n. Ph~ne 541/740-9649. Fax 541174!J:.7163
, :::
~.......
~~tCt
Page 1 of 1
'1~'II~ICl:<lIlf~'~~.IIII~_
.Gb.,u-..; " ,;CaJ & Construdion Servires
Daily Field Report
Client: EWEB Project: Hayden Bridge Water Filtration Date: 09-02-08
500E. 4th Ave. Plant Expansion Project No.: 2087168
Eugene, Oregon Springfield, Oregon Report No.: E-21 052
Inspector: A. Fenstermacher
10 No.: 5258882-49
ICC
Inspection of: Reinforcing Steel Weather: Clear Continuous Inspection: 0
Contractor: Wildish BP No.: Pending Periodic Inspection: 0
Performed preliminary inspection on the reinforcing steel for contact basin east
buttresses, east and north perimeter walls, all from ground to bottom'of slab elevation.
Reinforcing steel was checked for size, grade, laps', quantities, locations, ties and
supports. .Note: not all forms were in place arid clearances will need to be
verified. A final inspection will be performed prior to concrete placement.
To the best of our knowledge, the work in-progress was in accordance with plans dated
02/2008 and applicable workmanship provisions of the I.B.C., except if noted above.
Reviewed By:
~~~Z
Technical Manager
c: EWEB- Mike Stickling (email)
EWEB- Wally McCullough (email)
OBEC- Pete Slocum (email)
Wildish Building Co.- Kevin Fitzjarrell (em ail)
Wildish Building Co.- Jake Stucky (email)
City of Springfield
MLM:sc
This report and/or enclosed test data is the confidential property of the client to whom it is addressed and pertains to the specific
process and/or material evaluated. As such, information contained herein'shall not be reproduced in part or full and/or any part
th~reof be disclosed without FEI Testing & Inspection, Inc.'s 'Nf'itten authorization.